Can we remove Neutral wire? Importance of Neutral wire

แชร์
ฝัง
  • เผยแพร่เมื่อ 12 ม.ค. 2025

ความคิดเห็น • 226

  • @tedlahm5740
    @tedlahm5740 4 ปีที่แล้ว +25

    Wonderful explanation of neutral conductor to Wye transformer.
    As usual you supply wonderful information.

    • @GauravJ
      @GauravJ  4 ปีที่แล้ว +1

      Glad it was helpful!

  • @outerspacekaloy
    @outerspacekaloy 3 ปีที่แล้ว +2

    I plugged a 110V television to a 220V outlet and had it blown in a few seconds, this explains that occurrence that happened more than a decade ago. Thanks Dr. Electrical Guy.

    • @goaliedude32
      @goaliedude32 3 ปีที่แล้ว +1

      That should never be possible. Wes the neutral missing somewhere? 220v receptacles should have a completely different shape so 120v plugs should never fit

  • @tedlahm5740
    @tedlahm5740 3 ปีที่แล้ว +2

    I reviewed the lesson a second time (8 months later) naturally even more informative. Thank you.

  • @mrsaad1282
    @mrsaad1282 4 ปีที่แล้ว +12

    It is really great, easy and direct explanation, once the person understands the idea precisely he would explain it clearly as you did. Thanks for your golden efforts

    • @GauravJ
      @GauravJ  4 ปีที่แล้ว +1

      Thank you 😊 🙏🏻

  • @santhoshkumar4455
    @santhoshkumar4455 4 ปีที่แล้ว +36

    Crystal clear explanation.. somebody give this guy a PhD 🤗

    • @outerspacekaloy
      @outerspacekaloy 3 ปีที่แล้ว

      He might have PhD in Electrical Engineering

  • @MrEZW
    @MrEZW 2 ปีที่แล้ว +3

    Dude thank you, I've been struggling with this for a couple years now & you explained it in a way that I almost instantly grasped! Hats off friend!

    • @GauravJ
      @GauravJ  2 ปีที่แล้ว

      Glad it was helpful ☺️ Do share and subscribe 😊

  • @wnicora
    @wnicora 7 หลายเดือนก่อน +2

    Fantastic video, I finally understood several subtleties of three phase systems in just one short video THANKS

    • @GauravJ
      @GauravJ  7 หลายเดือนก่อน

      Glad it helped!

  • @dmuth
    @dmuth 8 หลายเดือนก่อน +1

    I came to this video while trying to understand how neutral lines work. And now I'm subscribing. 🙂

  • @syedmuzammilabbas3097
    @syedmuzammilabbas3097 ปีที่แล้ว +1

    Wow, one of the best explanations i ever listened on TH-cam. I want to add some practical application of not using neutral wire. For instance in transmission line we can not provide a neutral wire as we don't connect load

  • @amuchoki6
    @amuchoki6 2 ปีที่แล้ว +2

    Great job! Simple to understand explanation.

  • @mdhussain363
    @mdhussain363 3 ปีที่แล้ว +1

    I found your channel today and watched 10-12 videos on one stretch, you are truly a gem ❤

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      Thank you 😊 do share and subscribe to my channel ✌🏻✌🏻

    • @mdhussain363
      @mdhussain363 3 ปีที่แล้ว +1

      Already done ❤

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว +1

      Thanks 😊

  • @keithwarren1517
    @keithwarren1517 4 ปีที่แล้ว +3

    Very great video. God bless you sir.

  • @justwelltariang2456
    @justwelltariang2456 3 ปีที่แล้ว +1

    Well done Sir. You have cleared my doubts which have troubled, me for so long. Thank you once again.

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      😊 great. Do share and subscribe to my channel ✌🏻✌🏻

    • @justwelltariang2456
      @justwelltariang2456 3 ปีที่แล้ว

      @@GauravJ already done

  • @bikashsharma382
    @bikashsharma382 2 ปีที่แล้ว +1

    Giving summary is fruitful at last

  • @abinshipo1
    @abinshipo1 2 ปีที่แล้ว +1

    Excellent practical explanation keeping theory as base. Good!

    • @GauravJ
      @GauravJ  2 ปีที่แล้ว +1

      Thank you 😊 do share and subscribe 😇

  • @tusharupadhyay
    @tusharupadhyay 4 ปีที่แล้ว +1

    Bro That explanation was very easy to follow
    Thank You!

  • @deadly_user779
    @deadly_user779 3 ปีที่แล้ว +2

    Thank you, I finally understood how the three phase system works

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      Great 👌 do share and subscribe to my channel ✌🏻🙏

  • @deemankar3927
    @deemankar3927 3 ปีที่แล้ว +1

    The most clear cut explaination I've ever seen 🔥🔥❤️👍👍

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      Thanks 😊 do share and subscribe to my channel ✌🏻👍🏻

  • @b.srinivas9567
    @b.srinivas9567 3 ปีที่แล้ว +2

    You simply mind blowing sir

  • @zakirhussain6157
    @zakirhussain6157 2 ปีที่แล้ว +1

    Very clear explanation.thank you very much sir.

  • @kashifshaikh2264
    @kashifshaikh2264 4 ปีที่แล้ว +2

    Explaining removed all doubts in my head❤️ tysm💯

  • @edenlumbanraja5541
    @edenlumbanraja5541 2 ปีที่แล้ว +1

    Cool. Explain in simple way

  • @PictureFlux
    @PictureFlux 3 ปีที่แล้ว +2

    I am a Student of Electrical engineering and I love your explanation ❤️❤️

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      Thanks. Do share and subscribe to my channel ✌🏻✌🏻😊

  • @ericberman4193
    @ericberman4193 6 หลายเดือนก่อน +1

    Good, informative video!

  • @kabandajamilu9036
    @kabandajamilu9036 4 ปีที่แล้ว +2

    So nice and educative sir

  • @unifiedsparks693
    @unifiedsparks693 4 ปีที่แล้ว +2

    Thank-you sir for super explaination
    You Made that easy for me❤️❤️

  • @dhh488
    @dhh488 2 ปีที่แล้ว +1

    Great video Gaurav, thank you.

  • @hussain55019
    @hussain55019 11 วันที่ผ่านมา

    Love,Respect and salutation brother from Peshawar Pakistan.

  • @sskprl
    @sskprl 3 ปีที่แล้ว +1

    Well explained. Very valuable information.

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      Thanks 😊

  • @thevardhan5673
    @thevardhan5673 ปีที่แล้ว

    1)Sir at 2:17 how loads will work without neutral wire or without low potential path for each phase.
    2) Sir in case of balanced single phase system do we need neutral wire ?

  • @BerHarSenSam
    @BerHarSenSam ปีที่แล้ว +1

    Thank you indeed for such a clear explanation of the importance of neutral wire.
    Would you please advise if presence of an RCD would help and if it would trip off in case there is a loss of neutral wire on three phase supply.
    Thank you.

  • @pavansangli1056
    @pavansangli1056 3 ปีที่แล้ว +2

    Bang on target 🎯👏 👌, great explanation sir

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      Thanks 👍🏻 do share and subscribe to my channel 😊✌🏻

  • @Akshay-zd3ox
    @Akshay-zd3ox 4 ปีที่แล้ว +1

    You are doing amazing work

  • @heronimousbrapson863
    @heronimousbrapson863 ปีที่แล้ว +2

    In North American practice, the wye point of the primary in wye-delta three phase transformer banks (wye-primary; delta-secondary), is often disconnected from the neutral to balance the secondary voltages. This allows the wye point to "float".

  • @SpkTrue7
    @SpkTrue7 3 ปีที่แล้ว +1

    Always great videos.Im learning alot Many Thanks. Gaurav J

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      Glad to hear that

  • @GregSauteur
    @GregSauteur 2 ปีที่แล้ว

    Sir you are a genius. Much appreciated your videos as u have the art of teaching

  • @tejaswinikurapati9085
    @tejaswinikurapati9085 4 ปีที่แล้ว +1

    Sir,ur giving clear explanation to us about electrical topics and thank you soo much sir for your videos
    Which are very useful for us.

    • @vinaychiplunkar1988
      @vinaychiplunkar1988 4 ปีที่แล้ว +1

      We need this kind of teachers who have all practical knowledge

  • @manaoharsam4211
    @manaoharsam4211 2 ปีที่แล้ว +1

    Great illustrations .

  • @avidrationalist7281
    @avidrationalist7281 3 ปีที่แล้ว +1

    Superb explanation...

  • @magendiranmanoharan8990
    @magendiranmanoharan8990 4 ปีที่แล้ว +1

    Thank you, very clear presentation.

  • @johnnyeboy33
    @johnnyeboy33 2 ปีที่แล้ว +1

    Awesome video mate thank you !!!

    • @GauravJ
      @GauravJ  2 ปีที่แล้ว

      Thanks 😇 do share and subscribe 🙂

  • @amararyan4613
    @amararyan4613 4 ปีที่แล้ว +1

    Nice explanation sir!

  • @TADISRINIVAS
    @TADISRINIVAS 3 ปีที่แล้ว +1

    Good explanation. Pl. explain about Neutral and Earth in AC transmission.

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      Sure we'll try for that. Do share the video 😊

  • @harithababu7906
    @harithababu7906 3 ปีที่แล้ว

    Great explanation....at 1:50 isn't it at 210 degrees?

  • @laxminarayanlala6850
    @laxminarayanlala6850 4 ปีที่แล้ว +1

    Very nice information , thank u sir

  • @vvkvarnasi7177
    @vvkvarnasi7177 3 ปีที่แล้ว

    Very good demo and explantion what happens if earth and nutral are connected to avoid earth missing in supply

  • @sawakoo448
    @sawakoo448 3 ปีที่แล้ว +1

    Very clear. Thank you Sir !

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      You’re welcome 😊 do share and subscribe to my channel ✌🏻😊

  • @vinaychiplunkar1988
    @vinaychiplunkar1988 4 ปีที่แล้ว +1

    Understandable with ur explanation

  • @MdSalauddin-ks7rp
    @MdSalauddin-ks7rp 2 ปีที่แล้ว

    Excellent vedio explaination with technical terms.
    Can you please make a new vedio on VFD and Soft starter programming and troubleshooting.
    Thanks

  • @aslamkhan-hw1fh
    @aslamkhan-hw1fh 4 ปีที่แล้ว +1

    Very good explanation

    • @GauravJ
      @GauravJ  4 ปีที่แล้ว

      Thank you Aslam. Do subscribe to my channel and share the video ✌🏻🙏

  • @syedislam4004
    @syedislam4004 4 ปีที่แล้ว +1

    Good presentation n explanation
    Just one question where does the neural current go in single phase system

  • @entrepreneurnepal2020
    @entrepreneurnepal2020 4 ปีที่แล้ว +2

    Couldnt get much better explaination

  • @zeeshanahmad7070
    @zeeshanahmad7070 2 ปีที่แล้ว +1

    Definitely superb 👍

  • @russellteejaymolina6736
    @russellteejaymolina6736 3 ปีที่แล้ว +1

    That was nice and clear explanation, I just have one question in mind, in the unbalance load without neutral, voltages in all three phase will become unbalance too, but where does the unbalance current path back to the source if there is no more neutral conductor.

  • @nikhilsreekumar5744
    @nikhilsreekumar5744 3 ปีที่แล้ว +1

    Sir your way of teaching is good please make a video on floating neutral

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว +1

      Thanks. Do share and subscribe to my channel ☺️✌🏻

    • @nikhilsreekumar5744
      @nikhilsreekumar5744 3 ปีที่แล้ว +1

      @@GauravJ Also make a video on floating neutral sir

  • @ranjan1436
    @ranjan1436 4 ปีที่แล้ว +1

    what about non-linear inductive loads & harmonics in the system, can we use the neutral wire size half the phase size

    • @GauravJ
      @GauravJ  4 ปีที่แล้ว

      Yes (I think neutral current will not be more than phase current). In worst case, where waveforms are badly distorted, we can use neutral cable same size as other phase wire.

  • @anupsingh5858
    @anupsingh5858 4 ปีที่แล้ว +1

    Mind-blowing sir

  • @dharma.vibrates
    @dharma.vibrates 3 ปีที่แล้ว +1

    Wonderful Sir

  • @multitasker4737
    @multitasker4737 3 ปีที่แล้ว +1

    Great vedio bro.. love ur explanations

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว +1

      Thank you 😊 do share and subscribe to my channel ✌🏻

  • @erwinarief4567
    @erwinarief4567 ปีที่แล้ว +1

    excellent video...

  • @uditkashyap7178
    @uditkashyap7178 2 ปีที่แล้ว

    Thanks for the precious explanation ..
    Also wanted to know if a single phase RCCB connected to a load will trip if the loads in all the 3 phases are balanced (identical).

  • @MSKChess
    @MSKChess 4 ปีที่แล้ว +1

    Thank you bro, super clear.

  • @zwang9607
    @zwang9607 7 หลายเดือนก่อน

    Thanks for sharing. If the neutral wire detected amps value, which is not negligible, can we assume the 3 phase loads are not balanced? Second question, if we found the voltage on each phase is not identical, can we assume there might be a problem with the neutral wire?

  • @esamesam6312
    @esamesam6312 4 ปีที่แล้ว +5

    Dear Sir
    Thank you
    I have question:
    If I conected neutral wire with ground cable and neutral wire cut, is load will continue to work with out any problem?
    Is voltage and current will stay same?
    Regards
    Essam

    • @goaliedude32
      @goaliedude32 3 ปีที่แล้ว

      You should never never never connect a neutral to ground

    • @goaliedude32
      @goaliedude32 3 ปีที่แล้ว

      Do not ever connect neutral to ground. You can very easily kill someone

  • @ananthharitsa3428
    @ananthharitsa3428 2 ปีที่แล้ว

    After watching this video, I wanted to write this.
    First, we understand the CURRENT in a simple way.
    We are having an Over Head Tank at every house, right? From there we are having connections to our bath rooms, kitchen, utility etc. with the pipe line (Plumbing line). Once we open the tap, the water will flow from the Over Head Tank to the tap through the pipe line. We use / consume that water.
    Consider, you are having a Geyser at your house. It consumes current to operate. If we give some current by turning on the switch (Same as Water in the pipe line to the Tap) with required force, (Voltage) the Geyser will draw / Consume the power (As designed). Wires used in this are the Conductors which carry the current same as pipe line which carries water. Here the Power source would be Transformer same as Over Head Tank for water. We can draw the current as much as we required to our electrical gadgets. (But the transformer can not store the current as we store the water in Over Head Tank, Current comes directly from the Generating Station through Transformer)
    Example:
    Geyser Power (P) = 1000 Watts (Consider as Consumption of Water (Quantity) with specified force)
    Current (I) =? (Consider as Water which you are going to consume)
    Voltage (V) = 220 V (Consider as Pressure of Water flowing in the Pipe line)
    Formula: P = V X I
    That is, 1000 = 220 X I
    So Current (I) = 1000/220 = 4.5 Amps (Consider, you consumed 4.5 Litre of water)
    There is No Minus Current as told in this video. (Think about the Water, how will you minus the water?)
    Neutral Current will be zero if all the 3-Phase current is same. (Balanced)
    “All the current meeting at junction is Zero” according to Kirchhoff’s Current Law
    Consider, there are three houses with single phase power supply connection with different phases (R, Y B).
    House R - Consuming 5Amps
    House Y - Consuming 8Amps
    House B - Consuming 10Amps
    Then the Neutral Current would be
    √(R2 + Y2 + B2 - RY - RB - YB)
    √(52 + 82 + 102 - 5X8 - 5X10 - 8X10)
    √(25 + 64 + 100 - 40 - 50 - 80)
    √(189 - 170) = √19 = 4.36 Amps
    So, in this case, the unbalanced 3-Phase load Neutral Current will be 4.36 Amps.
    The Neutral Current would have been zero, if each Phase current would have 5 or 8 or 10Amps
    Neutral current will be high if the load is not equal in 3-Phase circuit. But it will be less when compare to each phase Maximum current. So always we use Half of the Phase Cable size for Neutral in 3-Phase loads, considering the balanced load.

  • @prabhakaranr3594
    @prabhakaranr3594 4 ปีที่แล้ว +1

    Perfect video 👌. simply super

    • @GauravJ
      @GauravJ  4 ปีที่แล้ว

      Thank you so much 🙂

  • @AlulaZagway
    @AlulaZagway ปีที่แล้ว

    Can we connect the equipment ground on devices to neutral instead of sending it to the ground rod?

  • @catchmypoint6756
    @catchmypoint6756 4 ปีที่แล้ว +3

    U r videos are interesting

  • @pubudunuwan1751
    @pubudunuwan1751 3 ปีที่แล้ว +1

    what a great explanation

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว +1

      Thanks 😊 Do share and subscribe to my channel ✌🏻

    • @pubudunuwan1751
      @pubudunuwan1751 3 ปีที่แล้ว +1

      @@GauravJ we are looking for more videos sir,i will share this video with my friends

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      Sure. New videos are coming!!

  • @thekirannalini
    @thekirannalini 3 ปีที่แล้ว +1

    Nice explanation sir.
    One question. Sir.
    Difference between neutral wiring and grounding..

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      Thanks. Do ahare and subscribe 🙏✌🏻 I'll try to make a video on that

  • @wnicora
    @wnicora 7 หลายเดือนก่อน

    Video is cristal clear but could you explain how the risk of unbalanced phases is coped with in distribution networks without neutral ? Like where I live

  • @ghaziibrahim488
    @ghaziibrahim488 7 หลายเดือนก่อน

    The question is in 220 V single phase system if we remove the neutral wire(meaning we only have hot wires) can the current complete the circuit back to the transformer?

  • @chinnakarlapraveen9966
    @chinnakarlapraveen9966 4 ปีที่แล้ว +1

    Nice topic sir 😍

  • @Bishalkarn
    @Bishalkarn 3 ปีที่แล้ว

    If there is current in neutral then why dont we get electric shock at neutral?
    If one says that neutral has 0 potential then what does that actually mean? Aren't we supposed to get phase in neutral too if phase changes in AC current??

  • @nothj
    @nothj 3 ปีที่แล้ว +1

    Thank you sir.

  • @Abhisheksharma-lk4ll
    @Abhisheksharma-lk4ll 4 ปีที่แล้ว +2

    I enjoyed, loved it ❤️💖❤️💖❤️

    • @GauravJ
      @GauravJ  4 ปีที่แล้ว +1

      Glad you enjoyed it

  • @mrsaad1282
    @mrsaad1282 4 ปีที่แล้ว +1

    Could you please make a video about Phase Shift Transformer (the operation principles, usage..)

    • @GauravJ
      @GauravJ  4 ปีที่แล้ว +1

      Sure. I’ll try!

  • @madhanagunasekaran8719
    @madhanagunasekaran8719 2 ปีที่แล้ว

    could you please take a video of controller explanation. with examples like PID,DYNAmic etc

  • @williamtrujillo5411
    @williamtrujillo5411 2 ปีที่แล้ว +1

    ✌🏽thank you …very helpfull

    • @GauravJ
      @GauravJ  2 ปีที่แล้ว

      Do share and subscribe 😊😊

  • @ruan2587
    @ruan2587 4 ปีที่แล้ว +1

    Good video. Suggestion, put three phase systems somewhere in the title, as it is not applicable in single phase systems.

  • @nelsonnelito5895
    @nelsonnelito5895 2 ปีที่แล้ว +1

    Thank you🙏🙏

  • @mohammadsalim5619
    @mohammadsalim5619 4 ปีที่แล้ว +5

    Sir, I have a question. If I connect unbalanced loads in Delta configuration then there is no opportunity for existing neutral wire. Then what is the voltage across the each load?

  • @nenunachelli3494
    @nenunachelli3494 4 ปีที่แล้ว +1

    Please Make a video on Difference between lbs and vcb???

  • @nasirulislam710
    @nasirulislam710 ปีที่แล้ว

    Pls make a video for star-Delta startor control panel for high power motor

  • @tharunetikikota7442
    @tharunetikikota7442 4 ปีที่แล้ว +1

    Sir, where the current in neutral goes to??whether it combine with phase current or not??

    • @tedlahm5740
      @tedlahm5740 4 ปีที่แล้ว +1

      Of course back to the Wye transformer as pictured.

    • @tharunetikikota7442
      @tharunetikikota7442 4 ปีที่แล้ว +1

      Whether it changes total rms or peak value??

  • @kinga-TheSheru
    @kinga-TheSheru 3 ปีที่แล้ว +1

    Nice explain

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      Thanks. Do like and subscribe to my channel !!

  • @yametekudasaisensei539
    @yametekudasaisensei539 3 ปีที่แล้ว

    Nice explain, can you explain how to calculate single phase voltage on a unbalanced wye with floating neutral

  • @iqbalnuthoo1566
    @iqbalnuthoo1566 6 หลายเดือนก่อน

    good explanation

  • @ravivaghela9696
    @ravivaghela9696 4 ปีที่แล้ว +1

    Nice video sir

  • @whenniceguysretaliate5619
    @whenniceguysretaliate5619 3 ปีที่แล้ว

    Awesome video. Thanks.

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว +1

      Welcome 🙏🏻 do share and subscribe to my channel ✌🏻👍🏻

  • @igordekanga8297
    @igordekanga8297 4 ปีที่แล้ว

    Hi
    Again thank you for your technical support.
    Now we want to understand what happens when batteries on telecom site are not fully recharged.

  • @amedeus_tz
    @amedeus_tz 9 หลายเดือนก่อน

    Let me ask a question of removing neutral cable in the system. In case of load are equal in three phase. Can i connect three lamps of the same current, voltage and power?. If i connect it work properly without any damages?. How i connect these connection?.

  • @_stardust__
    @_stardust__ 3 ปีที่แล้ว

    Suppose, we take a mcb, connect 3 phases in its input and short the 3 output terminals and turn ON the mcb. What will happen? Will there be a short circuit or the common point of the mcb output will behave like a neutral point?

  • @jijovarghese1987
    @jijovarghese1987 3 ปีที่แล้ว

    Very well explained. For single phase system neutral wire size should be equal to phase wire. What do you think?

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      Not necessary. It can be less as well. Depends upon the system

    • @jijovarghese1987
      @jijovarghese1987 3 ปีที่แล้ว

      @@GauravJ for example for a house supplied by single phase in that case whatever be the current flowing through the phase is flowing through the neutral wire also. In my house neutral wire gt heated up and burnt due to less wire size compare to phase wire in main switch. There were no loose connection problem or the case of short circuit, its just the neutral wire from main switch is not enough size to carry return current.

  • @unifiedsparks693
    @unifiedsparks693 4 ปีที่แล้ว +2

    Sir I have a doubt typically in India ground and neutral are internally connected and both are earthed
    So some power from source would go to earth rather than return to power source itself
    Also why we use two seperate wires nutral and ground instead of single wire as both are the same

    • @kimballscarr
      @kimballscarr 2 ปีที่แล้ว

      But India has many gurus for guidance on the subject. Actually it is the same everywhere I know of America, England, the civilized world and of course India would be included. Sort of like the Common Law we all share. He has explanation of floating neutrals too, FYI.

  • @sobrepena06
    @sobrepena06 3 ปีที่แล้ว

    Sir but why some designer choosed the neutral to be 2x larger size than the size of line wires.? I was confused on that...

  • @somnil404
    @somnil404 3 ปีที่แล้ว +1

    Thank you sir❤️🙏

    • @GauravJ
      @GauravJ  3 ปีที่แล้ว

      Do share and subscribe 😊

  • @surendrakverma555
    @surendrakverma555 4 ปีที่แล้ว +1

    Very good

  • @romeobaptista1572
    @romeobaptista1572 ปีที่แล้ว

    you can't not take out the transmission lines from Delta/Y or ,480V/377V to Distribution lines Substation to 120/240Vac residential houses Indian guy. You need a
    a step downty 7:53 7:53 7:53 transformer to feed feed

  • @ranjan1436
    @ranjan1436 4 ปีที่แล้ว

    what happens in the short circuit condition if the neutral & phase wire are interchanged.