Three Phase Mystery Solved, No Neutral Required in a Balanced Load?

แชร์
ฝัง
  • เผยแพร่เมื่อ 20 พ.ย. 2024

ความคิดเห็น • 234

  • @Sergey3023
    @Sergey3023 4 ปีที่แล้ว +12

    OMG.Just found your channel and can't fully describe how easier its for me to understand stuff that I've been taught with City and Guilds. Absolutely brilliant ,thank you!

  • @100greenoranges
    @100greenoranges หลายเดือนก่อน

    I have tried to understand this concept at least 10 separate times over the years. The missing piece was that the other end of the circuits were connected to each other. I now also understand Y and delta configurations. It's the simple things that other educational content skips that make it difficult for a complete newb to understand. Thank you!

  • @no_short_circuit
    @no_short_circuit 5 ปีที่แล้ว +18

    Thanks Joe. 3 phase has always mystified me but with your videos I'm getting nearer understanding it all.

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  5 ปีที่แล้ว +3

      Glad they're helping. As always if you have any questions or suggestions for future videos let me know!

  • @ahmedfayez4596
    @ahmedfayez4596 3 ปีที่แล้ว +3

    Thank you Sir for this amazing video.
    I am a junior biomedical engineer working on Xray machines. I have noticed that we are not connecting the neutral line in the generator and i was wondering why. Just watched this video and you explained it!
    Appreciate it.

  • @shamanking5195
    @shamanking5195 10 หลายเดือนก่อน +1

    Hi Joe.
    We have a motor that was recently rewound, full service done to it.
    But when we installed it is pulling high amps in two phases only.
    supply voltage = 460
    motor amp rating = 283
    voltage phase to ground
    phase A =279
    phase B = 280
    phase C = 282
    amps per phase
    phase A= 277.0 amps
    phase B = 296.0 amps
    phase C = 286.0 amps
    we are using a soft starter to get the motor up to speed , once the motor is at full speed a
    bypass contactor is energized and from that moment On the soft starter is only waiting for the stop command
    we are going across the line with the contactor.
    We suspected the bypass contactor was faulty and causing the high amps , but when we inspected the contactor it was in good
    condition , it worked properly.
    We checked for loose connections and found none .
    motor and cables Megged good.
    There is not enough imbalance to cause the problem.
    Any idea what could be causing this problem ???.

  • @neilholmes1275
    @neilholmes1275 2 ปีที่แล้ว

    Did wonder about this yesterday, I'm not an electrician but wondered how a 3 phase SWA cable could get away with a neutral that wasn't 3 times the size of the lives. Read some text that explained it but no where near as well as your video. Brilliant.Thanks

  • @tedlahm5740
    @tedlahm5740 5 ปีที่แล้ว +12

    But we did need the neutral with two phase of usage, as well as single phase.
    Very well presented video. Thank you.

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  5 ปีที่แล้ว +4

      Spot on Ted, you may remember from the previous video though that when we removed the neutral connection for two lamps they dimmed, I'll explain this in a future video!

    • @xerxes456
      @xerxes456 4 ปีที่แล้ว +1

      @@JoeRobinsonTraining could you use square root of 2 that give you lower voltage?

    • @tedlahm5740
      @tedlahm5740 ปีที่แล้ว

      @@JoeRobinsonTraining Joe: revisiting this subject 3 years latter.
      Still a Learner. Does the VOLTAGE jump up on 3 phase open neutral
      on the individual legs with ONE LEG no longer has no load?
      P.S. You do not look a day older.

  • @m0nkeytr0uble
    @m0nkeytr0uble 4 ปีที่แล้ว +5

    just found your channel and as i just started my apprenticeship in germany this is really helping filling in the gaps of the language barrier. so far one of the best explanations ive found and easily put across so thank you dude

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  4 ปีที่แล้ว +3

      Ah great to know, glad the content is helping and thanks for commenting. 👍

    • @PunmasterSTP
      @PunmasterSTP 2 ปีที่แล้ว

      How has your apprenticeship been going?

  • @keitho77
    @keitho77 5 ปีที่แล้ว +9

    Excellent video Joe. Very clear and concise explanation. No wonder I Subscribed!!

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  5 ปีที่แล้ว +3

      Glad it came across that way. Plenty more on the way so stay tuned!

  • @smokinpea
    @smokinpea 3 ปีที่แล้ว +1

    Just came across your channel & found this video super clear & extremely helpful (my apprenticeship, in the UK, finished over 30 years ago & since then I have had no exposure to 3-phase systems). Now in Gemany I have a 3kw immersion heater element, of the 400v 3-phase variety, to install at home. No info came with it & I can find nothing online (happy days!). From a visual inspection of its internal connections it is STAR configured, with 3 individual heating elements - one per phase. I have measured the resistance of each individual heating element/phase (i.e. to the neutral point) & they are all the same. I understand that this then represents a 'balanced load' scenario, and thus does not need the Neutral line to be connected. My question is, is there any disadvantage of connecting the Neural line if it is already there/available to do so? I don't beleive that there is but... Thanks ever so in advance for clarifying this.

  • @esfae8250
    @esfae8250 5 ปีที่แล้ว +13

    Hello Joe, Outstanding Video. Very informative and a great training tool.

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  5 ปีที่แล้ว +5

      Thank you kindly, there's more to come so stay tuned!

  • @midkort
    @midkort 3 ปีที่แล้ว +5

    This is a great explanation. I appreciate the fact that your explanation uses the actual goings on in the circuit. This really helps me understand - as opposed to just believing - how the circuits operate. Thank you!
    You just gained a subscriber.

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  3 ปีที่แล้ว +2

      Good to hear. I'm really glad the video helps. 😊

  • @sparky9378
    @sparky9378 5 ปีที่แล้ว +10

    Fantastic video joe thanks

  • @gbelectricks
    @gbelectricks 5 ปีที่แล้ว +9

    Excellent video again joe. I watched the first one a while ago, could you not leave it so long for the next instalment!! The suspense is killing me😄👍

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  5 ปีที่แล้ว +4

      😂 Sorry Gareth, it was an absolute monster of an edit. Next three phase video should drop next Wednesday. Thanks for the support! 👍

  • @DaftSwank
    @DaftSwank 4 ปีที่แล้ว +2

    This is brilliant stuff. Thank you! I wish Joe Robinson and TH-cam were around back when I was in Uni!

  • @LSF315
    @LSF315 5 ปีที่แล้ว +12

    Great video, Joe. Mystery solved although it seems too simple! I guess the way to look at it is that any wave form above the axis line is a positive figure and any value below the wave form is a negative figure; add these three up and you have the value of zero?

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  5 ปีที่แล้ว +5

      It pretty much is that simple and you've totally got the point of the positive and negative values. It gets a little trickier when we start looking at imbalanced three phase loads. Stay tuned for next week's video!

    • @LSF315
      @LSF315 5 ปีที่แล้ว +3

      Joe Robinson Training brilliant; can’t wait.

  • @brightspark263
    @brightspark263 5 ปีที่แล้ว +15

    Great video as always Joe, it's really helping my understanding of 3-phase supplies. I've always found 3-phase a fascinating subject, these videos are perfect for anyone trying to understand the underlying principles behind it.

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  5 ปีที่แล้ว +5

      Thanks for the nice comment, I'm glad they're helpful. The edit on this one was a nightmare so glad it wasn't in vain! Stay tuned for more...

  • @edwindelfin7923
    @edwindelfin7923 4 ปีที่แล้ว +8

    Amazing explanation. I have a question, there are loads that require two phases, for example an air conditioner or a 220 V luminaire. This type of load does not require a neutral conductor, where does the current return to? How does this kind of system work? Can you make a video about it, please? Thank you! Greetings from Mexico, you've been my best teacher so far!

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  4 ปีที่แล้ว +3

      Ah, thanks for the kind comment Edwin. In a two phase circuit the current just passes down one phase and back down the other before it changes direction.

    • @smacool2975
      @smacool2975 2 ปีที่แล้ว +1

      @@JoeRobinsonTraining Would you mind explain the answer further, I didn't unfortunately get the answer.

    • @deang5622
      @deang5622 ปีที่แล้ว +1

      ​@@smacool2975 You have two conductors connected to the load.
      In order for electricity to flow, there must be a continuous unbroken loop for the electricity to flow on. It starts off from the voltage source, travels along the conductor to the load, passes through the load and then returns down the second conductor back to the voltage source.
      That is all there is to it.

  • @Andrew-hu9ke
    @Andrew-hu9ke 3 ปีที่แล้ว +2

    Excellent presenter and teacher - Thank you Joe 👍

  • @mohamedkhalid7708
    @mohamedkhalid7708 ปีที่แล้ว

    This is the easiest explanation that I came across so far. Thank you very much. Superb!

  • @leoleorelated
    @leoleorelated 5 ปีที่แล้ว +6

    Really valuable due to the work I’m currently doing, thankyou👍🏾

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  5 ปีที่แล้ว +1

      My absolute pleasure Leo, stay tuned to get ahead for next week!

  • @kruzzah
    @kruzzah 4 ปีที่แล้ว +2

    Really nice n simple.
    Plz ur support for my question which is,
    If it says 3ph generator has 120amps capacity, does it mean that each phase will provide 120amps or each phase will provide 40amps?

  • @vanderpant2116
    @vanderpant2116 5 ปีที่แล้ว +6

    Great vid, like all your other vids are, your ability to convey your knowledge in a simple easy to understand way is exceptional.

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  5 ปีที่แล้ว +4

      Aw, thanks for the kind comment 😊 just hoping the videos help people out. Stay tuned for more!

  • @shahedkhan-bx1iw
    @shahedkhan-bx1iw ปีที่แล้ว

    your practical explanation way more specific than any others
    I need a practical explanation about Filter from you. Like you so much❤❤❤❤

  • @devonsalmon7554
    @devonsalmon7554 3 ปีที่แล้ว +1

    Hello I like your videos. You put them across so that most people can understand. There is a circuit that I would like you to do for a group of us.
    We would like you to show us a lift station with a high float and a low float switch. How I want it to operate is, when the water, sewage or any liquid rises it turn on the low float but the motor does not start until the water or sewage reaches the high float. When the water is pumped out the motor does not stopped until the water is down to the lower float.
    Thanks in advance.

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  3 ปีที่แล้ว +1

      Sounds intriguing, il add it to my to do list. 👍

  • @thapelogerald6754
    @thapelogerald6754 3 ปีที่แล้ว

    1.If i may ask, what causes the high/low voltage and how do you solve the problem?
    2.What causes shocking taps and how do you resolve it?

  • @vievlogs589
    @vievlogs589 5 ปีที่แล้ว +5

    Time to learn with Joe 📚

  • @oblu43
    @oblu43 4 ปีที่แล้ว

    Excellent Way of presentation.....Three Phase Concepts made explicitly simple....Appreciated..

  • @79brumley
    @79brumley 3 ปีที่แล้ว +2

    Omg this video is absolutely amazing, Helped me soo much in my AC principles class.

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  3 ปีที่แล้ว

      Great to know. Make sure you check out my other videos. 👍

  • @Galmm-ub2dc
    @Galmm-ub2dc 4 หลายเดือนก่อน

    I glad if you answer me on a question, why the current was 8.4 amps when l1 and l2 were connected without l3?
    Thanks in advance 🙏

  • @simonabel6869
    @simonabel6869 5 ปีที่แล้ว +8

    Great video, keep the three phase one's come.

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  5 ปีที่แล้ว +2

      Thanks Simon, next week's video is a three phase one as well. 👍

  • @mohammadsamir2713
    @mohammadsamir2713 3 ปีที่แล้ว +2

    Actually one of the best explanations, but with a greater explanation always comes more questions, you said that the current at the neutral point will be always zero, and you thankfully proved it by experiment, so there is the question "how could we get 8.4 amps in the lines before the heater while at the other end (the neutral point) has zero amps ?", it doesn't make sense to me as it means there is no charge carriers moving at all, they stop each other

    • @dimitrisblane6368
      @dimitrisblane6368 8 หลายเดือนก่อน

      They don't stop each other. They sort of "push/pull" each other at the other side of the load so it's always zero. As the 3-phase graph describes. You could think of it with the water example. At one point in time motor 1 might be pushing 5 litres of water, while motor 2 is sucking 3 litres and motor 3 is sucking 2 litres.
      The current from one phase will go through the load and then balance out with whatever the currents on the other 2 phases are doing cause they are in perfect balance.

  • @moisty254
    @moisty254 3 ปีที่แล้ว +1

    That 3 phase current cancelling example finally cleared the air for me after all these years on no need for neutral on balanced load, thanks!
    Got a question though- the electrons still need to return to their source, so at any given degree of rotation is the electrons flowing down the respective phases in the opposing directions back to the source?

    • @serpaolo7413
      @serpaolo7413 2 ปีที่แล้ว

      I have the same question? Any answer?

  • @rjpoonia717
    @rjpoonia717 ปีที่แล้ว

    Great Explanation, simplified to the maximum and easy to understand.

  • @PunmasterSTP
    @PunmasterSTP 2 ปีที่แล้ว +2

    No neutral required? More like "The amount of knowledge conveyed in these videos is wild!" Thanks for making and sharing them.

  • @Koggy9
    @Koggy9 2 ปีที่แล้ว +1

    Great video and makes sense when you have 3 balanced loads, but (unless I'm missing it) there isn't an explanation as to why when loads are only on L1 and L2 that the current in the neutral is the same as the individual loads? Sorry, new to this so might be a dumb question?

  • @any_one4255
    @any_one4255 4 ปีที่แล้ว +1

    You cleared my long time doubt so quick... @ motor winding... Y they are connected together

  • @ravindulakshan770
    @ravindulakshan770 3 ปีที่แล้ว +1

    Many many thanks sir... I was trying to understand about three phase. Finally, I got it..

  • @ulamichalczyk4216
    @ulamichalczyk4216 หลายเดือนก่อน

    I have a three phase 20A cirucit breaker, supplying three different single phase loads: stove, oven and microwave oven. Can the neutral conductor will be the same size as phase conductors?

  • @turbotrana
    @turbotrana 3 ปีที่แล้ว +1

    I've always wondered about this and you answered beautifully.

  • @lst080956
    @lst080956 9 หลายเดือนก่อน

    Thanks very much.
    Check with you, does RCB without neutral.

  • @randomjack477
    @randomjack477 7 หลายเดือนก่อน

    About the zero current, Can we think of it in terms Kirchhoff's current law? Not only when at peak values , but also at different points indicated by the graph, where we can add or subtract the 3 phase(r,y,b) values depending on whether it is in the Positive(up/forward) or Negative(down/negative).

  • @brentkelly5445
    @brentkelly5445 2 ปีที่แล้ว +1

    ty for that clarity. The only thing I don't see is at the 10:35 mark the total is a clear as day. 8-4-4=0. When you had 2 legs on it was 8 on the neutral. However when you pick any point on that waveform and try to match A + B they don't add up to 8 all the time. say for instance at the line you inserted. The red phase is 8 but either of the other 2 are -4. 8-4=4

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  2 ปีที่แล้ว

      It's the same principle as a single phase sine wave, it will have a different value at different points. What you're looking for is the rms value of the wave form. 👍

    • @brentkelly5445
      @brentkelly5445 2 ปีที่แล้ว +1

      @@JoeRobinsonTraining ty . one more question if you have the time. It would be almost impossible ,yes?, to have a panel balanced at any one moment. Thus there is always an amount of unbalanced current running back to the panel neutral, and from there to??? back through the service?
      Also in your example here if you touch the neutral in the balanced state you are fine. if you touch in when one heater is on .... you are toast?

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  2 ปีที่แล้ว

      @@brentkelly5445 it depends on the type of loads connected to the panel really. If you've got three phase motors it should be almost perfectly balanced, many three phase motors have no neutral for this reason. If you've got lots of different single phase loads, lighting, sockets etc., it's almost impossible to get it balanced.
      Touching the neutral is different as it's the voltage between neutral and earth that causes a shock, in theory you shouldn't get a shock from either a balanced or an unbalanced neutral, but as it's classed as a live conductor you'd NEVER want to touch it as things do go wrong and you could get a shock. Hope that helps. 😊

    • @brentkelly5445
      @brentkelly5445 2 ปีที่แล้ว

      @@JoeRobinsonTraining ah yes ty. because the neutral to ground is less resistance than me.

  • @peterdelapena8713
    @peterdelapena8713 2 ปีที่แล้ว

    excellent video. clear and precise. straightforward and easy to understand.

  • @siddhat7802
    @siddhat7802 4 ปีที่แล้ว +2

    Informative series of videos. It is great to see how you build up the concepts one after the other.

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  4 ปีที่แล้ว +2

      Thanks very much, you can understand anything if you take the right steps. 👍

  • @a_l7515
    @a_l7515 5 ปีที่แล้ว +7

    Great video joe

  • @kaokaoylan4510
    @kaokaoylan4510 3 ปีที่แล้ว +1

    Marvelous teaching, my local lecturer only did throwing equations and electrical diagrams at my face...

  • @AlanLumsden
    @AlanLumsden 5 ปีที่แล้ว +4

    Great video Joe 👍 Prime mover comes to mind...

  • @64NVG
    @64NVG 9 หลายเดือนก่อน

    Thanks a lot for the efforts taken to produce this very valuable content! I have two questions and hope you can clarify.
    1. Even though loads are balanced, the current must flow through closed path and hence at any moment, current from one phase gets split and flows through other two phases. Is this correct?
    2. In typical medium voltage distribution system, there is never a neutral, and the loads connected could be far from balanced. How does the net current (vector sum of all three phase currents) flow in this case? Does it flow through other phases as in case of balanced loads? If yes, then how get current in neutral in this video?
    Thanks a lot again for your time!

  • @n4thb4dc0
    @n4thb4dc0 5 ปีที่แล้ว +6

    Another great video 👍🏻👍🏻👍🏻

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  5 ปีที่แล้ว +2

      Thanks very much for commenting, stay tuned for more!

  • @vipinv8004
    @vipinv8004 4 ปีที่แล้ว +1

    Great explanation. I wish i had a teacher like you....

  • @KannanKannan-om9ln
    @KannanKannan-om9ln 4 ปีที่แล้ว +1

    I have seen 1000 video.But your videos are my life.

  • @g00glian0
    @g00glian0 4 ปีที่แล้ว

    Amazing how simple you made that to understand. So cool to understand this now!

  • @nolwazibridget3716
    @nolwazibridget3716 4 ปีที่แล้ว +2

    Joe thanks for making this video... Can I please get clarity why did u read 8.2A on the neutral when L1 and L2 was on???

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  4 ปีที่แล้ว

      Great question, stay tuned for a future video. 👍

    • @okud5850
      @okud5850 3 ปีที่แล้ว

      @@JoeRobinsonTraining has this video been made?

  • @baseball1441
    @baseball1441 2 ปีที่แล้ว

    Great Video! Can you explain how if you remove the neutral reference in this balanced load you still have coil to ground or coil to neutral voltage?
    In the US we commonly use a 120/208 Y system in commercial buildings.
    If I lose that reference why are my single phase loads not getting 208?
    Obviously if you take a voltage reading between any phase to a different phase its 208.

  • @johnreymaliao3352
    @johnreymaliao3352 ปีที่แล้ว

    Can you please make a video of 3 phase motor and explain the relation of the current drawn in low- high speed or wye-delta..

  • @Richard-fp1mk
    @Richard-fp1mk 2 ปีที่แล้ว

    Brilliant explanation. Something I've been looking for in a long time.

  • @waleedmohi356
    @waleedmohi356 3 ปีที่แล้ว

    very good,theoretical and practical

  • @sadiarehman9175
    @sadiarehman9175 4 ปีที่แล้ว +1

    Excellent Graphics ... Good work. Which is this Device in your hand ?? Measures what other parameters ??

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  4 ปีที่แล้ว +1

      It's a clamp meter. Measures current voltage and other things.

  • @coolminded850
    @coolminded850 3 ปีที่แล้ว +1

    Awesome explanation. Thanks a lot for sharing such a valuable and highly practical content.

  • @TheBigstve
    @TheBigstve หลายเดือนก่อน

    Thats becauae the neutral current is the inverted vector sum of the line/phase currents.
    Brilliant, keep up the good work fella

  • @wagabira
    @wagabira 2 ปีที่แล้ว

    wow, that's crazy stuff. I must be on my 3OTH video. great information and very well explained. thanks a million

  • @peterburger69247
    @peterburger69247 2 หลายเดือนก่อน

    If a 3 phase hot water system with no neutral dropped a phase due to a fuse blowing. Can you continue to use the hot water system? Is it dangerous?

  • @mohamedabdelmonem6468
    @mohamedabdelmonem6468 ปีที่แล้ว +1

    Beautifully explained ....Thanks

  • @mohamedyuszal8189
    @mohamedyuszal8189 ปีที่แล้ว

    Thank you so much for this amazing and direct video.
    Definitely looking forward to more videos from you

  • @krishath7085
    @krishath7085 2 ปีที่แล้ว

    Awesome tutorial. Many thanks Joe

  • @malachygallagher4936
    @malachygallagher4936 ปีที่แล้ว

    Hi Joe.
    Excellent!
    Can you do a video on bonded or floating neutrals on generators & if Earth rods are required?(TNCS)
    Regards mg.

  • @alexsotelo7176
    @alexsotelo7176 2 ปีที่แล้ว

    This video has answered so many of my questions

  • @srihaanshbobbili2781
    @srihaanshbobbili2781 3 ปีที่แล้ว

    Hello Joe,
    What is the voltage between the live wire and the neutral wire for three-phase four-wire.

  • @TheInkBuildUp
    @TheInkBuildUp 9 หลายเดือนก่อน

    Finally a video that made things more clear. 10:28 literally made say, "ooooooooooh. now I get it."

  • @lsnogaming2893
    @lsnogaming2893 5 ปีที่แล้ว +5

    Fantastic as always Sir 👍

  • @amrnassef5344
    @amrnassef5344 3 ปีที่แล้ว

    Thx for the video cleared some concepts for me, but quick question if the loads cancel each other out how does the electricity return to source, also and I know this might be quite stupid but if in this example we remove the neutral shouldn't the heaters still work because the is no return anyway?

  • @_stardust__
    @_stardust__ 3 ปีที่แล้ว +1

    Does connecting all the three phases together form a neutral point? Suppose, we take a mcb, connect 3 phases in its input and short the 3 output terminals and turn ON the mcb. What will happen? Will there be a short circuit or the common point of the mcb output will behave like a neutral point?

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  3 ปีที่แล้ว +1

      The answer is yes to all your questions. If you connect the outgoing terminals from the MCB they will create a neutral point but it will have the exact same effect as connecting the outgoing side of a single phase MCB to neutral, a short circuit and a huge bang! Don't do it! 😱

  • @Vector_Wong
    @Vector_Wong 3 ปีที่แล้ว

    Very understandable video about three phase thanks Joe

  • @plansimple9156
    @plansimple9156 2 ปีที่แล้ว

    Hi JR, than for the demo. If neutral is floating, and the load is not balance, what happened and what is expected? Are there any difference for the source is from utility Tx or UPS under discharge?

  • @hamzahmohamad2025
    @hamzahmohamad2025 4 ปีที่แล้ว +2

    Thanks for the great information on 3 phase. I just wondered if this is important to balance the loads that are connected to domestic electrical system. What happened if one phase is heavily wired up to many equipment/loads and one is much less. Will there any significant different with electrical bills ? Obviously it's very difficult to get equal loads in practice ie it always changes continuously throughout the the time.
    Thank you Joe for the reply.

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  4 ปีที่แล้ว +1

      Hi thanks for the comment and question. Unbalanced loads won't really affect energy bills but loading up one phase is inefficient, as the other conductors get underutilised and if poorly designed it could overheat the loaded phase.

    • @hamzahmohamad2025
      @hamzahmohamad2025 4 ปีที่แล้ว +2

      Thanks Joe. It would be nice if there is little gadget (like the clamp meter) in the market that can hooked up to all 3 phases to monitor the load. If you happen to know a good one would be nice to make a video of it. Great stuff.

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  4 ปีที่แล้ว +1

      Great idea, I'll see what I can do! 👍

  • @MrPress6
    @MrPress6 ปีที่แล้ว

    Fantastic example thank you

  • @JMKClassroom
    @JMKClassroom 3 ปีที่แล้ว

    Hi Joe your explanations are super clear ,can you do a video on a single phase max demand calculation of a building and a three phase max demand of a factory.

  • @bradmoore1247
    @bradmoore1247 4 ปีที่แล้ว

    Really great, I finally understand why.

  • @hadrizharif
    @hadrizharif 3 ปีที่แล้ว

    Joe, thanks for answering my curiosity! Great video and explanation

  • @antmerritt
    @antmerritt 5 ปีที่แล้ว +2

    Brilliantly put cheers buddy 😁👊👍

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  5 ปีที่แล้ว +2

      You're welcome Ant, thanks for the message, stay tuned for more!

  • @robinfrancis2911
    @robinfrancis2911 3 ปีที่แล้ว

    Great tutorial...apologies, I’m no electrician, but why is there not zero amps after connecting the 2nd phase?....and only when connecting the 3rd phase ?...I think I know the answer ...but not totally sure 🤔

  • @tylerarrigoni7700
    @tylerarrigoni7700 2 ปีที่แล้ว +1

    Nicely done!

  • @crozwayne
    @crozwayne 3 ปีที่แล้ว

    Excellent video, very informative for me, a non spark mech engineer who has to play with electricomagical angry pixies from time to time!

  • @Abdulrahman_M
    @Abdulrahman_M 2 ปีที่แล้ว +1

    Is there another way to have zero or close to zero current in the neutral other than balancing the loads?

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  2 ปีที่แล้ว +1

      Not really, the closer the currents are to each other in value the lower the neutral will be. You could have leading or lagging loads that would make a difference.

  • @nickh2799
    @nickh2799 2 ปีที่แล้ว

    This video was perfectly explained thank you sir

  • @WorldEngineersOnline
    @WorldEngineersOnline 2 ปีที่แล้ว +1

    Excellent explanation.

  • @williammcintosh6006
    @williammcintosh6006 5 ปีที่แล้ว +1

    Knocking it out the park Joe!

  • @amiznu
    @amiznu ปีที่แล้ว

    How do they create the dc power that powers the electro magnet within the generator?

  • @sidheekali3223
    @sidheekali3223 3 ปีที่แล้ว

    Thanks ❤ from India 🇮🇳

  • @ramuganesan
    @ramuganesan 4 ปีที่แล้ว

    sir, explain the operation of single phase generator and 3 phase generator. thanks in advance

  • @innovativeinfo7520
    @innovativeinfo7520 4 ปีที่แล้ว

    As there is no neutral wire is used in 3phase induction motor's connection.so what's the direction of current? In single phase current flows through load from Line to neutral wire. Is it that in 3 phase one phase acts as neutral

  • @EhsanulKarim-dn9fb
    @EhsanulKarim-dn9fb ปีที่แล้ว +1

    why did the neutral current with two motors on read 8.4 A?

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  ปีที่แล้ว

      Watch this video and try drawing it out! 😃
      th-cam.com/video/fHiaui-ROik/w-d-xo.html

  • @andersonpinesso2812
    @andersonpinesso2812 3 ปีที่แล้ว

    Thanks a lot for very good explanation

  • @swrdashy
    @swrdashy ปีที่แล้ว

    Thank you for your explanations...

  • @mikefox2379
    @mikefox2379 2 ปีที่แล้ว +1

    Is this a Wye or Delta 3 phase connection? I am assuming Wye because of the neutral current values you displayed.

  • @devotionz89
    @devotionz89 ปีที่แล้ว

    Hey, still confused. What do you mean by the currents meet and cancel each other out? I understand what the sine waves are showing but what is the logic or reasoning behind current having the ability to cancel each other if it’s a balanced load?

  • @mickuljatheseagull
    @mickuljatheseagull 3 ปีที่แล้ว +1

    Really rally good explanation

  • @philbasset7259
    @philbasset7259 5 ปีที่แล้ว +2

    Great videos Joe, your the only one covering the 3 phase, its obviously to technical for all the others 🙄 👍🏻

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  5 ปีที่แล้ว

      Thanks very much, I'm sure there's others who explain it better! New 3 phase video dropping today and it's a monster!

  • @Mr_ToR
    @Mr_ToR 2 ปีที่แล้ว +1

    I have a 3 phase no-neutral instant water heater from Siemens for the whole house. With the clamp meter, each line shows 27A current usage. How do I calculate power consumption? Since it is not using any neutral line, is it 230V x 27A = 6.2KW (x3) or is it 400V x 27A = 10.8KW (x 3). I tried to share a schematic but youtoube wont allow it. Well I actually know the asnwer, because I can also measure the light blinks on my electricity service power meter and I can see in realtime what my current power consumption is and it draws 230V x 27A = 6.2KW (x3) = 18.6KW.
    The question is why is it not 400V x 27A = 10.8KW (x 3) = 32.4KW since there is no neutral line involved?

    • @JoeRobinsonTraining
      @JoeRobinsonTraining  2 ปีที่แล้ว

      To calculate 3-phase power you do the square root of 3 multiplied by the line voltage multiplied by the line current. 😁

    • @Mr_ToR
      @Mr_ToR ปีที่แล้ว

      @@JoeRobinsonTraining Three line currents are: 31.08A, 17.86A, 17.83A. How can I calculate the total power when currents are different? The meter shows that this water heater is drawing 14.28kW with these currents. I would really appreciate any help on this.