2 crusher plant hai lagvag 1100 ampere load me chalta hai lekin isi full load me total (500 kvar) capacitor ek sath discharge ho jata hai or fluctuations ke bajay se plant trip ho jata hai lekin a to full load me ek sath discharge hona Nehi chaiye .A fault mera one year me 10/12 bar hua, iska solution kya ho sakta hai sir please
Aur ek cheez check kijiye , app ke APFC panel me proper cooling ho Raha he ya nehi , ek reason esa bhi he jab capacitor over heating hota he tab relay sara capacitor bank ko off kar deta he
1.Check your wiring of ct is proper or not. 2. Check your under current protection setting in the APFC relay. 3. If your load is very low then it may affects. 4. If there is no lower range capacitor bank ( 3/5/10 ) in APFC relay. It may creat problem.
Namoskar sir bahuti knowledge Mela ,,sir Mera ek Question tha ...pahili bat a hai ki mera Target PF 0.99 hai, but jab load 20/30 ampere ho jati hai tab Mera pf 0.70 ke ass pass lag ho jati hai. Tab bahut der der ke bad kavi kavi 5/10/15 kvar capacitor ON to hota hai but 1 second ke undar turant OFF ho jata hai pF maintain ho Nehi pata.sir ho sake to iska upay bata dijiyega, namaskar
Mera CT 2000/5 ka hai,aap suggest kiye hai ki minimum current 30 ampere hona chahiye lekin Ampere 30 ke niche 15/20/25 amp ho Raha hai,ek or bat hai ki Required kvar 15/20 kvar show ka bad vi capacitor on hata to hai lekin one second me band ho jata hai or PF wohi 0.70/0.80 lag Rahi jata hai...
Agar app 2000/5 CT use kar rehe hen and under current Setting 0.015 me he to 30 se niche jayega to capacitor bank active nehi hoga , agar load fluctuations ho Raha hoga tab bank on/off hoga ( in case of VFD load )
very good presentation. my local l&t tech team not informing this with clarity.
Welcome 😊
With out adding capacitor also its showing ocom what to do sir
Check my APFC part 6 video in my playlist
Sir 12 stage ka relay pf onload me 0.99 nahi aa raha hai
Ouur 0.345 to0. 350 bata raha hai sir
APFC relay ke upar mene 7-8 video upload Kia he usse sehi se check kijiye app ka problem solve ho jaega
4110 VAF +PF meter
AAP se baat kerni hai
Hann bataiye
Sir Mai bahut presan hu mera power factor set nahi pa Raha hai plz helf me
Thanq sir
Welcome 😊
Kwh reding kvah ki reding bhag raha bahut
What is your KVA reading and kw reading
PF मेनटेन नही है
Me APFC relay ka 8 video play list me dia hun jab video dekhiye agar fir bhi nehi ho Raha he to comment kijiye
Sir or ek Question tha apfc related,
Question kar sakte hai sir?
Hann puchiye
2 crusher plant hai lagvag 1100 ampere load me chalta hai lekin isi full load me total (500 kvar) capacitor ek sath discharge ho jata hai or fluctuations ke bajay se plant trip ho jata hai lekin a to full load me ek sath discharge hona Nehi chaiye .A fault mera one year me 10/12 bar hua, iska solution kya ho sakta hai sir please
1st check 500 kvar capacitor kyun discharge hota he
Proper observation kijiye kya alarm aa ker apka capacitor bank discharge hota he
Aur ek cheez check kijiye , app ke APFC panel me proper cooling ho Raha he ya nehi , ek reason esa bhi he jab capacitor over heating hota he tab relay sara capacitor bank ko off kar deta he
San setting kr di koi alarm bhi nhi h uske bad bhi relay auto nhi on ho rhi h sir
I will do another video within 2-3 days
Check relay me jo 1, 2, 3 ... 12 ( for etaSMART 12 R ) , koi capacitor bak active he ya nehi in auto mode
Please provide me suggestions
@@itzelectrical auto me nahi on ho rha h sir
16R ETA smart
I have some problem how to contact you bro
You can ask in comment section I will give my best to solve your problem
@@itzelectrical in Pf pannel meter it’s showing 0.999 but in department meter it’s showing 0.654
1.Check your wiring of ct is proper or not.
2. Check your under current protection setting in the APFC relay.
3. If your load is very low then it may affects.
4. If there is no lower range capacitor bank ( 3/5/10 ) in APFC relay. It may creat problem.
@@itzelectrical pls share your mailid want to contact you bro
@@itzelectrical pls share your mail I’d want to contact you I’m not understanding problem
Very good brother 🎉
Welcome 😊
Namoskar sir bahuti knowledge Mela ,,sir Mera ek Question tha ...pahili bat a hai ki mera Target PF 0.99 hai, but jab load 20/30 ampere ho jati hai tab Mera pf 0.70 ke ass pass lag ho jati hai. Tab bahut der der ke bad kavi kavi 5/10/15 kvar capacitor ON to hota hai but 1 second ke undar turant OFF ho jata hai pF maintain ho Nehi pata.sir ho sake to iska upay bata dijiyega, namaskar
App pehle Mera part 2 and part 6 video ache se dekhiye agar phir bhi nai hua then MSG kijiye
APFC relay Playlist me
Mera CT 2000/5 ka hai,aap suggest kiye hai ki minimum current 30 ampere hona chahiye lekin Ampere 30 ke niche 15/20/25 amp ho Raha hai,ek or bat hai ki Required kvar 15/20 kvar show ka bad vi capacitor on hata to hai lekin one second me band ho jata hai or PF wohi 0.70/0.80 lag Rahi jata hai...
App check kijiye load me fluctuations to nehi he ?
Agar app 2000/5 CT use kar rehe hen and under current Setting 0.015 me he to 30 se niche jayega to capacitor bank active nehi hoga , agar load fluctuations ho Raha hoga tab bank on/off hoga ( in case of VFD load )
Very Good sir
Keep watching 😊
Sir mujhe aap se bat karni hai
Text me no my Instagram I'd @itz_electrical, link in description
App sir bahut achhe se samjhate hai
Thank you
Mere play list me about 7-8 video he use dekh lijiye sayed aap ka problem solve ho jayega
Agar phir bhi problem aya to fir mujhe Instagram me message kijiye