New Carrier RTU No Cooling

แชร์
ฝัง
  • เผยแพร่เมื่อ 28 พ.ค. 2022
  • www.amazon.com/shop/miheatingguy
    Milwaukee 2131-20 M18 ROCKET Dual Power Tower Light
    amzn.to/3pe2hYH
    Milwaukee M12 Surge Hydraulic Driver Kit 2551-22
    amzn.to/3n5offb
    Makita E-01563 Impact XPS 3 Pc. 6" Magnetic Nut setter Set
    amzn.to/2JdAcku
    Milwaukee 48-22-6330 Tongue and Groove Pliers Set
    amzn.to/3kfch0R
    GoPro Hero 8 Black Action Camera with Accessory Bundle
    amzn.to/34AGamf
    Veto Pro Pac Tech XL Tool Bag
    amzn.to/2U1QqPF
    OLIGHT Bundle H2R LED Headlamp, 2300 Lumens Rechargeable Flashlight
    amzn.to/370rGiq
    Amprobe AMP-320 Clamp Meter
    amzn.to/2GNxUHe
    Fluke 117 Electricians True RMS Multimeter
    amzn.to/3iFZP9t
    Milwaukee 2364-20 M12 Rover
    amzn.to/2HNvitK
    Milwaukee Rocket light 2132-20
    amzn.to/341OTPm
    #MIHeatingGuy
    #MichiganHeatingGuy
  • แนวปฏิบัติและการใช้ชีวิต

ความคิดเห็น • 37

  • @kenbassett5942
    @kenbassett5942 2 ปีที่แล้ว +8

    Compressors going backwards. Typical call when these units are installed the units in the winter and now they dont cool. The blower motor will always spin in the correct direction because it is on a drive. On the ecoblue the drive is built into the blower motor. Old school way is check blower rotation for proper phasing. You cannot do that anymore with any Carrier unit. You must phase them in by checking compressor operation to make sure your low side drops and high side goes up. The high voltage on that unit is done properly. The third leg does attach to the blue on that block. Another thing to check is a setting in the Belimo Zip control. Go to settings then scroll to high limit modification. Enter that parameter until you see temperature. That is the changeover temp between mechanical and free cooling. It defaults to 75 degrees. Change it to 55. Love your vids.

    • @thomasmillwood2610
      @thomasmillwood2610 ปีที่แล้ว +1

      Appreciate your insight coming from a very green HVAC tech!

  • @ATSNorthernMI
    @ATSNorthernMI 2 ปีที่แล้ว +5

    You should test polarity by opening the indoor blower section and bumping the contactor to see if the motor is going in the right direction. Some meters have a phase testing function like the Fieldpiece SC-480.

    • @MiHeatingGuy
      @MiHeatingGuy  2 ปีที่แล้ว +4

      Can't do that anymore All the new rooftops are on drives

  • @deanmartin1966
    @deanmartin1966 2 ปีที่แล้ว +1

    Good video, thanks for sharing.

  • @williamserver4332
    @williamserver4332 2 ปีที่แล้ว +2

    Will take a while for those suckers to cool down. Great video

  • @MasterLexusTech
    @MasterLexusTech 2 ปีที่แล้ว +3

    Who else is surprised he didn’t check and condemn the heat exchanger?

  • @danobrien3109
    @danobrien3109 2 ปีที่แล้ว +6

    Seen this a number of times over the years. Too bad that installers don’t know this about three phase power. Just switch any two wires and problem solved. Would save these type of service trips and maybe save some equipment components. 👍👍🇨🇦

    • @CharlesAnsman
      @CharlesAnsman 2 ปีที่แล้ว

      Still need to check the blower rotation

    • @AmericanFarmerHVAC2024
      @AmericanFarmerHVAC2024 2 ปีที่แล้ว

      @@CharlesAnsman you can't do that with the new units. The VFD corrects the power phasing for correct rotation. Same with the axion fan.

    • @rwood1995
      @rwood1995 10 หลายเดือนก่อน

      @@AmericanFarmerHVAC2024 then he doesn’t have a rotation problem??

    • @AmericanFarmerHVAC2024
      @AmericanFarmerHVAC2024 10 หลายเดือนก่อน

      @@rwood1995 no, what I meant is you can't just look at the blower rotation and assume the phases are correct because the vfd will always have it corrected for the blower. The only way to know is to test the compressors.

  • @acrepairnearme
    @acrepairnearme 2 ปีที่แล้ว +4

    Interesting case)). Yeah, maybe the polarity is wrong. Since they newer use it as A/C, only as gas heat the problem appears only now. I usually put a wet rug on the compressor head, disconnect the compressor and run the fan to save time on return. Please tell me more about that orange controller.
    (I'm residential HVAC tech from California)

    • @murkyturkey5238
      @murkyturkey5238 2 ปีที่แล้ว +1

      Wet rag and run the fan to cool the compressor back down? Lol I always just wait like a dummy 🤦‍♂️

    • @watermanone7567
      @watermanone7567 2 ปีที่แล้ว +3

      Belimo (if it is the same company) has made electronic/electric control motors for a very long time. Used to make good stuff. I don't know if they got bought out or not.

    • @jasonjohnsonHVAC
      @jasonjohnsonHVAC 2 ปีที่แล้ว +1

      That is a Belimo brand economizer controller. The easiest out there to set up. They are, in my opinion the top of the heap. Next would be the Honeywell Jade. The Belimo, you set your zip code and it configures the enthalpy sensor settings. You can navigate the settings super easily. You can test the system in cooling from the controller.

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC 2 ปีที่แล้ว +1

    Love those Belimo Zip economizers. Easy to set up, troubleshoot and test operations......I'd also verify the XFMR is also tapped correctly. Those Carrier RTU'S are very easy to work on and troubleshoot. Not much to them. Those new Axial Vane fans are a trip ( Eco blue )

    • @c21meister
      @c21meister 2 ปีที่แล้ว +1

      Those eco blue keep dying

    • @jasonjohnsonHVAC
      @jasonjohnsonHVAC 2 ปีที่แล้ว +1

      @@c21meister haven't had that happen yet, but it wouldn't surprise me

    • @danieljones5135
      @danieljones5135 2 ปีที่แล้ว

      Man, they are horrible to work on. Not tech friendly at all.

  • @andrewedis9907
    @andrewedis9907 2 ปีที่แล้ว +2

    Ouch poor compressors I hope they're OK

  • @wonderhomie2011
    @wonderhomie2011 2 ปีที่แล้ว +3

    Carrier is currently flip flopping from the honeywell jade control, back to the old honeywell control that sits on top of the economizer back to blemo 🤷‍♂️

  • @douglascervantes773
    @douglascervantes773 2 ปีที่แล้ว +1

    Hey I think the wiring is wrong did you figured it out or do you have a recently video

  • @markhoffmann5941
    @markhoffmann5941 9 หลายเดือนก่อน +1

    condensate trap vent should be on the outlet side...

  • @throttlebottle5906
    @throttlebottle5906 2 ปีที่แล้ว +1

    nice, they don't usually oil as good running backwards, the oil may all leave and not return and obviously no gas/liquid cooling. winter or not, always check them for rotation. ☠
    or better yet, unhook the compressor contactors coils, so they wont even try to run. 😁

  • @Techhead777
    @Techhead777 2 ปีที่แล้ว +1

    Whats the name of the phone case you use? I saw it in your previous rooftop video but I couldn't make out the letters on the case. If it's not an OtterBox, why did you go with that brand? Thanks.

  • @c21meister
    @c21meister 2 ปีที่แล้ว +1

    I thought carriers had a controller that would change phase rotation for you? Or am I thinking of trane?

    • @MiHeatingGuy
      @MiHeatingGuy  2 ปีที่แล้ว +2

      On indoor blower

    • @DW-bo3qw
      @DW-bo3qw 2 ปีที่แล้ว +2

      The trane units have a phase monitor on them

  • @murkyturkey5238
    @murkyturkey5238 2 ปีที่แล้ว +1

    I haven’t seen that economizer controller

    • @jasonjohnsonHVAC
      @jasonjohnsonHVAC 2 ปีที่แล้ว

      Those Belimo Zip economizers are the best out there and easiest to set up

  • @JCT442
    @JCT442 2 ปีที่แล้ว +1

    Installers strike again... drats!

  • @MariosACandRefrigeration
    @MariosACandRefrigeration 2 ปีที่แล้ว +1

    brand new RTU with 100000 miles LOL.

  • @steveblake8766
    @steveblake8766 2 ปีที่แล้ว +1

    62 Thumbs uP