Should we BOTHER fitting CAPPING? | Thomas Nagy

แชร์
ฝัง
  • เผยแพร่เมื่อ 8 ก.ย. 2024

ความคิดเห็น • 511

  • @Fishbait075
    @Fishbait075 2 ปีที่แล้ว +72

    Good ol' Betty Crocker. She's either tripping down a flight of stairs, or buying endless houses and having re-wires! 😂🤣

    • @ryano8768
      @ryano8768 2 ปีที่แล้ว

      She's the one keeping the industry alive if anything!

    • @adamburns1077
      @adamburns1077 2 ปีที่แล้ว +4

      You’d have thought she’d have told Schlep & Kovak to put the stairs lights on a different RCD by now 🙄

    • @TheEulerID
      @TheEulerID 2 ปีที่แล้ว

      I wouldn't be her insurer, that's for certain.

    • @CyberlightFG
      @CyberlightFG 2 ปีที่แล้ว

      Get well soon, Betty.

  • @electrician247
    @electrician247 2 ปีที่แล้ว +122

    We fit oval tube as its faster and lower cost than clipping overall. Its not mechanical protection though. Flat twin and earth encased directly in plaster complies with all those regs you listed. All of them. The only small benefit from a safety point of view is agaisnt the plasters trowel. In narrow chases its a none issue.
    I totally agree it looks a lot better from a clients points of view, can help with future rewiring and saves on grometts into back boxes.
    But it is no more compliant than just clipping cable to a wall. Suggesting a spark is mediocre for not using capping is a bit harsh lol.
    If we want to improve on twin and earth in a wall from a safety point of view would be via containment in earth metallic conduit or using swa. Is that a costs clients need to suffer when carefully clipped and tested cable offers the same service and less destruction to the building during installation? Maybe those writing the regs have thought this out.
    Still overall I am with you. Capping/tube looks better and is quicker.
    Each to their own, lift others higher.

    • @bartman58
      @bartman58 2 ปีที่แล้ว +5

      I think naga is on thin ice here, he's certainly not john ward or photoinuction, wind your neck in ffs😂😂

    • @CommonInvesting
      @CommonInvesting 2 ปีที่แล้ว +3

      My thoughts exactly, as long as its in the zone you can clip direct ? I mean if someone bangs a nail in where your cable is, its liable to go straight through the capping anyway, and the cost would fall on the builder

    • @exeterrider
      @exeterrider 2 ปีที่แล้ว +1

      I'm still not buying in on the capping thing here. Cables already have mechanical protection. If it was used for protection then a nail would go right the plastic, so why not use metal conduit.
      Reality often is if anything goes to court which is very rare, then 7671 pretty much gets pushed to one side.
      I respect the angle Tom's taking but I don't agree tbh

    • @Josh-bs3ey
      @Josh-bs3ey 2 ปีที่แล้ว

      It’s not easier when u get good at metal capping u can do it so quick and it looks so much better at the end of the day

    • @electrician247
      @electrician247 2 ปีที่แล้ว

      @@Josh-bs3ey kinda what I said

  • @olly7673
    @olly7673 2 ปีที่แล้ว +19

    Tom, I like your vids generally and as someone who also takes pride in his work, applaud the thrust of "a picture paints a thousand words" when some one looks at oval conduit in a neat chase... and that used to be my stance running cacles in concealed conduit. I think however you are misquoting the BBB to justify your argument.
    I would be keen to see the design considerarations/calculations of having 2 or 3 (maybe more) T&E stuffed into conduit when it comes to the load CCC of the design. Cg etc and the difficulty for cables to dissapate heat in conduit compared to the heatsink of bonding. Now I don't have the books to hand to look up installation methods but I'm pretty certain it has to be considered as lowering the CCC.
    The only reason to cover cables in a chased walll is so when the plasterer comes over to bond it in, they don't knick the cables with his trowel, exposing conductors. I've gone over to using British Gypsum OneCoat to secure cables in the wall before leaving it just below the plaster for the skim coat and takes me a few minutes. An IR test beforehand tells me if there is damage that might cause an issue to Betty Crocker with her wet sponge cleaning it off afterwards. The RCBO would save her receiving a shock from the damp plaster in any case. The plasterer can do the skim coat with no chance of me having to go back.
    If Betty later decides she wants to hang a picture on the wall and hammers through my cables, the fact that they are heating up in oval conduit less that 50mm below the surface and protected by Kryptonite-like (NOT!) PVC conduit will not cause the nail to bounce off the capping/conduit, even metal capping: but will pierce it as though it wasn't there, the RCBO will then come into play..
    The other consideration on an horizontal run, in zone say between sockets is the safety of the wall where you cannot chase any more than a sixth of the wall thickness to keep the integrity of the structure. If the wall is 100mm as internal wall oftern are, you are limiting the depth to 16.66mm.
    I am a huge advocate of levelling up the industry but not necessarily here. I am happy to proved wrong though.

    • @rkan2
      @rkan2 2 ปีที่แล้ว +2

      Exactly... Save the customer the extra work that capping requires and invest into the actual electrical protection devices such as RCBOs.

  • @thattoolguy9432
    @thattoolguy9432 2 ปีที่แล้ว +32

    As a mechanical protection, its more to stop a plasterer catching a cable, i do it because it looks neat and more recently i've been doing kitchen, lounge switch drops in 20mm pvc conduit, the plus side i got a call from a previous client asking wether they could have the downlights in the kitchen on 2 switches.. bingo bango i was able to slip another t&e down the conduit split the circuit without damaging any of their new freshly decorated kitchen ... now im pricing for a friend of there's rewire ..

    • @denislostinlondon199
      @denislostinlondon199 2 ปีที่แล้ว +1

      ... theirs rewire.

    • @ja_adam_
      @ja_adam_ 2 ปีที่แล้ว +9

      @@denislostinlondon199 everyone check out this guy, he can correct people’s spelling. Omg he’s so cool

    • @davefarmery8180
      @davefarmery8180 2 ปีที่แล้ว

      @@denislostinlondon199 I'm dyslexic and your reply makes me piss 😅

  • @CraigJFW
    @CraigJFW 2 ปีที่แล้ว +24

    You're wrong. Nowhere in the regs does it specify a requirement for capping or tubing. It does specify RCD protection though for new installations and thats all you need at this moment in time in terms of protection against shocks for cables buried less than 50mm. If it was so important the regs would specify it for example in the presence of certain external conditions like damp in the fabric of the building. totally agree it looks better and if the customer was prepared to pay for it i would every time but thats not the way it goes unfortunately. Show me a single court case where a spark has been prosecuted for not fitting capping and someone died or just got a shock? to suggest a barrister would wrap you up like a kipper in court is laughable. stop it man

    • @GameLifts
      @GameLifts 2 ปีที่แล้ว

      ur dim

    • @CraigJFW
      @CraigJFW 2 ปีที่แล้ว +2

      @@GameLifts dim but efficient like a 8w led

    • @MrSeananners12345
      @MrSeananners12345 2 ปีที่แล้ว +3

      I do wish to see a contractor to be found guilty of this then I’ll believe Thomas. Until then you are right sir

    • @tspirit99
      @tspirit99 ปีที่แล้ว

      Ive just slapped a 2.5 at the wall for a tv socket, filled straight on top, I'm bricking it if council finds out 🤣

    • @leebarnes599
      @leebarnes599 วันที่ผ่านมา

      Exactly

  • @andrewcadby
    @andrewcadby 2 ปีที่แล้ว +40

    Nope. BS7671 lists cables embedded direct in masonry without added mechanical protection as a legitimate installation method. You'll find it in table 4A2, on P389, number 57.
    All capping does is protect cables from the plasterer's trowel during plastering. Necessary when solid wet plastering was common, as the trowel was likely to come into contact with the cable otherwise. It's not really needed now in the dot-n-dab age, or when chased into existing plaster, as the odds of the trowel hitting the cables is low. My plasterer has specifically asked me to omit it.

    • @CoulterTravel
      @CoulterTravel 2 ปีที่แล้ว +1

      👏

    • @jsl4228
      @jsl4228 2 ปีที่แล้ว +7

      Well done, Sir. Shame Mr Nagy didn't bother to make sure he actually knew what he was talking about before spouting rubbish on TH-cam. I always liked his videos, but I'm unsubscribed now. He's far too pretentious for me these days.

    • @rkan2
      @rkan2 2 ปีที่แล้ว +1

      Fit an actual electrical system protection device and don't make customer pay for what is very expensive additional insulation on perfectly good electrical cabling...

  • @mikeselectricstuff
    @mikeselectricstuff 2 ปีที่แล้ว +29

    Just run armoured everywhere - it's the only way to be sure...;-)

    • @wibbley1
      @wibbley1 2 ปีที่แล้ว +5

      surely wireless is the way to go.....

    • @rkan2
      @rkan2 2 ปีที่แล้ว

      How about using the actual electrical protection devices such as RCBOs and saving the customer an extra layer of plastic on their wires...

    • @SqwarkParrotSpittingFeathers
      @SqwarkParrotSpittingFeathers 2 ปีที่แล้ว +1

      I think you guys have excellent arguments as to why a court wouldn't be able to find you guilty or negligent.

    • @wibbley1
      @wibbley1 2 ปีที่แล้ว +4

      @@SqwarkParrotSpittingFeathers I would find him guilty, just for saying 'chicken dinners' :o)

    • @davefarmery8180
      @davefarmery8180 2 ปีที่แล้ว

      You can still hammer a nail into armoured

  • @beardedsparks2825
    @beardedsparks2825 2 ปีที่แล้ว +13

    Sorry, but this is just you ranting because you're fed up with competing against cheaper electricians Tom. Whilst I agree with you about the standards of work needing to be better, you can't use the courtroom to frighten people.
    BS 7671 is a non statutory document that cannot be used in court. EAWR is statutory and does use BS 7671 as it's guide as is Part P, but I think you're really stretching things here. I started my electrical apprenticeship in 1988 and oval conduit was about three times thicker than it is now. Despite it's thickness, it still didn't offer any protection against a hammer and a nail. Today's oval and capping is so thin, you could push a nail through without a hammer so it only offers the protection that it was intended to and that is against sharp edges, such as the plasterer's trowel.
    If you're being prosecuted for dangerous working practices, I very much doubt a barrister will be reading from BS 7671. There will be an expert witness in attendance, who themselves will be at least an electrician and they will be the ones reading scripture.
    One other thing. It isn't good to call electricians mediocre for not using capping, you've overstepped the line there. I should add that I always fit oval conduit, but that's down to my own personal preference.

  • @tflemming287
    @tflemming287 2 ปีที่แล้ว +5

    How does Betty Crocker get a shock from wiping a wall down?

    • @cag9284
      @cag9284 หลายเดือนก่อน

      😂😂😂 just what I was thinking

  • @nanogeekpro2
    @nanogeekpro2 2 ปีที่แล้ว +22

    I disagree on the use of capping, unless it's specifically required in a location in BS7671.
    Capping constantly cuts wires where the wire exits the capping, I used it all the time at the start, but realised that they will cause more issues than they prevent. They also restrict heat, you need 50% space free within capping for it to not be derate the CCC due to the fact that plastic prevents the loss of heat much more than plaster, you know this, but I haven't seen you account for that in your builds.
    Btw I'm pretty sure you've seen examples of nails through galvanized steel capping... in fact, that's how many of the older guys fit it to the wall... by nailing it in... So how is plastic capping going to help against nails and screws when even galvanized steel can't?
    Maybe I just think you shouldn't be throwing that term around... Mediocre electrician.... A mediocre electrician is one who likely installs the cheapest shit around but meets the guidelines, a great electrician installs the best of what they client needs, makes suggestions to futureproof their home or business, never installs a dual RCD board, and makes sure their wiring and install is perfect, and obviously meets BS7671 and often exceeding the requirements at every stage.
    I personally take images of all the wiring (so they can retrospectively understand their wiring), and give those to customers with their EIC + EICR, (they get both with a board change let alone a rewire) and spend time carefully explaining to customers what prescribed zones are, and how they can use that method to determine where is safe and where is not to fit pictures, tv's etc. I've also just bought an IR camera which cost me an arm and a leg to look for hot spots in the wiring.
    It's not a requirement, it looks better, (maybe if your wiring looks like shit) but it's actually worse for the home in the long run... Once Betty crocker has changed her sockets a couple of times, if you've poked your conduit through the back box you will be well through the insulation where the T&E meets the conduit.
    It's also worth noting that you're bringing the cables closer to the surface by adding capping, or taking even more wall out for its installation, I'm sure betty crocker would like to keep the extra half centimetre in the wall you'd need to remove to install the capping.
    I wanted to see your motives to install it, I approached the vid with an open mind, but you ignored any negatives associated to installing it, and there are issues.
    The other thing is Tom, are bad electricians spending their time watching and learning from others on YT?

  • @oninbridders
    @oninbridders 2 ปีที่แล้ว +9

    Your last point was the main point. If you walk into a takeaway, which I did, and see a oven being run off an extension lead, I know the refrigerators are full of out of date food. It's the same as checking out the toilets, before sitting down in a restaurant. Point: if a business is slacking in one area, they are likely slacking in all areas. The same reason why police pull you over if you have a light out, likelihood, they will find more. Food health and safety pretty much run off this no smoke without fire to give businesses a zero star, which is why paperwork, records and risk assessments are so important.

  • @mikeselectricstuff
    @mikeselectricstuff 2 ปีที่แล้ว +44

    Not arguing that it shouldn't be done well, but the regs argument doesn't seem that convincing -
    "...Withstand safely the stresses and environmental conditions...." in a normal domestic situation, how does a direct-buried cable in a wall not meet this requirement? What stresses and environmental conditions in a domestic situation does capping/conduit protect against ? You have two layers of PVC insulation to guard against any water-based issue. Probably the most plausible risk is a nail going through it, but if you accept that as a realistic situation, should you not be fitting (earthed) metal capping, as a nail would easily go through plastic?
    Wondering what danger or fault situations have people seen with an un-capped/enclosed cable chased into a wall , which would have been prevented by capping/conduit?

    • @pauldavies9709
      @pauldavies9709 2 ปีที่แล้ว +6

      You're considering the presence of capping solely as a safety measure to the end user. I've always considered capping as the protective measure for cable against the plasterers trowel and the long term erosion caused by plaster itself.

    • @steve11211
      @steve11211 2 ปีที่แล้ว +3

      I agree, I think it should as good workmanship have capping, but those regs I would say make reference to not putting twin and earth outdoors or buried underground. Capping is there to protect the cables when plastering... I have seen plasterers rip capping off as the plaster does not stick to it very well.. I agree if you were that worried you would put it with metal earthed conduit or capping, or run SWA in walls..
      Interesting in other countries they dont have prescribed zones as they argue, why bother you have an RCD, There must have been multiple failings for something to have happened as all new wiring should be RCD protected. We dont fit capping or any other kind or protection in stud walls.. Again I am not saying its not the correct thing to do but the regs are so wooley I would be surprised if any sparks would get convicted on that basis as a decent defence barrister would just shred that regulation to bits..
      Would love to raise the bar on every job but we all know most domestic installations people just want it to work and as cheap as possible. If its the option between a split load board or keep the old rewireable board with no RCD protection because they cant afford a full RCBO board.. What is better?

    • @TheXsheeple
      @TheXsheeple 2 ปีที่แล้ว +1

      Does plaster contain any ingredients that may breakdown the cable sheathing?

    • @johnadams1976
      @johnadams1976 2 ปีที่แล้ว +2

      Totally agree. Conduit isn't stopping my hammer and nail!?! If a quote was more because it had conduit, I'd go for the other guys

    • @steve11211
      @steve11211 2 ปีที่แล้ว

      @@johnadams1976 thats not the point of the capping, it is there purely to stop the plasterer damaging the cable when filling in the chases, putting cables in zones and additional RCD protection is put in place to stop you getting injured by hammering a nail. It should be fitted as standard..

  • @twowheel_enthusiast5925
    @twowheel_enthusiast5925 2 ปีที่แล้ว +2

    Firstly, your videos 5 or 6 years ago when I first set my business up inspired me to want to improve my work and knowledge every day, I learned a lot, very quickly from you and it is important to let you know I appreciate it.
    That being said, capping unless it is galvanised steel conduit for instance, does not meet the requirements for mechanical protection. If you were to wire outside the zones for example, simply fitting capping would not comply however installing steel conduit would.
    By the way I use capping on every installation so I do also agree with you that we should all be fitting it.
    I also and agree with your perspective on doing things over and above. I was once taught the regulations should be complied to as a minimum standard. Keep up the good work and I will keep watching your content.

  • @mikeselectricstuff
    @mikeselectricstuff 2 ปีที่แล้ว +67

    Unless the lack of capping was a contributory factor to an incident it shouldn't be a factor in any legal action - any half-decent defence should make that point.

    • @Sierraomega1991
      @Sierraomega1991 2 ปีที่แล้ว +7

      The prosecution will destroy you in it and will make the money grab argument and the dead granny argument and no matter how good ur defence is ur snookered

    • @steve11211
      @steve11211 2 ปีที่แล้ว +8

      Yeah I think you could argue that the cable was damaged by the plasterer, now would capping have stopped that.. Probably, but Ive seen plasters rip capping off cause the plaster wont stick to it as easy of there is no guarantee a bit of plastic will protect the cable. I think you could make a good defence that it was the plasters shoddy workmanship and him that caused the fault.. Again I always fit capping and think you should, but I dont think it would be as clear cut in a court.. I think any defence barrister would simply say where does it say in the regs that capping is required when burying cable in walls? Its not in there, case closed... Should it be in there, yeah probably... But its not specifically stated, its another example of the regs book being wishy washy and open to interpretation..

    • @jsl4228
      @jsl4228 2 ปีที่แล้ว +16

      @@Sierraomega1991 Spoken by someone who clearly knows nothing about the law or legal process. It really is hilarious when non-lawyers try to talk authoritatively about law. Causation is a critical part of any tortious or contractual claim and the burden of proof is on the claimant. If the lack of capping did not cause the injury, it is irrelevant to the matter of liability. It really isn't that difficult to understand.

    • @calebbrookes7896
      @calebbrookes7896 2 ปีที่แล้ว +8

      I agree. At 10:15 when he was acting like there wasn't an answer... There's no regs that say you need it. It's not the reason this person died. If someone was to bang a screw in it the. Plastic cappings not gonna do anything. And also affordability in my opinion is also a good reason. This persons electrics wasn't safe and they could only just afford a rewire without capping.

    • @stephenwabaxter
      @stephenwabaxter 2 ปีที่แล้ว +2

      Mike makes the correct point that we all engage representation for ourselves in court and issues are rarely ever clear cut.

  • @markrowland5393
    @markrowland5393 2 ปีที่แล้ว +8

    So, why don't the regulations spell it out? "Wherever practical, cable shall not be buried in plaster without additional mechanical protection conforming to BS whatever". If the regulations don't spell it out, they are sh!t.

  • @AK90
    @AK90 2 ปีที่แล้ว +21

    This is why we run all our cables in "tubes". Good protection and you can replace the cable should it get damaged. But thats with 3 loose wires in the pipe. Easy to drag in a new pair :D

    • @edc1569
      @edc1569 2 ปีที่แล้ว

      Often you don’t have the depth you need for a tube.

  • @nathanlucas6465
    @nathanlucas6465 2 ปีที่แล้ว +11

    A few years back, I skimmed our kitchen. I put my hand on the wet plaster to see if it was ready to trowel off and got chucked backwards across the room. After a little bit of investigation, when they nailed up the galv capping, they'd nailed through the cable too. The wall was presumably dry enough for this to not be noticed until someone chucked wet plaster over it. Couldn't pull the damaged cable out as it had been nailed in place, so had to hack my nice new plaster off the wall 🤣

    • @andyxox4168
      @andyxox4168 2 ปีที่แล้ว

      You could have waited for it to dry ... 🤔

    • @dvrn86
      @dvrn86 2 ปีที่แล้ว

      230v chucked you across the room.lol

    • @davefarmery8180
      @davefarmery8180 2 ปีที่แล้ว

      @dvrn86 yes it does happen

    • @andyxox4168
      @andyxox4168 2 ปีที่แล้ว

      @@dvrn86 , yes a shock of 230V will chuck you across a room very effectively …

    • @dvrn86
      @dvrn86 2 ปีที่แล้ว

      @@andyxox4168 how? The shock makes you jump? What force from a shock could throw you across a room. (Electrician, shocked countless times, know many electricians that have been shocked many times. Only diy and homeowners tell us their thrown across the room stories) 🤷‍♂️

  • @jonathanstephens7804
    @jonathanstephens7804 2 ปีที่แล้ว +13

    agreed it looks much better but as far as regs go your argument for it being legal seems a bit off. I've been called to faults where metal capping has been penetrated with a tiny picture nail leaving a N-E fault. To reveal the cable in the wall was a right nightmare. I don't think capping offers any protection whatsoever it just looks better. Sorry can't see a barrister arguing it should be installed because it looks better.

    • @rkan2
      @rkan2 2 ปีที่แล้ว

      Yeah - how about actually use the electrical system protection devices such as RCBOs instead of making the customer pay for capping which does not much more than add an extra layer of plastic for wires you could've probably already bought with thicker insulation that outperforms typical capping...

  • @Tyler-ph8bh
    @Tyler-ph8bh 2 ปีที่แล้ว +7

    3 advantages to capping 1 is that it offers protection between first and second fix, 2 is when it’s plastered it has a hollow sound behind the plaster so easily identified and 3 there’s like a 10% chance you’ll get another cable down it

    • @tspirit99
      @tspirit99 ปีที่แล้ว

      Heat dissipation too.

  • @iScoTT29
    @iScoTT29 2 ปีที่แล้ว +14

    I disagree with having to install capping or that if you don't you're a mediocre spark. Capping does not provide mechanical protection in any way. I believe it's was an old wife's tail that metal capping would stop people from putting nails through cables which it doesn't and the way I see it, in today's world is it is there to prevent plasterers from nicking/hitting a cable with their trowel. It's not there to protect the cables from normal operation. The chases you did on the last job with the metabo are neat and small, any competent plaster should be able to put a bonding coat in without striking a cable. And if we really want to play by the blue book, you shouldn't be energising cables that are still to be plastered because there is more chance of wet plaster being applied round live sockets causing death than betty crocker washing a wall with a wet sponge in my opinion. Great content as usual, keep it up!

  • @PJB71
    @PJB71 2 ปีที่แล้ว +10

    Capping is only used to protect the cable from the plasterers trowel, installing in conduit de-rates the cable. I personally have always used plastic capping in void properties. In occupied properties definitely not. Also you have to be careful how deep your cutting chases, you could actually make the wall unstable.

    • @CoulterTravel
      @CoulterTravel 2 ปีที่แล้ว +2

      Very valid point about how deep your chases are!
      Especially flats.. you can actually weaken the walls to the point of severe collapse when it’s poured concrete etc..
      “Vertical chases should be no deeper than one third of the wall thickness - with standard 100mm bricks and blocks, that going to be 33mm, which is quite deep anyway - that’s not allowing for any plaster coating which could be 10mm so the maximum depth then works out at 36mm from the front face of the plaster.’

    • @CraigJFW
      @CraigJFW 2 ปีที่แล้ว +1

      i like this pov. toms after 5 socket drops per room plus two way and inermediate switches in the living rm!! i think that metabo chaser has taken over his mind like the borg

    • @CoulterTravel
      @CoulterTravel 2 ปีที่แล้ว

      @@CraigJFW actually did a rewire like that for someone once. Even the kids bedrooms had two way switches by the beds, 5 double sockets, 6 downlights, and a double RJ45 in each room, they had four kids! 😂

  • @rkan2
    @rkan2 2 ปีที่แล้ว +4

    Just from my laymans point of view: electrical cabling is already covered by plastic.. what additional protection is the additional layer of plastic going to help with? How about save the extra work for the customer and put it in to the safety that the RCBOs provide.
    Naturally fit metal capping if somewhere in the house there is actual chance for the wires getting under stress.

  • @chrisjinks5197
    @chrisjinks5197 2 ปีที่แล้ว +14

    For me it's all about protecting the cables during installation as I don't think capping offers any protection forward from that point.
    We have a company rule, capping used when in contact with direct plaster, like chases but anything else, dot and dab where sharp tools won't be used during installation I don't feel it is necessary

  • @steve11211
    @steve11211 2 ปีที่แล้ว +10

    Who is an electrician and has seen problems, especially when fitting new RCD boards, and you find a fault, you eventually find the fault and its a nail to hold in the capping that has clipped the cable? I agree though that it should be fitted, I really like fitting pvc flexicon glanded into the back box, will make any future rewire a breeze as the cables can be pulled up and down..

    • @johnhoward2104
      @johnhoward2104 2 ปีที่แล้ว +5

      I agree with you, but glanding into a galv back box seems a bit excessive (though carry on if it makes you happy). A quicker alternative is to simply push some oval tubing through the box knockout so it just enters the box - the tube acts as a grommit, protecting the cable from the metal edge, and it allows for ease of rewiring, as you mention.

    • @markrainford1219
      @markrainford1219 2 ปีที่แล้ว

      Might as well use singles then, like they do on the continent.

    • @johnhoward2104
      @johnhoward2104 2 ปีที่แล้ว

      @@markrainford1219 but then you'll have to tube in the floor voids also, whereas using T&E means you don't have to.

    • @markrainford1219
      @markrainford1219 2 ปีที่แล้ว

      @@johnhoward2104 Exactly.

    • @greentoad6729
      @greentoad6729 2 ปีที่แล้ว

      @@johnhoward2104 I haven't done many if any identical like for like rewires

  • @keeganmccrae
    @keeganmccrae 2 ปีที่แล้ว +3

    Thought the regs where non statutory and are there just as a guide

  • @xXBuckOFiveXx
    @xXBuckOFiveXx 2 ปีที่แล้ว +6

    As a tradesperson, your work IS your reputation. Cheers Tom, from Arizona USA

  • @paulmoor3799
    @paulmoor3799 2 ปีที่แล้ว +1

    In Northern Ireland 20mm conduit used 98% of the time on every job. Oval is useless as can't get much down them and if told someone you were using capping, they'd laugh you off the site. Also when doing upstairs you can rewire or add to cabling from attic.

  • @petechatten-berry1865
    @petechatten-berry1865 2 ปีที่แล้ว +3

    Controversial Tom but its your opinion and I respect that.
    Capping offers no protection at all for nails or drill bits, its not earthed and you'll never end up in a court for not fitting it.
    I always use capping as it makes the install so much neater with a couple of pieces of all round band rather than clipping cables direct.
    You never know what goes on onsite between first and second fix so offering just that extra piece of protection is always a must for me.

  • @mikeZL3XD7029
    @mikeZL3XD7029 2 ปีที่แล้ว +1

    Personally,
    I was always taught that anything in a building where wall-chasing happens or fitting cabling behind false walls, you always use medium density electrical conduit to afford mechanical protection to the wiring you install.
    You do this from the fittings up to roof space height.
    It comes down to Workmanship and the safety of what you install, sure you can't stop anyone down the track drilling through your conduit, but it just gives your wiring a lot better protection.
    Thanks for bringing this up, Tom.

  • @markhardacre1
    @markhardacre1 2 ปีที่แล้ว +2

    Good points - but isn’t sheath mechanical protection on T&E? Also is a plastic capping going to stop a screw, drill or nail gun?
    The only way to prevent this is to pipe It up in earthed galvanised galv. 🤷🏼 How far do you go?
    I see you not having a defence if you placed singles directly into the wall, but not with a T&E….
    I had an instance where a plasterer ripped all of mine out after fitting it on a rewire years ago…

  • @petegriffiths5896
    @petegriffiths5896 2 ปีที่แล้ว +16

    The new wiring is insulation tested, should read 500M at 500v how will anyone get shock? the metal and plastic capping offers very little mechanical protection , I agree better to install as gives some protection against other tradesmen damaging the cables.
    This is why RCD protection is used in case cables are damaged by occupants

    • @steve11211
      @steve11211 2 ปีที่แล้ว +12

      Thomas likes metal capping, some kitchen fitter comes in after, sticks a screw through the capping and live conductor... Remember the capping is not earthed, old Betty washes the wall, gets a shock.... Mr Nagy was your choice to fit metal capping not earthed a contributing factor? You could rattle off all those same regs and argue it would be case closed..

    • @alhughes9698
      @alhughes9698 2 ปีที่แล้ว +5

      @@steve11211 Very good point, its also an absolute ball ache repairing cables that are behind cappings that have been damaged by nails or drill bits. Repairing an upcapped cable is much easier.

    • @rkan2
      @rkan2 2 ปีที่แล้ว

      Save the customer the work of adding an extra layer of insulation for cabling which you could've probably bough with thicker insulation from the get-go and instead fit the goddamn RCBOs which are the actual protection devices.

    • @supersparks9466
      @supersparks9466 2 ปีที่แล้ว

      @AL Hughes got to disagree , much easier to repair with capping installed

  • @sparx2391
    @sparx2391 2 ปีที่แล้ว +2

    I always use ovel conduit, if a damaged cable needs replacing, it's alot easier to pull another through, with capping, it's not so easy, and cable plastered in the wall is a bodge, and looks shit, in my opinion, anyway.

  • @robertreeder6742
    @robertreeder6742 2 ปีที่แล้ว +7

    Cable drops in plastic conduiit of any shape, round or oval, are afforded no extra mechanical or electrical protection, but look professional. The obvious very good reason for conduit installation is to provide, in the event of any subsequent damage to the cables from for example careless picture hanging, a possible way to rewire wire the drop without decorative damage. I notice in some of your videos that the enclosed plastic conduit drops you install stop some inches short of the back boxes. These installations therefore provide no extra mechanical or electrical protection neither can any damaged drop be easily replaced without decorative damage?

  • @tonynewton7902
    @tonynewton7902 2 ปีที่แล้ว +4

    Much prefer metal capping. Can’t see the point in plastic. Great video 👍👍

    • @glynnmorris2667
      @glynnmorris2667 2 ปีที่แล้ว

      Whats the point in metal capping?

  • @neilsemi777
    @neilsemi777 2 ปีที่แล้ว +1

    Hi Thomas. Whilst I completely agree with you on your views regarding capping or any other form of mechanical protection I must state.: - BS7671 is not LAW they are recommendations which if fo;llowed will comply with the Electricity at work regs 1989 and Electricity at work act 1974. Surely a Barrister would be using one of the two publications which apply and are MANDATORY requirements for all Electrical work. This is by no means a criticism Thomas just pointing out my view.

  • @s.kxx1956
    @s.kxx1956 2 ปีที่แล้ว +8

    Capping ensures the cables are in the chases neatly and prevents any damage when the wall is being finished or plastering. As for mechanical protection both plastic and metal offer none whatsoever they are so thin. If your in a situation where fitting capping is not possible such as a wall with very thin depth or just a small chase its not worth it

    • @gettogo0159
      @gettogo0159 2 ปีที่แล้ว

      Sami Khamis - I'd say & know installed conduct rather than capping is more professional thinking. You've cut the chase anyhow but you don't need to cut as much out so save time & making good is much quicker...... capping is a stop gap measure, nice to see some even pvc conduct install work glued & fixed with male or female end points making pulling through the cable so simple.

  • @stuartcraigon2003
    @stuartcraigon2003 2 ปีที่แล้ว +6

    13 seconds in Tom and personally I think conduit/pipe is better over capping. The cable is safer, if you use galv you can easily find it, and rewiring is a doddle with conduit/pipe.

    • @londontrada
      @londontrada 2 ปีที่แล้ว +2

      It is better, but much more work

    • @JezCunningham
      @JezCunningham 2 ปีที่แล้ว +2

      Yup, the Barrister is going to ask "will plastic capping withstand a nail for hanging a picture - if not, why didn't you use metal?"

    • @londontrada
      @londontrada 2 ปีที่แล้ว +1

      @@JezCunningham I think the legal arguments are a bit far fetched to be honest, no ones ever been in court for this

    • @stuartcraigon2003
      @stuartcraigon2003 2 ปีที่แล้ว

      @@londontrada I don't know mate, there are thousands of cases accross the uk every day most no one ever knows about. Doesn't mean it doesn't happen. Jesus companies have been in court because employees have dumb and nor followed rules and its the companies fault.

    • @londontrada
      @londontrada 2 ปีที่แล้ว

      @@stuartcraigon2003 No, If someone had been prosecuted for using plastic capping it would cause a change in the industry. The regs are not even a statuary document.

  • @bigshoe9130
    @bigshoe9130 2 ปีที่แล้ว +3

    I think your whole legal argument could be argued against pretty easy. I install cables to their required zones. If somebody was to stick a pin in the wall to hang a picture then it would be their fault. Capping wouldnt do shit to protect the cable anyway.
    I do fit capping, but for no reason due to BS7671 as my interpretation of it is that you don't need capping.
    I fit capping because of your first points - its neat and tidy and leaves an impression. I also fit capping for plasteres.

  • @AGRElectrics
    @AGRElectrics 2 ปีที่แล้ว +2

    Plastic capping offers no protection against nails or such so. Unless your fitting metal conduit throughout your example kinda falls through

  • @billysmart24830732
    @billysmart24830732 2 ปีที่แล้ว +6

    Didn't we originally fit it to keep the plaster off the cable because it destroyed the insulation? The protection it offers is minimal to none. It is useless when it comes to nails and drills and only really has a job to do when the plasterer is in. Granny can still be electrocuted when wiping the walls down with capping fitted if the cable is faulty.
    The arguement to fit it should primarily be a technical one and nothing else. It looks to me like it has become a tradition rather than a technical neccesity. FYI, I fitted it when building my extension because after talking to manufacturers, electricians and someone at the institute where they write those regulations, not a single person could definitively give me a yes or no to the question "do I have to fit it".

    • @markpotter8280
      @markpotter8280 2 ปีที่แล้ว

      ahhh i just commented on this then I seen your post. YES we did VIR's and lime in plaster that was why we originally did it

  • @100SteveB
    @100SteveB 2 ปีที่แล้ว +23

    "Withstand safely the stresses and environmental conditions". When you consider that the most likely time that a cable buried in the wall will be damaged is when someone puts a nail through it when hanging a picture, or drilling through it when putting up a shelf. Plastic capping does nothing to stop that happening - it happens all the time. The thin steel capping is nearly as bad, offers next to no protection against a hammer and nail. Sorry, but if you want to do it where it will be protected against the most common types of damage, you really need to put it in round steel conduit. Lets face it, a cable buried in a wall is perfectly safe until someone puts a nail through it, or drills through it. Plastic capping will not prevent that. What plastic capping does help to prevent is the heavy handed plasterer sticking his trowel through the cable. And of course using capping could well make the next rewire easier, plus it looks so much more professional. But for protection - nope, next to useless.

    • @joefrayling9263
      @joefrayling9263 2 ปีที่แล้ว +5

      Also to add to that the whole cable zone arguement as well as RCD protection is a massive bit of protection for you in that kind of scenario
      "Why didn't you install capping or conduit"
      "Why should it be needed the cable wasn't under any risk of damage had it not had a nail driven through it, also the cables were installed in the correct cable zones according to BS7671 so nothing should've been fixed there in the first place and RCDs/RCBOs were installed in order to protect the person in the event they decided to drive a nail through a cable"

    • @stuartcraigon2003
      @stuartcraigon2003 2 ปีที่แล้ว

      @@joefrayling9263 are you for real! Zones! Had it not had a nail driven through it!
      You do know that no normal person knows or gives a shit about zones!
      As for RCD etc I've seen brand new out of the box units fail to operate, how many people religiously get their fixed wiring regularly inspected, just because they are fitted doesn't mean they will operate.
      You've obviously not tried putting a nail into capping because it's bloody obvious the substrate has changed and something isn't right!

    • @joefrayling9263
      @joefrayling9263 2 ปีที่แล้ว +4

      @@stuartcraigon2003 no I havnt put a nail through capping in a long time because I'm not a moron and I stopped using it in favour of oval tube a long time ago.
      Also yes they fail (were talking rewire new install here btw I feel like that needs to be said) but that is why we test them to ensure that they are working properly if they are not working properly after just being installed and they are left there then that spark is a twat and shouldn't be anywhere near electrics.
      It doesn't matter wether or not everyone knows about them (cable zones) the fact is they exist and they exist for a reason and that is to protect our ass when some dinlow puts a nail through a cable if they were in the right cable zone then there is no reason someone couldn't have got informed on how cables are installed and where prior to banging nails in the wall left and right.
      And yes had a nail not Been steamed Into the cable that was installed in a zone invented to try and mitigate exactly that and that was also protected by a properly tested and working RCD/RCBO the cable would've been fine and free from damage in that environment for the foreseeable future thus not requiring any further mechanical protection (of which capping offers next to fuck all) but because some divvy couldn't be bothered to spend 5 minutes learning about where cables might be they did in fact drive a nail into it.
      RCDs were invented to protect people using the electricity cable zones were invented to protect electricians from getting collard by people who are dimp enough to bang a nail through a wall in the general vicinity of an electrical accessory, it puts the blame back on whoever nailed the cable as opposed to whoever installed the cable

    • @joefrayling9263
      @joefrayling9263 2 ปีที่แล้ว +4

      @@stuartcraigon2003 also just to back myself up about being to lazy to learn I typed into Google literally just now "where are cables likely to be in my house" and the very first thing that came up was a GSH video about "the prescribed zones for wiring cables on walls" try it yourself not even 5 minutes to learn less than 10 seconds.
      "I didn't know" isn't a valid excuse for anything in this day and age where Information is so readily accessible

  • @NivagSwerdna
    @NivagSwerdna 2 ปีที่แล้ว +3

    "Mechanical Protection" hm... that plastic conduit isn't going to save Betty Crocker's nephew when he nails the ducks to the wall... but the RCD might.

  • @coralbay00
    @coralbay00 2 ปีที่แล้ว +1

    I use oval for speed and neatness. I am on the understanding that the plaster can affect the insulation? Deterioration over time?
    Clipping direct if one chooses to do so, would be done in prescribed zones so compliant 🤷‍♂️

  • @pdmpdm999
    @pdmpdm999 2 ปีที่แล้ว +3

    Thank you I live in New Zealand and we have the same problem here, everyone is in a race to the bottom. Let’s do it better for the customer and for our own pride

    • @tncorgi92
      @tncorgi92 2 ปีที่แล้ว

      Unfortunately our global economy has been suffering so long that cutting corners is the only way some tradesmen can keep their heads above water.

  • @joefrayling9263
    @joefrayling9263 2 ปีที่แล้ว +6

    Its an interesting subject but I doubt not having capping installed would win a court case provided everything was done correctly, the capping thing is open to interpretation it's an engineering judgement situation.
    In your example old Betty carking it because a cable was damaged and she washed the wall the 2 people at fault would be the plasterer and the sparks the plasterer for damaging the cable and not alerting anyone and the spark for not carrying out proper testing of the installation because that damage capping or not would show up when you do you tests.
    Would it have been damaged if capping was present, probably but that still doesn't negate the fact that the tests weren't properly carried out so I doubt it would hold much weight.
    The other arguement would be an external factor the old nail through a cable that we've all seen in this scenario capping wouldn't have prevented the damage but if presented with that the counter to it would be cables installed in the correct zones and RCD protection if they are done as per the regs then the capping argument would be null and void since the whole point of cable zones and RCD protection is to stop people putting nails through cables and the stop them being fried if they still do

  • @rmhblain
    @rmhblain 2 ปีที่แล้ว +5

    "An Old Duffer" - are you flirting with me again Thomas? 😍

  • @Chris_In_Texas
    @Chris_In_Texas 2 ปีที่แล้ว +12

    Forgive me for asking, however, as I am in the US, how is plastic capping any good for wire protection in brick/concrete walls? If there is a drill or nail, going though concrete, not sure that a thin plastic capping would save the wire from that? Shouldn't it be steel capping to provide protection against nails / drilling etc? Keep up the good work sir! 👍

    • @callimero2409
      @callimero2409 2 ปีที่แล้ว +1

      Even metal capping wont stop a nail,, and then it’s proper pain to repair cable

    • @alhughes9698
      @alhughes9698 2 ปีที่แล้ว +1

      Even steel capping won't protect against a hammer and nail or drilling.

    • @Benzknees
      @Benzknees 2 ปีที่แล้ว

      It used to be all galv steel capping here too, but plastic is cheaper & easier to work with. I agree it's crazy, you may as well not use it.

    • @CraigJFW
      @CraigJFW 2 ปีที่แล้ว

      its not, it was originally intended to protect cables from the plastering. ive found a few over the years kitchen fitters going straight through it fitting cupboards and just turning the tripped circuit back on, if it stays on!

  • @vukasincmiljanic9776
    @vukasincmiljanic9776 2 ปีที่แล้ว

    Tomas, you are right, I am an electrician in Norway and here the cable that you use for installations is illegal according to the law and rules to be used without a channel, pipes because the cable does not have double insulation to grounding. Here it is a cable type PR 2x2.5 +2.5 we can use this cable in open installations where inspection is possible. For installations that are covered and hidden, a double-insulated cable or a corrector tube with conductors is always used, here are examples of PFXP cables or TECON

  • @stephenwilshaw3052
    @stephenwilshaw3052 2 ปีที่แล้ว +4

    Sorry Tom, I have to disagree with you on this one.
    The most likely cause of damage to any cable in a domestic wall is Betty knocking a nail through it when she's putting up her grandchild's graduation photo. Plastic capping will offer no additional protection whatsoever to the cables from that.
    Mr Lawyer might well ask in that case why did you charge Mrs Crocker extra for capping which offers no extra protection when, if that was your aim, there are other solutions available to you specifically designed to achieve that end.
    Indeed, a lay-person seeing capping may well think it is there to offer protection. The home--owner may, as a consequence be less careful about their nailing, in the mistaken belief that if they do hit the capping, it will protect the cable (and them). Wrong, it won't!

  • @peterwentworth9181
    @peterwentworth9181 2 ปีที่แล้ว +8

    Plastic capping doesn't give any protection whatsoever from drills or nails being hammered in to a cable.
    As long as cables are in the correct zones, ie straight up and down where there is an outlet l can't see the problem with direct clipping.
    More effort should be made to make sure correct RCD,RCBO and MCB are in place and fit for purpose.

  • @kevinpoore5626
    @kevinpoore5626 2 ปีที่แล้ว +1

    Well I am from the other side of the pond and yes our construction techniques are different but when it comes down to it you got to protect your product AKA The wire and if you are a plumber the pipe capping nail plates hardened sleeves whatever it takes when your names involved you don't want that call you up the good work

  • @Kikz-1v1pinginit
    @Kikz-1v1pinginit 2 ปีที่แล้ว

    From Australia, your content in terms of business and how to set up and work towards growth has driven me to take the next step and invest alot into my electrical business. one can never forecast the future but I'm confident in my own ability to succeed. Thank u for the extra motivation.

  • @shlepkovakltd4881
    @shlepkovakltd4881 2 ปีที่แล้ว

    Mr Nagy, Thank you for advertising our company. Mrs Crocker is very good customer. She has lot of work from us, we do electric, gas, tiling, plumbing, plastering and she is very happy. You do not need to concern with her falling down stairs - we fitted S&K stair lift 3000™ for her last week, she now very good on the stairs. We will in future use cap you mentione when doing electricity work - I have purchase baseball caps for my employee to wear when doing electricity - they will wear this instead of cowboy hat - we save these for gas works.

  • @dannycrooks8462
    @dannycrooks8462 2 ปีที่แล้ว +5

    Been in the high court due to a health and safety accident believe me you never ever want to be in that situation the company had done nothing wrong but still an awful thing to go through it was lucky the company followed all health and safety training and had all proper procedures in place it would have ended badly if they hadn't

    • @tncorgi92
      @tncorgi92 2 ปีที่แล้ว

      It's bad enough that the company gets that kind of publicity, whether or not they're vindicated isn't going to matter to a lot of potential customers.

  • @calvinhale9913
    @calvinhale9913 2 ปีที่แล้ว +1

    Firstly TN is a youtube legend BUT I can't believe he let Artisan get to 100K first :) RE: This video, the blue book is non-statutory and clipping direct is ok if all other regs are abided by. Yes it looks better and I agree with Mark The Spark, oval conduit actually saves time and therefore money and does look better. Capping is a must on block walls that will be bonded out or even dot'n'dabbed to protect against the plasterers trowel, but if you are doing a standard rewire that damage if very very unlikely, again though, I agree it does look better and does set you apart from those who don't bother, but you can't really throw the regs at it.

  • @timbo19
    @timbo19 2 ปีที่แล้ว +17

    Sorry completely disagree with you on capping. ALL it does is give some protection from plaster's trowels. It gives bugger all mechanical protection once buried and those who use metal capping never earth it so potentially creating more of a hazard. Omitting capping doesn't save time as often it's ballache to get cable clips to stay in the walls depending on the type of masonry. Far better to fit conduit, whether that be oval or round and if you want to achieve mechanical protection then do metal conduit (unless that's too much effort?). That way you can easily rewire in future without opening up existing chases.

    • @CoulterTravel
      @CoulterTravel 2 ปีที่แล้ว +2

      Spot on, this video is utter bollocks from start to finish.

    • @coyote5735
      @coyote5735 2 ปีที่แล้ว

      @@CoulterTravel What happened to street lighting and commercial work supplanting domestic house bashing I thought that was consigned to the past? My guess is he baulked at the low rates subbing to a subcontractor subbing to the main contractor.................crumbs from the table.

  • @MrTobarac
    @MrTobarac 2 ปีที่แล้ว +1

    in Malta we all still pass all cables through conduit...and it makes sense if you want to pull another cable on a future date

  • @EXFElectrician
    @EXFElectrician 2 ปีที่แล้ว +1

    I can see the point your making, it dose make you look more professional, but installing plastic capping or oval conduit. Dose not provide much much protection, we have all been there installing practice capping and it cracks or brakes. Would you go back to installing earthed metal conduit ?

  • @adammiddleton3362
    @adammiddleton3362 2 ปีที่แล้ว +1

    As electricians we all know that capping does not offer mechanical protection against a nail or screw but does offer protection against the plasterers trowel.
    On rewires, where narrow chases have been made, the plasterers trowel will cover the width of the chase, therefore it is unlikely the plasterers trowel will damage the cable. Similarly, where dot and dab is used, there is no risk from the plasterers trowel.
    However, I do agree that by installing capping, whether on a rewire, dot and dab walls or walls that are being directly plastered, it is perceived as being better.
    Many years ago, I was working on a project, where metal capping had been installed. There was a fault with one of the slave telephone points. A BT engineer came out and said that the he suspected that one of the cables had become damaged, perhaps by the plaster. I explained that metal capping had been installed to provide protection against the plasterer and he told the client that we were wrong to have installed metal capping as this could have damaged the cable during installation 🤷‍♂️and could have caused damp to penetrate the cable. I couldn’t believe my ears.
    The client complained to the builder who we were working for and to appease the client we ran in a new telephone cable.

    • @Emin3m1986
      @Emin3m1986 2 ปีที่แล้ว

      Mate, I came across a similar problem few years ago. That BT Engineer was right.
      Since then I never use capping at all. If anything I’m chasing the wall deep enough (as long as the wall allows) to be impossible to be damaged by other trades (plasterer).
      Not even metal conduit will give you protection from drill bits.

  • @acelectricalsecurity
    @acelectricalsecurity 2 ปีที่แล้ว

    Your right about the regs, there was a case of a guy, came home pissed, put the landing light on, bulb blew, he decided it was a good idea to stand on a chair, hanging over the stairs, in the dark, and change the bulb, he fell, and sued the council and won, because some switched on lawyer found a reg that the light position didn't comply with the regs, I think he got around £100k. It happened in flint North Wales.
    And I recently used this example with a customer, who wanted me to fit a light over the stairs where he couldn't reach, I refused to do it, he understood after reading the story.

  • @lossantoslols
    @lossantoslols 2 ปีที่แล้ว +2

    Id say it takes longer to clip than put capping/conduit in...

  • @wibbley1
    @wibbley1 2 ปีที่แล้ว +1

    Capping gives protection from the plaster's trowel. It is vey easy to nick the cable. I notice that Tom does not bury his capping deep enough to allow a decent depth of plaster, so to avoid cracking, I can see why plasters would remove it.

    • @stuartwilliams8663
      @stuartwilliams8663 2 ปีที่แล้ว

      🤔 The trowel used for either the base coat or render is normally a plastic float and definitely not capable of damage to a cable ! The metal float is only used for the skimmed top coat .
      I've only been in the Industry 35 years, so what would I know 🙄🙄

  • @nedperry8527
    @nedperry8527 2 ปีที่แล้ว +4

    I always use conduit and use metal strapping to hold it in place , no need for grommets and can pull wires in and out after

    • @ryaneasterlow8247
      @ryaneasterlow8247 2 ปีที่แล้ว

      Why no need for grommets ??

    • @mikeselectricstuff
      @mikeselectricstuff 2 ปีที่แล้ว +2

      @@ryaneasterlow8247 if the end of the conduit passes through the hole in the backbox, this protects the cable from abrasion

    • @nedperry8527
      @nedperry8527 2 ปีที่แล้ว +1

      The round conduit goes straight into the metal back box

    • @garethblake3941
      @garethblake3941 2 ปีที่แล้ว +1

      I totally agree much prefer to use conduit for all the reasons express.

  •  2 ปีที่แล้ว +2

    I am not at electrician by trade, but the frasing in the regulation book sounds weird. You have a regulation that states that you need to evaluate if you instalation has proper mechanical protection the question is to what extent?Proper mechanical protection if someone is pressure washing their walls, if someones water piper burst,... there are a million possible coincidents that cant happen and you can interpret those regulations in many ways. Its just weird to me.

    • @rossthompson1635
      @rossthompson1635 2 ปีที่แล้ว +1

      Most safety regs are vague like this, often stating you must do what is "reasonably practicable".... it is up to you to try to decipher what that is. Tom's approach was what I was taught - imagine yourself in the dock explaining why you did (or didn't) do something. If (in this case) the regs clearly stated that cable run in plaster must be (or doesn't need to be) capped, it would be so much easier!

  • @bombadk
    @bombadk 2 ปีที่แล้ว

    Like you videos. In Denmark where i come from, we never use capping. Some times, we put the conduit in the wall for easy replacement, but never for protecting the cable.

  • @andyjennings2061
    @andyjennings2061 2 ปีที่แล้ว

    Same problem in Gas Industry you could do everything to regs and to the letter, but gas safe and courts would still find something you " should have done" plus lots of clients want Rolls Royce Jobs for Mini money. Such a Vicious circle and why corners get cut.
    Top channel and great content ✊🏻

  • @neilhazell9057
    @neilhazell9057 2 ปีที่แล้ว

    I always fit over size oval pipe no matter what.And it's easier if any alterations needs doing as you can pull the cable out and push a new cable down. great video 🙂

  • @christopliss9947
    @christopliss9947 2 ปีที่แล้ว +1

    Tom, I love your passion for what you do, you are a credit to your trade. I also love your scenarios in your presentations. You should do some lecturing at colleges, you certainly would keep your audiences attention 👍

  • @idi0tdetectioninprogress
    @idi0tdetectioninprogress 2 ปีที่แล้ว +7

    Take each installation on its individual merits, circumstance and nature of build. Thats the skill in being qualified and interpreting the application of the Regs accordingly. Toms losing the plot of late, crying over ring mains, crying over RCD's, and this Rumpole of the Bailey lark is cringe.

    • @BritishBeachcomber
      @BritishBeachcomber 2 ปีที่แล้ว +1

      But Ring Final Circuits are a really bad thing. Only introduced to save copper in the 40's. If a line/neutral break occurs the cable will overheat before the MCB trips.

  • @leighbrowne8863
    @leighbrowne8863 2 ปีที่แล้ว

    Couldn’t agree more, if it looks neat it’s normally wriht. I’m currently rewriting a property that was retired by a builder in 2000. Capping was the least of the customers worries in this case!

  • @jemseed
    @jemseed 2 ปีที่แล้ว +7

    To be fair I 100% agree with the professional look to capping, but it does not offer mechanical protection and I believe it would hold in a court of law. If the regs are to be interpreted as you have then surely it would mean the use of metal conduit everywhere as capping offers no protection after the wall has been plastered. I mean capping can protect from a plasterers trowel and such, but a nail being hammered into a wall then no . The only other benefit in some cases is if you have a fault you can pull the cable through and rewire.

  • @leesworld3659
    @leesworld3659 2 ปีที่แล้ว

    I remember being told many many years ago that capping offered protection from chemical dryers used in some plaster....

  • @CoulterTravel
    @CoulterTravel 2 ปีที่แล้ว +6

    In this video (linked below - how I install back boxes in lathe and plaster walls) you’re not using capping or oval, so you’d better hope Betty isn’t wiping any walls down there!
    But in my opinion much worse is the fact that you’re not even following cable zones? You come up and got at a right angle to an accessory?
    You’re in no position to start name calling other electricians out, my friend, with shit workmanship like that, that could 100% end you in court. Always follow the zones. Not everyone knows they’re there, but you’re doing the best you can to at least put them in the right place.
    th-cam.com/video/UaSWNftCEc0/w-d-xo.html

  • @Darkonon
    @Darkonon 2 ปีที่แล้ว +1

    Tom, probably not the best video to comment this on but have you seen the street lighting electrician R9YND on here? He seems a top guy from just watching his content like fairly thorough so when you are saying in your videos whether people know about street lighting for particular things perhaps reach out to him? He's scottish so things might be a bit different but he might be willing to help you out as he does seem really knowledgable in that field.

  • @neilbridgeman7768
    @neilbridgeman7768 2 ปีที่แล้ว +9

    Could have saved you 15 minutes:
    1. Capping is not mechanical protection
    2. It cannot be earthed so is pointless.
    3. You will never go to court for not installing capping.

    • @dannyboisparky
      @dannyboisparky 2 ปีที่แล้ว

      Still 💩practice for the majority. Industry standard nowadays of not giving a flying f for the next person

    • @neilbridgeman7768
      @neilbridgeman7768 2 ปีที่แล้ว +4

      @@dannyboisparky capping cannot be used for rewiring. If people want to assist in rewiring in the future then they should consider conduit drops, not capping. Capping is only to protect the cable from damage from the plasterer’s trowel.
      To be so unkind to electricians that don’t install capping in all circumstances and state they are ‘mediocre’ is pretty poor. Especially when Tom uses expanding foam to fix back boxes and conduit to the wall 🤔

    • @dannyboisparky
      @dannyboisparky 2 ปีที่แล้ว

      @@neilbridgeman7768 conduit absolutely, yes. Capping is rather pointless but would still pick that over nothing.
      Yeah this video is rather strange when on his last couple of videos was a mix bag of cables chased in walls with all round band holding the cables back and drops with quite short conduit to points but then some were spot on with conduit between boxes

  • @TheGorillahands
    @TheGorillahands 2 ปีที่แล้ว +2

    Have all of your installs in your electrical career had capping ? Just asking the question.

  • @Waynesworldofgaming
    @Waynesworldofgaming 2 ปีที่แล้ว

    Completely agree with you Tom, I always use oval capping and a first fix looks so much better and neater

  • @clarkneil1980
    @clarkneil1980 ปีที่แล้ว

    When we had building work done we chose on price, we learnt from our lessons and when we had all windows and doors replaced we went with reputation and not price, made no difference, regret not using our original builder..

  • @raminjavadi2413
    @raminjavadi2413 2 ปีที่แล้ว

    Dear Tom, The only part of your argument that is correct (in my opinion) is the part which state it looks like better and nicer (it even does not fall under more professional), that's it, rest of it is just justification of the logic or reasoning that is not actually in the Blue Book. It is absolutely your preference and I respect that.

  • @TheMidbro84
    @TheMidbro84 2 ปีที่แล้ว +2

    I’m sure they can’t use the regs book in a court as it’s a non statuary regulation

  • @BritishBeachcomber
    @BritishBeachcomber 2 ปีที่แล้ว

    The main point is... Document, for the customer, exactly what you have done and why. Always CYA.

  • @alantorrance6153
    @alantorrance6153 2 ปีที่แล้ว

    Thanks Thomas. A great resume of what is needed. Better to go that extra half mile and find you didn't need to go there, than to get there and find you missed the mark.

  • @dvrn86
    @dvrn86 2 ปีที่แล้ว +1

    In NI we track our wall so our boxes are inset and our wire is ran in pvc conduit. if you ran twin and earth directly onto block here you wouldn't get another job again.

  • @andysims4906
    @andysims4906 2 ปีที่แล้ว

    I was on a job about 6 months ago . Customer nailed a cable . Cables were buried straight in the render I had to chase the whole wall to replace the cable. On the same job ceiling fittings were hanging loose as they used red plugs straight in the plasterboard. One lighting circuit for the whole house and guess what they were in the NIC . The point I’m making is if someone can’t be bothered to use tube or capping chances are the rest of the job is is going to be shoddy

  • @Fanta....
    @Fanta.... 2 ปีที่แล้ว

    6:33 "Dicky heart, she pops her clogs, the old duffer!" love it.....

  • @escfxp
    @escfxp 2 ปีที่แล้ว

    Thomas Malory Nagy - whenever I see you post a video, my bell goes ding-a-ling-a-ling.

  • @MrSammyb1234
    @MrSammyb1234 2 ปีที่แล้ว +1

    Really enjoying these "Nagy Knows" / "Top Tom Tips" / "Nagy Knowledge" videos. Any chance you could get them in a playlist as I'm not sure if I've missed any. So hard as someone who has recently passed their 18th edition to be able to retain all the information, but having someone talk through real world examples of where the regs come to life really helps. So, thanks!

  • @Sean006
    @Sean006 2 ปีที่แล้ว +5

    The answer to Tom's La La Land wishful thinking is building inspectors who inspect the wiring installation at various stages of the installation to ensure the safety of the job...it isn't going to happen in the UK. This is a race to the bottom. How do you think Grenfell tower happened....govermnet deregulation killed people. Full stop. Sod the lawyers!!
    BTW Twin & Earth has basic insulation (each cable is insulated) plus supplementary insulation (the insulated conductors have a gray protective sheath(=)...surely. The capping provides additional supplementary insulation - probably not reinforced - so beyond BS7671. A prosecution lawyer would struggle to prove that the electrician hasn't taken account of that in their design....don't even mention RCD's or RCBO's as additional protection for the final circuits. What the fcuk are you asking for ....all the cable is to be SWA????!!!
    Or are you just trying to justify your West Hampstead prices because you want a villa on St Dominique with a fashion model girlfriend!!!....I know I do.

    • @daxw2460
      @daxw2460 2 ปีที่แล้ว

      No fair mate. He's just saying as we get thought in the college's.

    • @Sean006
      @Sean006 2 ปีที่แล้ว

      @@daxw2460 I would use it too. But I don't think it is a requirement of 18th Ed. To suggest you could get into legal difficulty if you didn't use it may be wrong.
      Fair enough it creates a better end result. But I'm not sure one would end up in court if one didn't use it.
      As Mr Nagy pointed out in his video, there were points where capping couldn't be used in one of his jobs for practical reasons....that didn't mean he was suddenly at risk of prosecution. He was relying on his 'skill & judgement' as per BS7671 to tell him when & if to use it.
      Most of his video was talking about creating a professional look....to impress the other trades. Nothing to do with safety of the electrical system IMO.

  • @brianwoodruff4891
    @brianwoodruff4891 2 ปีที่แล้ว +3

    Capping protects cables from corrosive alkaline in cement when it's used to render walls which is not common these days but 30 years ago it was very common for walls to be plastered with sand and cement then skimmed . I've never regarded 2mm or less of plastic as mechanical protection .

  • @anotherledfreak8649
    @anotherledfreak8649 2 ปีที่แล้ว +4

    Capping is crap. I wouldn't use it UNLESS the customer specifically asks for it. I always use conduit as I feel it gives better protection and (once plastered) if Betty Crocker wants an alteration it's easier to remove (ring circuit) and reroute. Capping just doesn't work. Zero protection from nails so why use it? At least plastic conduit "might" cause the nail to deviate. Capping won't even metal stuff.

  • @tangoengineering
    @tangoengineering 2 ปีที่แล้ว +1

    Plastic oval or capping is of no use against penetration metal capping is the best but I've never seen you use it

  • @Souped-up-Saiyan
    @Souped-up-Saiyan 2 ปีที่แล้ว +2

    Non of the regulations mentioned require capping. Perhaps it may provide protection from other trades while building work is in progress but under normal use it doesn't do anything

    • @dxnpaniicz5663
      @dxnpaniicz5663 2 ปีที่แล้ว +1

      Regulation and good practice/pride in your work are separate things

    • @Souped-up-Saiyan
      @Souped-up-Saiyan 2 ปีที่แล้ว +3

      @@dxnpaniicz5663 not really. It requires needlessly butchering more of the wall and plaster doesn't stick to plastic very well either. All this for no benefit

    • @dxnpaniicz5663
      @dxnpaniicz5663 2 ปีที่แล้ว +1

      @@Souped-up-Saiyan metallic capping is a fool proof way of ensuring no cable strikes are made from homeowners, doesn’t cost a lot, priced into job. Again regulation and good practice are separate things, stands you out from the rest, amount of compliments I’ve had from other trades when installing it that has led to more work is endless

  • @BritishBeachcomber
    @BritishBeachcomber 2 ปีที่แล้ว

    Best house I ever owned had all the cables chased in with steel conduit. Rewiring was so easy.

  • @paulthompson5416
    @paulthompson5416 2 ปีที่แล้ว +6

    20mm Conduit every time.

    • @e5Group
      @e5Group 2 ปีที่แล้ว +1

      👍👍👍👍👍

  • @HeathenGeek
    @HeathenGeek 2 ปีที่แล้ว +2

    what's that thing about going to war with the army you have, not the army you want? Same applies here.
    It would be great, fkn awesome if all pricing was for the same standard: working 'from' the regs, not 'to' them.
    But the reality is you can be as awesome a sparky as you want, sitting at home waiting for the phone to ring, while somebody else is out there getting it done. . . without having to include capping in the price that undercut you.

  • @rossthompson1635
    @rossthompson1635 2 ปีที่แล้ว +2

    My property has metal stud frame walls, the cables just hang loose inside (UK property, 14 years old). I'm sure that isn't adequate protection - and the metal frame isn't earthed either. Also where the cables are unprotected in the loft (in both this and a previous property) I found at least one cable had been gashed to the copper, presumably by whoever was cutting the loft insulation. UK new builds... not great!

  • @Rustynail3r
    @Rustynail3r 2 ปีที่แล้ว +1

    Pretty much disagree with everything said in this. Which is unusual for your videos.
    1) firstly, and this is a big one. BS7671 isn't a legal document and can't be used as such in a court room.
    2) sure capping looks nice but never seen plastic or metal capping / oval conduit stop a nail or screw.
    3) everything is RCD protected now and youve done you're cable calcs, so you have done your bit to protect the installation.
    4) clipping cables when done correctly look incredibly neat.
    5) the only possible reasons to use mechanical protection would be for future rewiring purposes. In which case you're going in with 20mm tube. Even then, if you wanted to protect it fully you would be looking at galv tube so that a screw couldn't go through the plastic tube.
    Other than that...capping is pointless. As long as you don't have a heavy handed plasterer following you around.

  • @tonywebb9909
    @tonywebb9909 2 ปีที่แล้ว

    Some really posh jobs in the old days had us use metal conduit with a bend into the joist run, these would be the wealthy house on Bishops avenue. But you had to enamel paint any scratches on the pipe or rush could show through

  • @TeamSimpsonRacing
    @TeamSimpsonRacing 2 ปีที่แล้ว +10

    Capping is pointless, especially plastic. I work to a very very high standard but never install capping unless its a completely bare wall where the cables could get damaged before of during dot and dabbing. Even then you have to test your work before its been energised to confirm that hasn't happened. The regs required capping in the past when RCD protection wasn't around and also to protect from the lime in old plaster which used to burn into a cable over time. Plastic capping will not stop anyone putting a nail through a cable etc. Yes it looks good but thats as far as it goes.
    To add, in your last video you had one drop on your rewire with multiple cable and you said you just used cable banding as there are too many cables for capping!

    • @d.newsom110
      @d.newsom110 2 ปีที่แล้ว

      14:00 If you decided to watch to the end of the video before you rant he clearly states that yes in some situations its not possible. But it shows a court or a regulator that you made an effort to be safe IF the situation arises that its necessary. Its a low cost relative to the cost of damages after being found guilty in a court room.

    • @keigun5546
      @keigun5546 2 ปีที่แล้ว +2

      Exactly. There is also reasons why UK is one of the only countries I know of that does capping.
      It might look neater thatncables thrown in the wall, but cables neatly fixated into it look just as good, or sometimes even better.
      All it does from a safety standpoint, talking of plastic capping, is that the plaster doesn't make contact with the cable itself.
      And that is only safer if the cable is not made to be in contact with plaster. I don't know if Twin and Earth is.
      For anything else, like damage of cable, you will have to test your installation anyways before energizing.

    • @TeamSimpsonRacing
      @TeamSimpsonRacing 2 ปีที่แล้ว +3

      @@keigun5546 modern plaster is none corrosive and fine to be directly on PVC cables 👍

    • @keigun5546
      @keigun5546 2 ปีที่แล้ว +2

      @@TeamSimpsonRacing Fair enough.
      I am from germany and our normal cables for in or below plaster are PVC sheathed with PVC filler and PVC isolated wiring.
      Just didn't know what UKs standard cable was made out of.
      Furthermore, capping like that is not even sold here.
      Personally I don't see the point.
      As well as that regulations by EN/IEC/CENELEC or adjusted for germany DIN/VDE specifically specify that wiring like we use can be installed in or below plaster without consequences, of course as long as everything else is also up to code.
      You might know cables like NYY-J being used in the UK as replacement for Tuff Sheath, for example.
      That cable is standardized by us, for in house installation we use NYM-J.
      Its not as UV or *continuously submerged* water resistant, as well as not as hard as the NYY sheathing.

  • @RandyDarkshade2
    @RandyDarkshade2 2 ปีที่แล้ว

    BAck in 1999-2000 when I was on work experience with a local spark, we always used capping on a new install and/or rewire as and when it was practical to do so. As for mechanical protection it isn;t going to stop DIY Bob coming along to put a shelf on the wall and drilling into it (I know, I've done it myself many years ago lol and so has my stepdad) However, it will protect it from the plasterer and their trowl.