Troubleshooting A 4-20mA Submersible Level Transducer In the Field With A Fluke 789 Process Meter

แชร์
ฝัง
  • เผยแพร่เมื่อ 28 ก.ย. 2024
  • Step by step in the field troubleshooting of a submersible level transducer with a Fluke 789 process meter. Understanding and troubleshooting 4-20mA signals is one aspect of being a Control Systems Technician.

ความคิดเห็น • 16

  • @smarterthanthou1953
    @smarterthanthou1953 18 วันที่ผ่านมา

    Would definitely love to see more of these videos! very informative

  • @chito3508
    @chito3508 3 หลายเดือนก่อน +1

    Great video! Super informative nice to see real life issues!

  • @ender198
    @ender198 6 หลายเดือนก่อน +3

    Awesome! Very enjoyable.

  • @2PacStoleMyBike
    @2PacStoleMyBike หลายเดือนก่อน +2

    Excellent ! Thanks for the training

  • @williemasonjohnson
    @williemasonjohnson 4 หลายเดือนก่อน

    Awesome, thank you for sharing very informative!

  • @christophersutherland6019
    @christophersutherland6019 6 หลายเดือนก่อน +2

    Very interesting seeing troubleshooting in real time.

  • @barrylougheed8369
    @barrylougheed8369 2 หลายเดือนก่อน +1

    The wiring is busch league, install some Panduit and clean it up so it looks professional.

    • @kenyattafrazier
      @kenyattafrazier หลายเดือนก่อน

      Welcome to the industrial world

  • @1GreatLake
    @1GreatLake 6 หลายเดือนก่อน

    My millwright brain can barely process this but very interesting!

  • @genecoppedge5972
    @genecoppedge5972 4 หลายเดือนก่อน

    Will the 789 meter generate 12 volts on a 12 volt system, such as a vehicle or only good for the 24 volt systems?

    • @Up-CountryElectric
      @Up-CountryElectric  4 หลายเดือนก่อน

      It's built in power supply is only for sourcing 24vdc loop power for 0-24ma current circuits. It can also sink using an external power supply.

    • @Up-CountryElectric
      @Up-CountryElectric  4 หลายเดือนก่อน

      It's built in power supply is only for sourcing 24vdc loop power for 0-24ma current circuits. It can also sink using an external power supply.

  • @soundfrequency-2520
    @soundfrequency-2520 2 หลายเดือนก่อน +1

    Hay, Can I ask you something? How does the radio guy know the PLC raw value is from 6500 to 32k for that level sensor range? If we don't know, could we just give the 4-20mA from 789 and find out the min & max raw data range for that level sensor? Or Have to find that PLC manual for analog card raw data? Or is there another way?

    • @Up-CountryElectric
      @Up-CountryElectric  2 หลายเดือนก่อน +2

      That's the standard range for an analog input converted to a signed 16-bit integer. Some PLCs and equipment use different values, but the PLCs we use all utilize a signed 16-bit integer with a range of 0-32k.

  • @tommymyers3183
    @tommymyers3183 2 หลายเดือนก่อน +1

    Where can I get those very useful equations like the one you used 15 ÷ 2.31 ) like is there any books or anything like that?

    • @Up-CountryElectric
      @Up-CountryElectric  2 หลายเดือนก่อน +1

      That equation is "feet of head (elevation) to PSI"
      Google.com and TH-cam videos 😜