Alarm Check Valve Assembly - ACV Complete Detail in Urdu/Hindi

แชร์
ฝัง
  • เผยแพร่เมื่อ 4 พ.ย. 2024

ความคิดเห็น • 85

  • @TanweerAhmed
    @TanweerAhmed  2 ปีที่แล้ว +1

    Riser Check Valve th-cam.com/video/A0TO8ZX96Aw/w-d-xo.html

  • @manishsharma-ip5hs
    @manishsharma-ip5hs ปีที่แล้ว +4

    such a great platform to learn thank u sir kindly teach us more.

  • @DivyaRajput2013
    @DivyaRajput2013 ปีที่แล้ว +2

    From Hindustan to Doha Qatar Jay ho super duper

  • @farrukhmahmood4099
    @farrukhmahmood4099 2 ปีที่แล้ว +1

    Tanveer bhai. Fire fighting pump ko bypass kasy krin gay. As ke video banyan detail k sath. Pump test nai krna ata ha mujhy

  • @rahilsayyed2339
    @rahilsayyed2339 2 ปีที่แล้ว +1

    Assalamualaikum sir
    Sir.. HVAC duct estimation ke liye kya karna hoga

    • @TanweerAhmed
      @TanweerAhmed  2 ปีที่แล้ว

      W.Salam,
      You have to duct area calculation as per drawing

  • @farrukhmahmood4099
    @farrukhmahmood4099 2 ปีที่แล้ว

    Assalamualkum. Allah aap ko dunya akhrat main kamyab krin or Allah aap sa deen ka kam lain

  • @deepakkhotkar9785
    @deepakkhotkar9785 2 ปีที่แล้ว +2

    Mind Blowing Boss... Salute

  • @zahidullah5724
    @zahidullah5724 2 ปีที่แล้ว +2

    Dear tanveer,
    As per NFPA in alarm check valve there have pressure switch.
    For low pressure you mention in this vedio 4 to 15 psi and for high pressure range set on how much PSI ? Please give a short answer...

    • @TanweerAhmed
      @TanweerAhmed  2 ปีที่แล้ว

      6psi pressure is normally used at pressure switch

    • @TanweerAhmed
      @TanweerAhmed  2 ปีที่แล้ว

      Minimum 4psi and maximum 15psi

    • @TanweerAhmed
      @TanweerAhmed  2 ปีที่แล้ว

      This pressure is used for tripping pressure switch

  • @taqirkan7712
    @taqirkan7712 2 ปีที่แล้ว +2

    AOA Tanveer Bhai...yeah bhi batayaa ga k (at the start of project) when we have architectural drawings ya phir agar covered area available ha ( let say a hospital / university/library etc) then how can we roughly calculate the tonnage requirements of the entire covered area ) ...Thank you

  • @AbidHussain-rv7ll
    @AbidHussain-rv7ll 2 ปีที่แล้ว +1

    Can we use Alarm check valve in stand pipe system. Is any requirement of nfpa regarding this. Please advise. As per my experience I haven't seen ACV with fire hose cabinet system

    • @TanweerAhmed
      @TanweerAhmed  2 ปีที่แล้ว +1

      This ACV used in automatic operating system like sprinklers systems while fire hose cabinet is manual operating system there no required

    • @AbidHussain-rv7ll
      @AbidHussain-rv7ll 2 ปีที่แล้ว +1

      @@TanweerAhmed Thank you so much. Appreciated .

    • @TanweerAhmed
      @TanweerAhmed  2 ปีที่แล้ว

      Welcome

  • @syedwakeel140
    @syedwakeel140 ปีที่แล้ว +1

    thank you for sharing worth information.

  • @PradeepKumar-ds5lc
    @PradeepKumar-ds5lc ปีที่แล้ว +1

    Sir 1 video banaey jis me pump room se le kar building 🏢 ke top tak jisme kitna Haider niklta hai pump se kaise kanection Kiya hua hai pipe line ka or besment ka video Daley
    Thanks 🙏

  • @farrukhmahmood4099
    @farrukhmahmood4099 2 ปีที่แล้ว

    ماشاء اللہ بہت خوب

  • @SyedSalman-s7x
    @SyedSalman-s7x ปีที่แล้ว

    If any tower having 20 floors and each floor consists 30 sprinkler means 20 x 30 = 600 sprinkler,
    If tower exceeds more than one!!
    Shall provide more than one icv Or need only one icv for more than one tower????

    • @TanweerAhmed
      @TanweerAhmed  ปีที่แล้ว

      What is icv?

    • @TanweerAhmed
      @TanweerAhmed  ปีที่แล้ว

      As per NFPA 13:2019, 4.5.1 The maximum floor area on any one floor to be protected by sprinklers supplied by anyone sprinkler system riser or
      combined system riser shall be as follows:
      (1) Light hazard - 52,000 ft2 (4830 m2)
      (2) Ordinary hazard - 52,000 ft2 (4830 m2). Therefore on any one floor, you can install one Zone Control Valve Assembly and sprinklers quantity to be calculated according to hazard recommended area.

  • @faridkhan-mf5xg
    @faridkhan-mf5xg 2 ปีที่แล้ว +1

    SIR THANKS. JAZAKALLAH

  • @rameshkannansubburam2822
    @rameshkannansubburam2822 3 หลายเดือนก่อน +1

    can you add english subtitle also it is helpful for all of us

  • @babugandhibose6663
    @babugandhibose6663 ปีที่แล้ว

    Very useful video thankyou sir 🙏

  • @rajeshkushwaha4902
    @rajeshkushwaha4902 7 หลายเดือนก่อน +1

    Sir moffler kis liye lagaya jata hai

    • @TanweerAhmed
      @TanweerAhmed  7 หลายเดือนก่อน

      It is used for sound reducing but where it is uses? Application

  • @ashrafsalafi
    @ashrafsalafi ปีที่แล้ว +1

    Good explanation

  • @vijaykumar-hh7hm
    @vijaykumar-hh7hm 2 ปีที่แล้ว

    Please post video design and working principle of water curtain

  • @dineshgautam5658
    @dineshgautam5658 ปีที่แล้ว +1

    Brother ham ko ek daut hain please confirm Karen Jo alarm check valve se Jo chamber mai watar jata hain to water pressure hold nahi hota hai continue Bell bajta hai aur pressure switch active rahta hain system normal nahi hota hai please confirm

    • @TanweerAhmed
      @TanweerAhmed  ปีที่แล้ว

      There is mistake in installation of assembly. Follow the assembly of ACV accordingly to manufacturers drawing recommendations. Drawing always given in catalogue of ACV assembly. Recheck the assembly according to drawing and install accordingly. If installation is correct then accessories may be some fault/error.

    • @dineshgautam5658
      @dineshgautam5658 ปีที่แล้ว +1

      @@TanweerAhmedbrother mistake toh kuch hai lekin pata nahi chalrah hai , lekin jab check valve ka 1/2" valve open karte hai to water direct chamber me jata hai aur fir waha se sedha gong Bell bajta hai fir watar dren hota hai continue 👉 chamber me toh koi koi watar dren point nahi hai please confirm

    • @TanweerAhmed
      @TanweerAhmed  ปีที่แล้ว

      @@dineshgautam5658 Water will drain continue from the chamber then the mechanical bell will start because the gong works with the flow of water. If you want to close the bell then its valve has to close manually.

    • @dineshgautam5658
      @dineshgautam5658 ปีที่แล้ว +1

      @@TanweerAhmed ok brother I got your point but we need to open All times the chamber Valve if not open the valve pressure switch not going to rest in the fire alarm control panel please confirm

    • @TanweerAhmed
      @TanweerAhmed  ปีที่แล้ว

      @@dineshgautam5658 It will be reset when the water flows from the ACV assembly will stop. If water is flowing through the assembly then it will continuously run gong and also signals will transfer to FACP. You can reset either manually by closing the valve of the assembly where water is going to a gong or stop flowing water from the ACV assembly.

  • @sahidahmed8092
    @sahidahmed8092 หลายเดือนก่อน +1

    Assalamualaikum bhai jan acv ki back site per jo Mattel ka pipe gaya hai yah kya hai

    • @TanweerAhmed
      @TanweerAhmed  หลายเดือนก่อน

      W.Salam, what do you want say?

  • @Shaaz_Line
    @Shaaz_Line 2 ปีที่แล้ว

    hello engr,
    can we use grooved type instead of flange type, is there any nfpa requirements on this regards

    • @TanweerAhmed
      @TanweerAhmed  2 ปีที่แล้ว

      Yes you can use

    • @Shaaz_Line
      @Shaaz_Line 2 ปีที่แล้ว

      @@TanweerAhmed our project spec demands for using flange type, but we installed groove type. So do we have any nfpa reference for this, so client will accept our installation

    • @TanweerAhmed
      @TanweerAhmed  2 ปีที่แล้ว

      @@Shaaz_Line NFPA requirements is pressure and these both types are allowed to use but according to project aspect point of view should follow specifications. If you change any thing from contract then should get approval before change anything from approving authority

  • @azadmohmmad2721
    @azadmohmmad2721 ปีที่แล้ว +1

    Assalam alikum sr Darin karne par fire alarm system Nahi sound karta ha kiu

    • @TanweerAhmed
      @TanweerAhmed  ปีที่แล้ว

      W.Salam,
      Alarm Check valve (ACV) assembly's alarm activate when this ACV open. When water flow from pump to sprinklers then ACV opens. Now you have to check the location of drain valve then you will understand.

  • @editlab7128
    @editlab7128 ปีที่แล้ว +1

    You are great of the fire fitting engr🐵

  • @younusali8459
    @younusali8459 10 หลายเดือนก่อน +1

    Thanks

  • @joydevmondol9170
    @joydevmondol9170 ปีที่แล้ว +1

    Valve inspection Alarm problem plz help

    • @joydevmondol9170
      @joydevmondol9170 ปีที่แล้ว

      Kaeser Compessor bsd 75 model

    • @TanweerAhmed
      @TanweerAhmed  ปีที่แล้ว +1

      Refer technical catalogue for trouble shooting

  • @funnyvideos9375
    @funnyvideos9375 2 ปีที่แล้ว +1

    Sir please elevator lift control panel

  • @samrinriza9659
    @samrinriza9659 4 หลายเดือนก่อน +1

    didnt explain what the use of O S Y VALVE

  • @ibrahimgadwal5510
    @ibrahimgadwal5510 2 ปีที่แล้ว

    Manifolding ke bare video banaye details mr

    • @TanweerAhmed
      @TanweerAhmed  2 ปีที่แล้ว +1

      Manifolding about what?

    • @ibrahimgadwal5510
      @ibrahimgadwal5510 2 ปีที่แล้ว

      Fire fighting me Pupm room Manifolding system hota jise water ka pressure or flow speed maloom hoti hi.
      High pressure zone Hydrant & Sprinkler se alag alag Manifolding pipe me pipe connection hota hi jisme pressure Gage or flow mtr lage hotey hi.
      Same ayse hi low pressure zone se bhi Ayse connection hoti hi.
      Or system me water drain pipe bhi laga hota hi.

    • @ibrahimgadwal5510
      @ibrahimgadwal5510 2 ปีที่แล้ว

      Is system ko explain kre
      Or Manifold ke importants ke bare bataye

    • @TanweerAhmed
      @TanweerAhmed  2 ปีที่แล้ว +1

      Manifold means header with junction connections

    • @TanweerAhmed
      @TanweerAhmed  2 ปีที่แล้ว +1

      Ok noted

  • @mohammadamir4822
    @mohammadamir4822 ปีที่แล้ว +1

    💯💯💯💯

  • @muthumuruganm9795
    @muthumuruganm9795 4 หลายเดือนก่อน +1

    Brother please add english suptitle..
    ..please

  • @zahidnawaz2345
    @zahidnawaz2345 ปีที่แล้ว +1

    Sir ap kabhi bhi Makkah ayain to is comment pey apna number chor daina , i will give you personnel tour of all ziarats in Makkah. Jazak Allah khair.

  • @ahmadlodhi6998
    @ahmadlodhi6998 10 หลายเดือนก่อน +1

    thanks

    • @TanweerAhmed
      @TanweerAhmed  10 หลายเดือนก่อน +1

      JazakaAllah