Rooftop Unit Not Cooling-HVAC Service Call

แชร์
ฝัง

ความคิดเห็น • 32

  • @thomasmclaurin7036
    @thomasmclaurin7036 3 ปีที่แล้ว +5

    Fan capacitor. I spin the blades to check also. With no former training, I found out that little trick just by trial once. It's a handy tip to know that the motor spins freely and hasn't seized up.

    • @michaelthurber2660
      @michaelthurber2660 2 ปีที่แล้ว +1

      Actually that can tell you alot. Cap usually, but seized, you would hear it....

    • @murkyturkey5238
      @murkyturkey5238 2 ปีที่แล้ว

      Lol I’m sure he knows that trick as well

  • @robertmilligan3831
    @robertmilligan3831 2 ปีที่แล้ว

    Thanks for this video! We have a rooftop A/C on a 4-story condo building with 55 apartment units and the cooling is poor, even on 80-degree days. I know enough not to call a service company and speak your language, well almost!

  • @irisnavarro3162
    @irisnavarro3162 3 ปีที่แล้ว +1

    awesome video thank you. continue to learn and grow. great job!!

  • @user-xd9im4td1f
    @user-xd9im4td1f วันที่ผ่านมา

    I went to school for HVAC, and I have field experience. One of the reasons a capacitor could go bad is the condenser fan motor could be going bad.

  • @michealolson7217
    @michealolson7217 หลายเดือนก่อน

    Thanks for the video

  • @mohammadmahdawi4821
    @mohammadmahdawi4821 หลายเดือนก่อน

    Appreciate your help
    More RTU please

  • @chrisd933
    @chrisd933 2 ปีที่แล้ว

    Great video

  • @SoGQue
    @SoGQue ปีที่แล้ว

    Great work🙌🏾

  • @wildoutrudeboy
    @wildoutrudeboy 7 วันที่ผ่านมา

    It looks like you are connected to the discharged line coming out of the compressor, which is a high-pressure vapor.

  • @llesco693
    @llesco693 ปีที่แล้ว

    My ac roof is goin on and off on the compressor but the fan blower is working well. Where should I start with?

  • @alvarolucio8264
    @alvarolucio8264 3 หลายเดือนก่อน

    Parabéns pelos seus vídeos. Estas placas deste equipamento são iguais para todos os modelos de ruf top? O seu manômetro que vc acompanha pelo celular, qual modelo dele? Aqui no Brasil nunca encontrei deste modelo!!!! Parabéns

  • @trendingnow3973
    @trendingnow3973 2 ปีที่แล้ว +1

    For I taking RTU Data for analysing,I seen rtu give 255 value continuesly,Can you explain why this happend.

  • @ianwalbert8727
    @ianwalbert8727 2 ปีที่แล้ว +3

    looked like u hooked to the discharge instead of liquid line. thought u cant measure subcool that way

  • @juanrobles9511
    @juanrobles9511 2 ปีที่แล้ว +4

    High Subcool and High Superheat indicates a restriction in the metering device along with dirty condenser coils. Did you replace filters? Good video✌️

    • @chrissipple1018
      @chrissipple1018 ปีที่แล้ว +1

      The sub cooling was high because he was checking the discharge pressure and not the liquid line pressure. He would need to install a liquid line pressure line tap to read the sub cooling. Carrier does not install a liquid line pressure line fitting, to much money.

  • @thepoopsoup
    @thepoopsoup 2 ปีที่แล้ว +3

    I have never heard a tech say there's always a reason why a capacitor goes out.

    • @Brisket9392
      @Brisket9392 2 ปีที่แล้ว +3

      They do just go bad. The plates deteriorate. Heat will kill them faster.

    • @fragartyparty
      @fragartyparty 2 หลายเดือนก่อน

      A tech once told me that back in the day capacitors were huge and could outlast an AC unit. Then one day, capacitors got really small and their lifespan was greatly reduced.
      Planned obsolescence

  • @bb3283
    @bb3283 2 ปีที่แล้ว +1

    AC tries to turn on and buzzes for 10-15 seconds, then it turns off. No fan. Nothing…. Tried turning it from ON to OFF a few times, and still have nothing going on when I try it.

    • @Brisket9392
      @Brisket9392 2 ปีที่แล้ว +1

      Contactor would be the first thing I check.

  • @shannonstiles9838
    @shannonstiles9838 2 ปีที่แล้ว

    🇺🇸

  • @Al-gr2pg
    @Al-gr2pg 8 หลายเดือนก่อน

    Always change the fan. Usually the fan is on the way out

  • @user-rn4ko9rx7z
    @user-rn4ko9rx7z 11 หลายเดือนก่อน

    unit looks old, that has 410A?not r22

  • @michaelthurber2660
    @michaelthurber2660 2 ปีที่แล้ว +3

    Please get in the habit of totally disconnecting the cap before reading. Same with compressors.

    • @murkyturkey5238
      @murkyturkey5238 2 ปีที่แล้ว

      Lol it doesn’t make a difference and compressors, you can check the wires at the same time

  • @mrrichards6007
    @mrrichards6007 2 ปีที่แล้ว +1

    Is it standard for the compressor to get really hot to the touch?

    • @murkyturkey5238
      @murkyturkey5238 2 ปีที่แล้ว +1

      Probably not, check the charge

    • @decal4707
      @decal4707 ปีที่แล้ว +1

      scroll compressors tend to get hot to the touch on the bulbous top section