Connecting a power logger to a LIVE 600A 3 phase fuse board | REC004

แชร์
ฝัง

ความคิดเห็น • 46

  • @petehiggins33
    @petehiggins33 หลายเดือนก่อน +18

    A reactive load of -3.5kVAR corresponds to a capacitance of about 200uF hanging directly on the mains. It's a big capacitance and I can't think of anything that would do that, so I suspect that there might be a faulty grid tie inverter connected which is failing to match the phase of the supply. It might be an idea to repeat this measurement at night when there's no solar power.

    • @residualelectrical
      @residualelectrical  หลายเดือนก่อน +3

      Check the latest video, it looks like you’re correct!

    • @we-are-electric1445
      @we-are-electric1445 หลายเดือนก่อน

      Unless there is a lot of electronics connected you would expect (on balance) the load to be more inductive rather than capacitive.

  • @three-phase562
    @three-phase562 หลายเดือนก่อน +4

    Interesting that the VAr reading on the first PEL was negative indicating a capacitive load rather than inductive. The second PEL to the plant room was showing inductive VAr, 0.9 pf is pretty respectable for motor plant. Would be interesting to see what the pf closer to the intake is, as the capacitive loading should counteract the inductive loading.
    For connections into boards like this I have a set of fly leads made up with 4mm safety sockets on them that connect direct into the leads to save taping the crocodile clips in place. For Red Spot fuses, I have a set with the 4mm sockets built into the fuse carrier.

    • @residualelectrical
      @residualelectrical  หลายเดือนก่อน

      Nice, can you send me some pics of those? They sound great!

  • @retozaugg3775
    @retozaugg3775 หลายเดือนก่อน +9

    You said that there is a bit of PV connected to the board with the bad power factor. One time we had a case, where the inverter was faulty. It produced a huge apparent power and was tripping the 25 A fuses, but the meter only read a few amps active power.

    • @tangojango44
      @tangojango44 หลายเดือนก่อน +1

      If the load and generation are closely matched, then irregular power factors are quite common. It would be worth turning off the solar and re-checking those readings. Though at 5pm you wouldn't expect much of an influence.

    • @gokugeorge011
      @gokugeorge011 หลายเดือนก่อน

      I will be very glad if you can make me your apprentice 🙏🙏
      ..i have a electrical backround.

    • @gokugeorge011
      @gokugeorge011 หลายเดือนก่อน

      I will be very glad if you can make me your apprentice 🙏🙏
      ..i have a electrical backround.

  • @001Elan
    @001Elan หลายเดือนก่อน +4

    Hey Mike great vid mate followed since you started , so thought I’d kindly point out …. Wearing your arc flash is a good example to the majority who don’t, but without your balaclava it’s fairly irrelevant, your head is well within the theoretical arc flash zone which means second degree burns if all goes up ! On hands that’s a problem , on your neck and face ??!!!
    Please take care , keep safe

  • @Ash-gw2bk
    @Ash-gw2bk หลายเดือนก่อน +2

    We love to see it I told you I’d be back 👌

  • @John_Faultless
    @John_Faultless หลายเดือนก่อน

    Great video mate. It's really good to see someone explaining the potential losses due to low power factor. Look forward to the results 🫡

  • @russellslater4037
    @russellslater4037 หลายเดือนก่อน

    Fantastic, I've finally got my head around PF. Thank you, thank you, thank you.

  • @Ronny86_
    @Ronny86_ หลายเดือนก่อน

    Nice video Mike! Looking forward to the next one

  • @rcoombs100
    @rcoombs100 หลายเดือนก่อน

    Hi there, thanks for the vid. What size fuses did you replace the originals with when you powered up?

  • @lewisbrand
    @lewisbrand หลายเดือนก่อน

    Most LED luminaires are around 0.8 power factor or less.

  • @_eusty
    @_eusty หลายเดือนก่อน +3

    5:53 made you jump!

  • @ShalomBrother
    @ShalomBrother หลายเดือนก่อน

    Your shaping like your disarming a 💣

  • @Fishfingersarnie
    @Fishfingersarnie หลายเดือนก่อน

    Any plans for a BMS? would save all of the confusion in the future and allow for live readings at any point.

    • @residualelectrical
      @residualelectrical  หลายเดือนก่อน

      Sure would, I don’t think they would install one though.

  • @0liver0verson9
    @0liver0verson9 หลายเดือนก่อน +1

    Very interesting stuff. So it's possible a supply can alter the cost of electricity? Or is the "power factor" related to something else? I work with meters and obviously some customers dispute meter reads and bills. This usually results in a 2nd check meter being installed to run concurrently. I wasn't aware of other factors on the supply side that alter bills, if that's what you're investigating.

    • @Ronny86_
      @Ronny86_ หลายเดือนก่อน +2

      It’s to do with real power and apparent power. Basically the property is wasting electric that could be used but instead it’s not. It’s nothing to do with the meter side of things but more the equipment using the power.
      And power factor isn’t really used in domestic properites

    • @0liver0verson9
      @0liver0verson9 หลายเดือนก่อน

      @@Ronny86_ ok thanks, all good to know

    • @cameronmantell9959
      @cameronmantell9959 หลายเดือนก่อน +2

      @@0liver0verson9 Yea, Ronny is right: nothing to do with supply but depends what loads are installed. Inductive loads like induction motors will lag the power factor by nature, dropping the power factor. Lagging power factor reduces real power, but the supply company still needs to pay to transport the total current (real + reactive). They are only concerned with VA through the lines, so they effectively charge you more than the real power you are using. Only really applies to commercial properties that would have lots of inductive loads (e.g. lots of induction motors)

    • @0liver0verson9
      @0liver0verson9 หลายเดือนก่อน

      @@cameronmantell9959 Well I just learnt something! Cheers

  • @scotchy88
    @scotchy88 หลายเดือนก่อน

    Im surprised the supply authority hasn’t come knocking on their front door!

  • @Uk_Grid_Engineering
    @Uk_Grid_Engineering หลายเดือนก่อน +2

    This is the issue with solar, tye inverters are all designed to produce a perfect power factor, when a prem has an amount of reactive power and an amount of real power, the solar can offset the real but cannot change the reactive, that remains constant, hence why the oower factor is worse with solar

    • @residualelectrical
      @residualelectrical  หลายเดือนก่อน

      Just read the white paper, thanks man!

  • @cliveramsbotty6077
    @cliveramsbotty6077 หลายเดือนก่อน

    does direction of flow matter when im using my clamp meter to measure current?

    • @MrMaxyield
      @MrMaxyield หลายเดือนก่อน +1

      AC amps and DC amps should be measured separately... There are 2 separate positions on a meter to measure each one respectively...

    • @three-phase562
      @three-phase562 หลายเดือนก่อน +3

      He is measuring power, so the meter needs to know the direction of the current to differentiate between exporting an importing electricity. Hence the clamps have a direction arrow, so you put them all in the same direction. For normal clamp use on AC to measure current only, it doesn't matter quite so much.

    • @ShalomBrother
      @ShalomBrother หลายเดือนก่อน

      No

    • @cliveramsbotty6077
      @cliveramsbotty6077 27 วันที่ผ่านมา

      @@three-phase562 thanks

  • @we-are-electric1445
    @we-are-electric1445 หลายเดือนก่อน

    That 0.33 PF looks suspicious !

  • @walseee
    @walseee หลายเดือนก่อน +1

    BOOOOSH

  • @hvsparky
    @hvsparky หลายเดือนก่อน

    Great video pal 💪🏼💪🏼

  • @1992Craigster
    @1992Craigster หลายเดือนก่อน

    Noice

  • @samuelchamberlain2584
    @samuelchamberlain2584 หลายเดือนก่อน +1

    Crap led drivers ?

    • @residualelectrical
      @residualelectrical  หลายเดือนก่อน

      Possible, but the PF is a lot better at night so can’t be those alone!