  • In today's video I get to explore a Carrier dual stage scroll compressor rtu- very neat

ความคิดเห็น • 71

  • @actechformallyyomama746
    @actechformallyyomama746 ปีที่แล้ว +28

    That’s called a digital compressor. The plug you found hanging loads the compressor when energized. Which is kinda weird. Semi-hermetics energize to unload. As far as Carrier goes the first 2 digits in the model number indicate gas or electric heat. 48 is gas and 50 is electric heat. Stay safe brother.

    • @hackfreehvac
      @hackfreehvac ปีที่แล้ว +11

      *Digital compressors* are the ones that unload 100% when the unloaded is active, lifting the upper scroll plate up and vary a duty cycle of how many seconds loaded vs loaded on an approx 15 second cycle (7 sec loaded then 7 sec unloaded then repeat... = 50% capacity for example) .
      This compressor here is a scroll that always pumps except when the loader plug is off, the discharge bypasses the last short section of the scroll to lower the compression (resulting in a fixed 70% capacity) and powering the loader uses the whole scroll for 100% compressiin.compression.
      The "digital" compressors are all or nothing when loaded vs unloaded.

    • @dimpy010
      @dimpy010 หลายเดือนก่อน

      Aka scroll compressor

  • @fredflintstone8048
    @fredflintstone8048 ปีที่แล้ว +8

    You have my sympathy.
    I've also had to study some types of diagrams for a while that were confusing and frustrating to me at first.. The longer I would study them the more they would make sense until I finally understood. I would beat up on myself because I felt I should have been able to get through that process more quickly than I did.

  • @coldking8383
    @coldking8383 ปีที่แล้ว +10

    Hey Bill - new to your channel . Good video. The impedance of the unloader will depend on the series -the ZPS -K4 compressors have a resistance of 330ohm . The ZPS-K5 compressor has a resistance of 1640 ( source A )or 350 ohm source B

  • @ericgrooms6645
    @ericgrooms6645 ปีที่แล้ว +2

    Ive never seen that plug before. My first thought was crankcase heater, but yeah.. thats how the trade is, theres sooo many things we can learn.

  • @jrh86
    @jrh86 8 หลายเดือนก่อน

    We never stop learning, thanks for this very interesting video.

  • @stevencossaboon3237
    @stevencossaboon3237 ปีที่แล้ว +2

    Nice work Bill.

  • @domenicpurgatori7068
    @domenicpurgatori7068 ปีที่แล้ว +2

    I always wondered what those wires were for haha. Luckily I'll be a step ahead if I run into this same issue in the future. Keep up the good content brother.

  • @chrissipple1018
    @chrissipple1018 ปีที่แล้ว +3

    Your second stage for cool sends 24 dc to the plug and that energizes the second stage cooling.

  • @tehGazdaa
    @tehGazdaa ปีที่แล้ว +6

    Please make a part 2, this is interesting ive never seen one either, seems like you got it, unfortunately for the customer they've probably spent a lot of $ on that unit

    • @jproper
      @jproper 11 วันที่ผ่านมา

      Keeping us in business

  • @Thermoelectric7
    @Thermoelectric7 ปีที่แล้ว +5

    Wonder if the high supply temperature you were seeing was because it was in reheat mode trying to dehumidify. That would have greatly reduced the cooling capacity as it was already running at half capacity.
    Potentially pulling the reheat call would allow it to maintain temperature a little better, until the compressor is swapped.

  • @mc-sp8zr
    @mc-sp8zr ปีที่แล้ว +5

    Carrier tonnage is in the numbers after the "48TC...", so in this case the "08" that follows. I believe that's a 7½ ton unit you've got there.
    About 8 years ago I ran into a similar problem that really stumped me. We had a Carrier unit with an intermittent low voltage short. Cooling would run in test mode, but after a few minutes it would cut out. Couldn't find any immediate clues.The compressor with 2 thin blue wires coming off the back which I had never seen before. What I thought was some kind of thermal overload was actually a stage 2 solenoid. Apparently it had a short, and we had to replace the compressor. Never saw another one since.

  • @randytorboli
    @randytorboli ปีที่แล้ว

    Great video Bill

  • @roqueherrera8471
    @roqueherrera8471 8 หลายเดือนก่อน

    I like that no blinking

  • @hackfreehvac
    @hackfreehvac ปีที่แล้ว +4

    48 means gas pack. The capacity is in tens of thousand BTU so a 48HCD06 would = 60,000 btu which = 5 tons.
    *The plug on the back of the compressor is the LOADED plug for the 2 stage scroll* So with that unplugged you were down to 70% total rated capa ity. With the supply on high speed with Y2 call you'd have horrible split temp

    • @ZRock7771
      @ZRock7771 11 หลายเดือนก่อน

      It's confusing but with carrier they have a number system for capacity that has nothing to do with BTUs, although it is close oddly enough. It goes somthing like this:
      Carrier Tons (In Model#) 48TCFD[--]
      04 - 3tons
      05 - 4tons
      06 - 5tons
      07 - 6tons
      08 - 7.5tons
      09 - 8.5tons
      11 - 10tons (12 EER)
      12 - 10tons (11.5 EER)
      14 - 12.5tons
      16 - 15tons
      24 - 20tons
      28 - 25ton
      34 - 30ton
      Edit: I have all the major RTU brands in a note on my phone with how to tell the tonnage based off the model# if anyone's interested.

    • @hackfreehvac
      @hackfreehvac 11 หลายเดือนก่อน

      @@ZRock7771 Actually the model number has everything to do with BTU's but just each number counts as 10,000
      So a size 03 is 30,000, 04 is 40,000, 05 is 50,000, 06 is 60,000 etc. And they just do all the sizing in 10,000 increments rather than the usual residential increments of 2 ton, 2.5 ton, 3 ton, 3.5 ton etc... It is different. But again. Carrier was pretty much the first mass produced Air Conditioner so I guess they do what they want. LOL

    • @ZRock7771
      @ZRock7771 11 หลายเดือนก่อน

      @hackfreehvac so why after 5 tons does the BTUs and tons not match? A 25ton carrier is 28, but 25tons is 300,000 BTUs not 280,000?

    • @hackfreehvac
      @hackfreehvac 11 หลายเดือนก่อน

      @ZRock7771 A ton is a unit of measurement that simply means 12,000 BTUs (like 1 yard = 3 feet).
      The Carrier commercial numbers indicate how many BTUs in 10,000 btu increments.
      30,000 40,000 50,000 60,000 70,000 80,000 90,000 100,000 110,000 120,000 etc. The size on the label is just an abbreviation. So a 03 =30,000 and a size 06 = 60,000 etc. All in btus. The raw unit of measurement.
      When comparing the two separate units of measure, it just so happens that a size 60,000 is exactly 5 tons (12,000 time 5) and a 120,000 is exactly 10 tons (12,000 time 10).

    • @ZRock7771
      @ZRock7771 11 หลายเดือนก่อน +1

      @@hackfreehvac I'm still struggling to understand it with the bigger size units, but just wanted to say I really enjoy your videos man. Keep up the drone footage! That amazon warehouse with 300 carrier RTUs was crazy.

  • @davidturney2975
    @davidturney2975 11 หลายเดือนก่อน +1

    I ran into a fun one this week. Had a liebert unit that wouldn't cool and the hot gas bypass was staying engaged and the liquid line solenoid valve wasnt opening. It had me confused for a bit. The HGB staying open because the LLSV wasn't opening made sense to me. After some thinking and digging and tracing I found that the solenoid coils had been switched by someone for whatever reason. I was dumbfounded by that. The most confusing part was I was getting voltage to the LLSV coil the whole time but that valve wasn't opening.

  • @rickalders
    @rickalders 4 หลายเดือนก่อน

    If you look at the whole data tag you can easily tell it’s not a 4 ton, 5 ton, or 6 ton unit. Right above the two bar codes and below the Intertek logo it says “Cooling Capacity 88000”. So that makes it a 7.5 ton unit. Pause the video at 0:27 and you can plainly see it.

  • @jrsmyth9761
    @jrsmyth9761 ปีที่แล้ว +2

    Misspoke I am sure, but it was a Y2 call and not a W2 call.
    The dotted line did not go to reheat, it went up to 8 before it "landed" at reheat.
    A txv takes the place of the Acutrol metering devices, so there should NOT be anything else to meter the refrigerant past the txv.
    I am not familiar with that unit specifically, but I do not recall ever seeing a LL solenoid in an RTU. The look of that install of the LL solenoid screams retrofit, kind of like the heat block on the txv.

    • @FrostHVAC
      @FrostHVAC 10 หลายเดือนก่อน

      It's normal for these carriers, I've seen em on there, I figure it to be the "second stage" lol

  • @MarkCarpenterHVAC-me2jg
    @MarkCarpenterHVAC-me2jg 9 หลายเดือนก่อน

    70 degrees is normal supply air if the unit is in de-humidification mode. That solenoid allows hot gas to go to the reheat coil. There are also two other solenoids in the blower compartment to control the refrigrant flow through the reheat coil to hold the return and supply tempature the same. Essentially loading the space with the reheat coil so you can keep running air through the cooling coil for hours on end.
    A digital compressor! The unloader allows the scroll plates to separate in a 15 second interval, so 7 seconds off, 7 seconds on would be 50% duty cycle. 1) This is better than an inverter driven compressor because the refrigerant velocity doesn't change in the on cycle. VFD running a compressor slower speeds causes the suction line to be oversized and that can cause oil return problems. 2) There's no expensive VFD in the mix.
    Sometimes you can hear the compressor making a clicking and tone change as the compressor engages and disengages, motor speed doesn't change. They sound broken when working properly.

  • @michaelbuckley3808
    @michaelbuckley3808 ปีที่แล้ว +2

    What did you find on the second RTU? Will that be a third video?

  • @EverythingHVACR
    @EverythingHVACR ปีที่แล้ว +1

    Nice job, Bill!

  • @fredflintstone8048
    @fredflintstone8048 ปีที่แล้ว +2

    The resistance of the loader would not be that unusual if the voltage that feeds it is AC due to inductive reactance. I wasn't really sure if you were saying there were diodes in the circuit and I'm not able to read the schematic on the display to tell. If there is one or more diodes in that circuite then it's going to be a DC voltage. With a DC voltage supply 0.4 ohms is pretty low.

  • @t.a.servicehvact.a.service3189
    @t.a.servicehvact.a.service3189 11 วันที่ผ่านมา

    nice job

  • @chrissipple1018
    @chrissipple1018 ปีที่แล้ว

    Copeland used 2 different manufactures for the compressor solenoid unloader and each has a different ohm readings.

  • @HVACRNorth
    @HVACRNorth ปีที่แล้ว +1

    🤘👍

  • @wayneschneyer8699
    @wayneschneyer8699 ปีที่แล้ว +3

    Did you ohm out the unloaded terminals in the compressor? Should have had like 10-14 ohms for that coil. If low (5) ohms the coil is internally shorted. ( comp change out) OR if the terminals are grounded too.
    Point is, now your SURE that is the issue.

  • @CallsignMayhem
    @CallsignMayhem ปีที่แล้ว +1

    The Copeland Mobile and AE Bulletins apps will tell you everything you could ever want to know about Copeland compressors.

  • @hrdworkin7633
    @hrdworkin7633 ปีที่แล้ว

    I've never seen that either. I wonder if more information available on the Emerson site for the compressor? just a thought.

    • @lakeshvac
      @lakeshvac ปีที่แล้ว +1

      Second stage plug. It uses 24 volts ac to the plug and the plug converts to dc . To bring the 2nd stage of the compressor in

  • @Jeff-Lawrence
    @Jeff-Lawrence ปีที่แล้ว

    Curious, why would W2 kick on? Is that the signal for the unloaded?

  • @EkremOncirak
    @EkremOncirak 11 หลายเดือนก่อน +1

    Isn't that a solenoid for mechanical 1-2 stage modulation?

  • @markhoffmann5941
    @markhoffmann5941 6 หลายเดือนก่อน

    Did you check the evap. coils entering air temperature when you recorded the S/A leaving air temp @ 70 degrees F.

  • @MariosACandRefrigeration
    @MariosACandRefrigeration ปีที่แล้ว

    the question is,what caused the unloader to fry ?

  • @Techniclay
    @Techniclay 9 หลายเดือนก่อน

    “Makes my brain hurt” ha! SIR what it all boils down to is. . Well . . Fucken things sucks 😊 stay safe out their!

  • @jacobfoxworth
    @jacobfoxworth ปีที่แล้ว

    Carrier has a weird model number nomenclature. The numbers after the letter string are the tonnage, and it's always one size less than the number. Yours said 8 so it's 7.5 ton I believe. Crazy carrier always gotta be different. 😂

    • @hackfreehvac
      @hackfreehvac ปีที่แล้ว +1

      It is in 10's of thousands so an 05= 50,000 and. 06= 60,000 etc. So the 06 is a 5 ton, 12 is a 10 ton, 24 is a 20 ton etc as they fall on the even numbers for btu/12,000 ratings and all the others are oddball in between sizes.😂
      But as far as sales are concerned they sell a 04 as a 3 ton, 05 as a 4 ton, 06 as a 5 ton, 07 as a 6 ton, 08 as a big 7 ton etc as the numbers drift slightly.. Can be fun

    • @jacobfoxworth
      @jacobfoxworth ปีที่แล้ว

      @hackfreehvac lol did not know that. I knew they were up to something. The engineers at carrier must've been as high as a kite the day they came up with that complicated stuff. 🤣🤣

    • @hackfreehvac
      @hackfreehvac ปีที่แล้ว +1

      @@jacobfoxworth Yeah I still don't know why they did that on the commercial equipment.
      But you get used to it.
      Another thing they do differently is their heat pumps use Y for cool and W for heat (conventional rather than direct reversing valve control) so when a tech is installing a new digital t stat and selects " heat pump" in the stat, it wont work right. You must set the stat for "conventional" or electric heat etc.
      Engineers are still laughing!!!

    • @jacobfoxworth
      @jacobfoxworth ปีที่แล้ว

      @hackfreehvac holy crap. No shit? Jeez, ill definitely have to remember that one. We don't have many heat pumps in my area so that's definitely one to remember in case I ever come across one.

    • @hvacmisadventures
      @hvacmisadventures 11 หลายเดือนก่อน

      @@hackfreehvachahaha only took me 2 call backs to the same place to figure that one out as a green tech. Never forgot it since 😅

  • @davidwalz2283
    @davidwalz2283 ปีที่แล้ว

    It has a humidimizer in it.

  • @LadariusCapersOfficial
    @LadariusCapersOfficial ปีที่แล้ว

    2:45 that’s the connection plug to the compressor know wonder why the unit wasn’t working 🎉

  • @electroshed
    @electroshed ปีที่แล้ว +1

    If only the unloader, or more of a half-unloader would have failed to 2stage eg power supplied to it = single stage, you could have worked around the fault by cycling the compressor instead

  • @SickaMorStyle
    @SickaMorStyle ปีที่แล้ว

    I’m somewhat sure that solenoid is a for the dehumidification reheatcoil.

  • @winkhvac62
    @winkhvac62 11 หลายเดือนก่อน

    Never see a extra plug like that.

  • @shadowbanned69
    @shadowbanned69 ปีที่แล้ว +1

    Turns from a 2 ton to a 4 ton with only 1 compressor...I thought it was a humidification thing but that opens the unloader???? Wow that's a different way to do it...only carrier

    • @shadowbanned69
      @shadowbanned69 ปีที่แล้ว

      Another way for the customer to save money but actually cost some more in the end That's a really stupid idea

    • @RalphMercuroMusic
      @RalphMercuroMusic ปีที่แล้ว +1

      Two stage scrolls have been out for quite a while... Copeland calls them The Ultratech

    • @shadowbanned69
      @shadowbanned69 ปีที่แล้ว

      @@RalphMercuroMusic didn't know that...I've seen mostly refrigeration types for walk ins and freezer comps with the injection circuit on top....but never a two stage like that...thanks for the info

  • @DanielHernandez-tp2tm
    @DanielHernandez-tp2tm ปีที่แล้ว

    Two stage compressor.

  • @liam3284
    @liam3284 ปีที่แล้ว

    0.5 ohms = short for sure at 24 volts

  • @blakeshull9316
    @blakeshull9316 9 หลายเดือนก่อน

    No that is not a digital. That is a 2-stage compressor receives an AC signal from the board, and gets converted to DC buy a rectifier within that plug. Make sure that you have 24-volt AC off of the board. Then check that cell annoyed on the compressor itself. If the solenoid is good and voltage from the board is right, replace that plug. If the solenoid does not check out, replace the compressor.

    • @blakeshull9316
      @blakeshull9316 9 หลายเดือนก่อน

      Since you plugged in the rectifier plug, and had a bad loader solenoid, it may be a good idea to replace the rectifier plug as well as the compressor. I have had them smoke the rectifier because of this.

  • @johnrider7826
    @johnrider7826 ปีที่แล้ว +4

    you really need to go back to working at Mcdonald's, at best a helper.

    • @joshuaricks7730
      @joshuaricks7730 11 หลายเดือนก่อน

      How long you been doing HVAC

    • @johnrider7826
      @johnrider7826 11 หลายเดือนก่อน

      @@joshuaricks7730 38 years

    • @luisortiz590
      @luisortiz590 10 หลายเดือนก่อน +3

      So after all that time in the field and experience, instead of offering advice to another brother you decide to bring him down. 👏 we all at some point or another have encountered a system that was new to us and it involved a little time or advice to get acquainted to it. Good day to you sir. Be a blessing and not a curse we already have enough of that in this upside down world of ours

    • @joshuaricks7730
      @joshuaricks7730 10 หลายเดือนก่อน +2

      It’s people like you that bring this trade down. Glad to hear you’re close to retiring.

    • @joshuaricks7730
      @joshuaricks7730 10 หลายเดือนก่อน +2

      I work for Trane and still run into units that are new that I haven’t seen and I struggle with.