@@AKElectroTech Assalamualaikum... sir Apc 1 kva ups control card ups on nahe Karwa raha (not power on)....main board teek hay I checked with serviceable control card...
@@AKElectroTechAssalamualaikum sir control card ki Q20 change karnay say ON hogeya but ab panel pay battery ki pehle light on hay or Sath may red cross ❌ on hay kindly guide karain agay...
Sir ap ki videos boht zabardast hain. Allah ap ko khush rahkay. Sir 1kva apc main bord ok hai control card charging volt nae a rhay kindly guide me kon sa component hai jo control per charging say deal karta hai.
Assalamualaikum... sir Apc 1 kva ups control card ups on nahe Karwa raha (not power on)....main board teek hay I checked with serviceable control card...
@@AKElectroTechAssalamualaikum sir control card ki Q20 change karnay say ON hogeya but ab panel pay battery ki pehle light on hay or Sath may red cross ❌ on hay kindly guide karain agay...
Sir I am checking another surt6000xli having negative bus fluctuating (392-409)on battery mode, I have changed bus voltage sensing resistors also give me a solution
Sir i have a problem with APC SUA 3000I dropping battery voltage very fast after switching to battery taking less than 2 minutes when fully charged, even after replaced with new batteries. Please help me with this Sir. And this happens even without any load Sir.
Very informative and helpful videos
Thanks
@@AKElectroTech Assalamualaikum...
sir Apc 1 kva ups control card ups on nahe Karwa raha (not power on)....main board teek hay I checked with serviceable control card...
Check F1 fuse and Q20 on board.
@@AKElectroTechAssalamualaikum sir control card ki Q20 change karnay say ON hogeya but ab panel pay battery ki pehle light on hay or Sath may red cross ❌ on hay kindly guide karain agay...
@@zonairaazmat1533
This is over temporature light
JazakAllah!!
bhot wait kia app ki video ka
Thanks for your love
hi sir jki. the same problem i have got it and issue with the same resistance.. tq for vdo.
Hi. It was a perfect work. Thanks for your video
Thanks
Sir ap ki videos boht zabardast hain. Allah ap ko khush rahkay. Sir 1kva apc main bord ok hai control card charging volt nae a rhay kindly guide me kon sa component hai jo control per charging say deal karta hai.
pl check following complaints IC3, IC4, Q3, Q4 for charging
Thx sir
Very helpful video, Sir can you make a video on the error 01010 (charger fault). Thanks in advance
@@PakGuides Yes
@@AKElectroTech I have the same problem: Battery Charger Fault Exists
Please make a video on this or Give a short explanation
@Naatu-s9j
Check fuses F3 and F4 with Q730 and Q731. These are used in charger portion.
Replace Q730 and its fuse. I hope problem will be solved
Battery Charger Fault Exists
Please make a video on this or Give a short explanation on what to look for
Check Q731 and Q731 with fuses F703 and F704.
welcome Sir G
Thanks
Assalamualaikum...
sir Apc 1 kva ups control card ups on nahe Karwa raha (not power on)....main board teek hay I checked with serviceable control card...
Check F1 and Q20 on control card
@@AKElectroTech let me check....thanks for your time
@@AKElectroTechAssalamualaikum sir control card ki Q20 change karnay say ON hogeya but ab panel pay battery ki pehle light on hay or Sath may red cross ❌ on hay kindly guide karain agay...
Pl check IC15 and surrounding components. This fault is over temporature
@@AKElectroTech thanks sir g let me check
Hi Sir, I have Apc surtd3000xli its showing 70 - 80% load, and sometimes 100% load without attach any load. Help me sir thanks in advance
Pl check load sensing resistor attached with inverter. R758 and R759 should be checked
Sir surt3000xli having charger fault when apply load ,charging voltage drops when apply load please help me
@@ganeshm1735
Pl replace relay 703 and relay 704
@@AKElectroTech thank you sir relay 703 faulty
@@ganeshm1735
Wellcome
Sir I am checking another surt6000xli having negative bus fluctuating (392-409)on battery mode, I have changed bus voltage sensing resistors also give me a solution
@@ganeshm1735
Replace relay 704
Sir i have a problem with APC SUA 3000I dropping battery voltage very fast after switching to battery taking less than 2 minutes when fully charged, even after replaced with new batteries. Please help me with this Sir.
And this happens even without any load Sir.
@@antonymakoye4410
Need software update for battery parameter.
Sir g next video ?
Soon
Hello sir i have an issue surt 6000xli negative bus not raising checked power components and driver ok.give me a solution
@@ganeshm1735
Replace relay 704. Otherwise check controller board
@@AKElectroTech sir I have started on battery itself negative bus not raising
Replace relay 704
Hello sir I have replaced relay704 still negative bus not raising can you give me an idea
@@ganeshm1735
IC36 and IC17 are used for negative PFC on controller. Pl check
Sir surtd 3000 xli ka control card invertor fault dy raha hai kindly help kr dain.
Kindly share video at wattsapp
00923215717132.
You can watch my video on inverter fault
Sir main bord ok hai service able control card laga k chek kia hai. Control card invertor fault dy raha hai.
Check IC32 with q24,q15,q30,q31,q33,q37 and associated components
Aslaam u Alaikum
WAS
assalamualaikum..sir I have apc surt 8000xli error code 01100, can you help me?
Yes
This fault belongs to Battery soft start.
May be UPS batteries are dead.
may be PFC portion damaged.
@@AKElectroTech new battery and I found the igbt gp50b60pd 4 seeds were damaged in the pfc circuit
@@AKElectroTech I have replaced the igbt gp50b60pd but it still has error 01100, can you tell me what steps I should do next?
Pl see my 10kva inverter fault video and check Drivers of igbt
@@AKElectroTech OK, I'll take a look and thank you