HVAC Service Call: LG Multi V 5 Compressor/Inverter PCB Installation (LG Error Code CH26/CH29)

แชร์
ฝัง
  • เผยแพร่เมื่อ 10 มี.ค. 2023
  • HVAC Service Call: LG MULTI V IV Not Cooling/Heating (LG Multi V 5 Error Code CH26/Error Code 261) LG Error Code CH21 / LG Error Code 211 / LG Error Code CH26 / LG Error Code 261 / LG Error Code CH29 / LG Error Code 291 / LG HVAC Training / LG HVAC Troubleshooting / LG VRV / LG VRF / LG Heat Recovery Heat Pump / LG Heat Pump / HVAC Service Call: LG MULTI V IV Compressor & Inverter Board Replacement (LG MULTI V 5 Repair) HVAC(Heating, Ventilation, Air Conditioning) Service Call: LG Multi V IV Error Code CH29 (Inverter Compressor Over Current) Error Code 291 / LG MULTI V 5 ERROR CODE CH29 - Outdoor Unit Inverter Compressor Over Current ( Outdoor Unit Inverter Compressor Fault Or Drive Fault) LG Troubleshooting / HVAC VRF VRV Training #HVAC #LG #HEATPUMP #JUMPERMANTECH
    Veto Pro Pac TECH MC
    amzn.to/3gURJyZ
    Fluke 902 FC HVAC True-RMS Clamp Meter
    amzn.to/39wvwiK​​
    Fieldpiece ADK7 Deluxe Silicone Test Lead Kit
    amzn.to/3VNYXDv
    Fluke 1AC-A1-II VoltAlert Non-Contact Voltage Tester
    amzn.to/3FcWElQ
    Fieldpiece JL3KR4 HVACR Charge Kit (Digital Gauges/Probes)
    amzn.to/3E4W0Fr
    Fieldpiece SPK2 Folding Pocket In-Duct Thermometer
    amzn.to/3mi8Fih
    Fieldpiece SPK3 Folding ROD Dual Temperature Thermometer
    amzn.to/3FbDufQ
    Milwaukee M12 2-Tool Combo Kit 2598-22
    amzn.to/3CtCRNC
    Milwaukee Cut 1 Dipped GLOVES L
    amzn.to/3s8H18O​
    Milwaukee 2351-20 M12 LED Stick Light
    amzn.to/3rVJKEK
    Milwaukee 48-22-1985 Fastback Hawk Bill Folding Knife
    amzn.to/3e53ygW
    Milwaukee 48-22-1500 Fastback Compact Folding Utility Knife
    amzn.to/3qazJkC
    Milwaukee 48-22-4041 Iron Carbide Core Large-Looped Jobsite Scissors
    amzn.to/32fxC6I
    Milwaukee 4932459097 Billet Torpedo Level
    amzn.to/30Dh6Nw
    Milwaukee Wide Blade Magnetic Tape Measure 16 FT
    amzn.to/3yEN7kL
    Milwaukee Fine Pt. Markers Black
    amzn.to/3e4fH5W
    Streamlight 66604 MicroStream USB 250-Lumen Rechargable Pocket Flashlight
    amzn.to/320XiEF
    Klein Tools 11-in-1 Screwdriver / Nut Driver
    amzn.to/3s3o8ql
    Klein Tools 32561 Multi-Bit Screwdriver / Nut Driver 6-in-1
    amzn.to/3e4ur4x
    Klein Tools 32807MAG 7-in-1 Nut Driver, Magnetic Driver
    amzn.to/321n4bW
    Klein Tools 600-4 1/4-Inch Keystone Cushion-Grip Screwdriver
    amzn.to/3J11hS1
    Klein Tools 32581 4-in-1 Electronics Screwdriver Set
    amzn.to/3yEj3WC
    Klein Tools LLK12 L-Style Hex Key Caddy Set 12-Piece (Metric/Sae)
    amzn.to/3yRUiGJ
    Yellow Jacket 18975 Charge Tool
    amzn.to/3J4pfvJ
    Yellow Jacket 60613 Service ratchet Wrench
    amzn.to/3E8iYeZ
    Yellow Jacket 19173 5/16" Female Quick Couplers x 1/4" Male Flare
    amzn.to/3q0TQ4M
    Gerber Gear 30-000469N Dime Mini Multitool Keychain
    amzn.to/32ekMG6
    LEATHERMAN Style PS Keychain Multitool
    amzn.to/3sdGdSB
    SOG Flint Survival & Defense Tool Safety Whistle, Fire Starter, Glass Breaker (FT1001)
    amzn.to/3mhy63p
    3 Pieces Telescoping Inspection Mirror
    amzn.to/3e6tubS
    Cooper Bussmann BP-FP-2 Cartridge Carded Fuse Puller
    amzn.to/3e0USrY
    Crescent 2 Pc. X6 4-in-1 Black Oxide Spline Ratcheting SAE Wrench Set
    amzn.to/3qqKlw7
    Crescent 4" Adjustable Cushion Grip Wrench
    amzn.to/3J4qsmL
    Knipex 09 08 240 SBA 9.5-Inch Insulated Ultra-High Leverage Lineman's Pliers (1000v)
    amzn.to/30EQmw5
    Knipex 09 11 240 9.5-Inch Ultra-High Leverage Lineman's Pliers with Fish Tape Puller and Crimper
    amzn.to/3H9iYAu
    KNIPEX Tools - Long Nose Pliers With Cutter, 1000V Insulated
    amzn.to/3e3IEi7
    KNIPEX Tools - Long Nose Pliers With Cutter
    amzn.to/3gUSE2i
    KNIPEX Tools 98 62 02, Flat Nose Plastic Pliers 1000V Insulated
    amzn.to/3p6lFsZ
    KNIPEX - 74 08 200 - High Leverage Diagonal Cutters, 1000V Insulated
    amzn.to/3mh8K5U
    KNIPEX - 74 01 200 Tools - High Leverage Diagonal Cutters
    amzn.to/3F1VScb
    KNIPEX Tools - Cobra QuickSet Pump Pliers, 1000V Insulated
    amzn.to/3sftr5Q
    KNIPEX Tools 3 Piece Cobra Pliers Set
    amzn.to/3FbRwy7
    KNIPEX Tools Pliers Wrench 3-Piece Set
    amzn.to/3nnRLfW
    Empire Level 2783 Brass Pocket Caliper
    amzn.to/3FcqCGp
    Diversitech GG-1 Drain Gun for A/C Condensate Lines
    amzn.to/32cuYib
    Diversitech Corp 16G CO2 Drain Gun Cartridges GGC-12
    amzn.to/3J0O8IP
    CPS Solenoid Valve Magnet Tool TLMKC18
    amzn.to/3E6rX07
  • วิทยาศาสตร์และเทคโนโลยี

ความคิดเห็น • 75

  • @Garyganeu
    @Garyganeu ปีที่แล้ว

    Reminds me of hauling all the crap up two floors to the top of the building of the hospital I worked in. Changing 20 hp fan motors what a job.

  • @kamechanicalhvac2891
    @kamechanicalhvac2891 ปีที่แล้ว +1

    Great video, brother. Just a few pointers since ( I've never used Teflon on Refrigeration equipment. Eventually, it was leak out of the Teflon tape will dry out and leak the oil . I normally use (loctite thread sealant (554) or nylog Refrigeration gasket thread sealant. Either one works great . Also, before re-installing the compressor threw in some Scavenger Acids neutralizer works great helps with the burn out . Also, next time, order some refrigeration isolation valve to place across the drier to isolate the drier, swapping them out after a week of running the system We normally start with an high acid removal core drier . We normally start with the (RC-4864-HH) core , and after a week, we go back and put in the regular standard core drier RC-4864 but in those type of system we also put in bypass valve to bypass the drier with verifying the oil is good . I definitely understand the headache you go threw working in NYC building

  • @zorinho20
    @zorinho20 ปีที่แล้ว

    You sound pretty young,but seems like a real pro in your trade.

  • @aquaticspecialities5382
    @aquaticspecialities5382 ปีที่แล้ว +6

    These are my favorite units to watch you work on. They’re pretty advanced.. good stuff my guy

    • @JumpermanTech
      @JumpermanTech  ปีที่แล้ว +1

      Awesome. Glad you're enjoying the content. They are definitely very advanced & difficult to work on. This is a heat recovery heat pump so you can have heating and cooling at the same time. Thank you! Stay tuned for new videos every week🔧⚡️

  • @jayaircon
    @jayaircon ปีที่แล้ว +4

    Nice job. To save on recovery, what we do is shut the valves to the system so we are only recovering from the outdoor unit. Then we put the refrigerant back after changing the compressor.

    • @SteadyX-go4wc
      @SteadyX-go4wc ปีที่แล้ว

      That’s no good

    • @jayaircon
      @jayaircon ปีที่แล้ว

      @@SteadyX-go4wc why??

    • @Hamasisfilthytrash
      @Hamasisfilthytrash ปีที่แล้ว

      @@SteadyX-go4wc show me where lg says that ! They have videos on here explaining to close those valves

  • @thesilentonevictor
    @thesilentonevictor ปีที่แล้ว +2

    You made a mess with suction drier lol 😂 great work jmt

    • @JumpermanTech
      @JumpermanTech  ปีที่แล้ว +2

      I made a mess and cleaned it up. Now it's better than ever 😬🤣 That thing was so rusted. It was time to go anyways🔧

  • @50CaI
    @50CaI ปีที่แล้ว

    Nice work. Instead of turning the unit on to weigh in the rest of the refrigerant into the liquid side, now I just heat up the jug of refrigerant while the unit is still off so I know I’m not damaging the compressor. Then I let it sit for about 10 minutes then I turn it on. It flows pretty good with a good heat gun on it

  • @svdleer
    @svdleer ปีที่แล้ว

    2:30 you don't have to go to the gym this way :) keep up the good work! thanks for the video.

  • @samuelsteffan6987
    @samuelsteffan6987 ปีที่แล้ว +1

    Also, when charging, get yourself a hairdryer. Keep the refrigerant in the box, put the drier in the hole, where you connect your hose. You'll get the complete charge without out force operating the machine. Makes it much easier and faster to get total charge.

  • @navystorm8323
    @navystorm8323 ปีที่แล้ว +2

    You are my hero straight up hardcore!! I'm new to the business however you inspire me work harder! keep up the good work God bless

    • @JumpermanTech
      @JumpermanTech  ปีที่แล้ว

      Haha thank you! Much appreciated 🙏 Keep working and showing up💯 God bless you too. Stay tuned for new videos every week🔧⚡️

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC ปีที่แล้ว +2

    Makes me enjoy the weather here in TX.....been in the 80's for 2 weeks in a row. I used to live in WNY......yall NE cats can keep that cold weather.

    • @JumpermanTech
      @JumpermanTech  ปีที่แล้ว +2

      I definitely don't enjoy working in the cold. The weather for this job was good. We were in the mid 40s.The first compressor replacement was 29 degrees. Now that wasn't fun at all. I need to go to the West coast for sure 🤣🤣🤣

  • @nicolerennie
    @nicolerennie ปีที่แล้ว +1

    phew hard job, even before the job begins (climbing the maze). great video JMT⭐️

    • @JumpermanTech
      @JumpermanTech  ปีที่แล้ว

      Definitely. Just getting up there is a workout. Thank you & thanks for watching! Stay tuned for new videos every week🔧⚡️

  • @samuelsteffan6987
    @samuelsteffan6987 ปีที่แล้ว +1

    We use biflow and canned driers. It just depends on the customers. Most definitely on the burnouts. We are always testing oil samples for acid.

  • @christopher20008
    @christopher20008 ปีที่แล้ว +1

    Good job, always enjoy your videos.Very informative.

    • @JumpermanTech
      @JumpermanTech  ปีที่แล้ว

      Thank you! I'm glad you're enjoying the content & find the videos informative. Stay tuned for new videos every week🔧⚡️

  • @jraposala
    @jraposala ปีที่แล้ว

    have some questions with the nitrogen leak test. do you need to bring power back to the unit so that all EEV'S and solenoid open up? not too sure about eev's
    but solenoid they close when power is taken out.
    thanks.

  • @bohanger6315
    @bohanger6315 ปีที่แล้ว +1

    Just thought I'd mention that the 14# written on the electrical case assembly is most likely the trim charge for the system and its associated IDUS/ pipework. You have to add that trim charge to the factory charge listed on the ODU to properly reach the calculated total system charge. This is all based on the design software "LATS". I would strive to remove that suction drier as soon as a oil sample passes, replace the cleanup cores until you achieve that goal and remove it. Vertical upflow/horizontal suction driers are bad in any application. The impact to suction line pressure drop and oil trapping will cause further issues.
    You are my hero for hauling your van to that roof 😂

  • @rodgraff1782
    @rodgraff1782 ปีที่แล้ว +1

    Did you determine why you are loosing compressors on this job? I was told that the compressors rarely fail on VRF units. I imagine it would be a nightmare to have a running burn on one of those systems. I’ve done those changeable core driers, that had five cores, for large systems. Do you test for acid, and change the drier cores until it’s clean? Looks like this wasn’t the first change out. Must be a good reason for repeat failures. I would dump the oil out of the old compressor and see if you have an oil return problem. That suction line drier looks like it was a major oil trap.

  • @johnwalker890
    @johnwalker890 ปีที่แล้ว +1

    Great job Jumper.

    • @JumpermanTech
      @JumpermanTech  ปีที่แล้ว

      Thank you John! Much appreciated 🙏🔧⚡️

  • @zekenzy6486
    @zekenzy6486 ปีที่แล้ว +1

    Great Video, Great Job, Nice work. Thank you for sharing . HVAC in NY is nightmare ^_^. NO ELEVATOR ^_^

    • @JumpermanTech
      @JumpermanTech  ปีที่แล้ว

      You're very welcome & thank you! Haha some locations are really terrible. Space is such a luxury out here. There is an elevator to the 8th floor but then we need to go up those staircases 😵‍💫 Thanks for watching! Stay tuned for new videos every week🔧⚡️

  • @fredricfrancisco7134
    @fredricfrancisco7134 ปีที่แล้ว

    And nice clear 4k video! well done!

  • @SteadyX-go4wc
    @SteadyX-go4wc ปีที่แล้ว

    Few tips:
    -Look into buying an apion kit. Allows you to pull the cores which makes the whole vacuum/recovery process much faster
    -Eliminate your manifold while using the valves. Place one valve on the liquid and another on the suction line
    -When pulling vacuum attach the micron gauge on side port of the apion valve then close the apion valves when performing micron rise test
    -Use a heat gun wile adding refrigerant then start the system afterwards
    -After you pull out the old compressor you should always drill into it and collect all the oil and complete a acid test kit. If its acidic, its always recommended to flush the entire system

    • @AdrianButler86
      @AdrianButler86 ปีที่แล้ว

      Very good observations. I heard similar practices from AC service tech regarding the oil in the old compressor. It gives u a reference of how much oil to put back in the new compressor and if u can even use the old oil no acid shows up on acid test. If acid shows up then the lines should be blown out with nitrogen prior to install n starting new compressor

  • @aldoo7972
    @aldoo7972 ปีที่แล้ว +1

    Awesome job!

    • @JumpermanTech
      @JumpermanTech  ปีที่แล้ว

      Thank you! Stay tuned for new videos every week🔧⚡️

  • @davefeely2101
    @davefeely2101 ปีที่แล้ว

    Great content , love your work. Not trying to be negative but just wondering why you don’t sand the pipe before cutting it to try and keep possible debris from entering the pipe later. Keep up the great work Jumper man.

  • @EkremOncirak
    @EkremOncirak ปีที่แล้ว +2

    i learned something yesterday, check your indoor units for oil traps at the suction line, if they dont your compressor wil run out on oil.

    • @JumpermanTech
      @JumpermanTech  ปีที่แล้ว

      So each indoor unit should have its own oil trap? Each 1 outdoor unit up here is connected to 8 or 9 indoor units.

    • @bohanger6315
      @bohanger6315 ปีที่แล้ว

      LG is very clear about unnecessary traps, you cant have them. If you are accumulating oil in a IDU coil its probably an air flow issue or lack of refrigerant velocity through the coil to return the oil . The oil sensor on the compressor should initiate a forced oil return where the system goes into heating and blasts hot gas through to achieve this, if it doesn't it will alarm off after a fixed number of attempts.

  • @douro20
    @douro20 ปีที่แล้ว

    I wonder how many of the lines on that compressor are for oil cooling?

  • @TheMuleAHI
    @TheMuleAHI ปีที่แล้ว

    I like to cut under the braze joint not above, also try using a cable cutter instead of the pipe cutter way easier.

  • @johnloydandasan34
    @johnloydandasan34 10 หลายเดือนก่อน

    Shoutout bro. From Hi - M solutek Abu Dhabi

  • @perguntasdojhonyHvac
    @perguntasdojhonyHvac 2 หลายเดือนก่อน

    otimo trabalho , parabéns

  • @HVAC544
    @HVAC544 ปีที่แล้ว +1

    Nice repairs, HVAC in NY looks crazy having to bring all that up the stairs even the locations of some of the units. Interesting there's a suction dryer on that unit did they have an acid burn out before?

    • @AdrianButler86
      @AdrianButler86 ปีที่แล้ว

      It's prolly been put in during install for future purposes of a compressor change out

  • @mcotech1573
    @mcotech1573 ปีที่แล้ว

    Hi how much pressure you need at the nitrogen regulator, thanks

  • @thesilentonevictor
    @thesilentonevictor ปีที่แล้ว +3

    Man this should pay you for lack of proper access hmmm good job the boss 😂

    • @JumpermanTech
      @JumpermanTech  ปีที่แล้ว +2

      It's like going to the gym but you're at work instead 😂 There should be an extra fee for this😅💰🔧⚡️ Thanks for watching!

  • @amoni1959
    @amoni1959 ปีที่แล้ว

    How do u like being a HVAC tech in NYC?

  • @danielmahoney4266
    @danielmahoney4266 ปีที่แล้ว

    U can buy new bolts for those canisters at hardware store we do it all the time

  • @retrofitter
    @retrofitter ปีที่แล้ว

    You could probably sell a service replacing all the thermal grease with some kind of thermal pad that doesn't dry up or suffer from pump out

  • @shine-cg9uf
    @shine-cg9uf ปีที่แล้ว +2

    💪👍❄️🇺🇸 wow what a job. 💪💪💪💪

    • @JumpermanTech
      @JumpermanTech  ปีที่แล้ว

      It was a serious job for sure. These units are something else. Thanks for watching & stay tuned for new videos every week🔧⚡️🇺🇲🙏👍

  • @williamguillensoto4763
    @williamguillensoto4763 3 หลายเดือนก่อน

    Hello, im from mexico, how do you autoload?

  • @frankspliff7037
    @frankspliff7037 ปีที่แล้ว +1

    Did you get board or maintenance people

    • @JumpermanTech
      @JumpermanTech  ปีที่แล้ว

      The building provided the parts as they keep some stock there due to these units failing so often. Thanks for watching & stay tuned for new videos every week🔧⚡️

  • @prowesstv
    @prowesstv ปีที่แล้ว +1

    Finally some sun 🌞

    • @JumpermanTech
      @JumpermanTech  ปีที่แล้ว +1

      Definitely better weather this time. Thankfully winter will be over soon! Thanks for watching & stay tuned for new videos every week🔧⚡️

    • @prowesstv
      @prowesstv ปีที่แล้ว +1

      @@JumpermanTech keep them coming i love the vrf content

    • @JumpermanTech
      @JumpermanTech  ปีที่แล้ว

      @@prowesstv Glad you're enjoying the content. Looks like we will be busy here with LG!

  • @67tr876
    @67tr876 ปีที่แล้ว +3

    This is you're new spot huh ? Haba

    • @JumpermanTech
      @JumpermanTech  ปีที่แล้ว +3

      Haha new spot for sure and they like the service so far 👍👌 A 3rd unit went down but it's not a compressor related issue thankfully. 3 in 3 weeks! Thanks for watching🔧⚡️

    • @JumpermanTech
      @JumpermanTech  ปีที่แล้ว +3

      Domino effect 🤯

    • @svdleer
      @svdleer ปีที่แล้ว +1

      @@JumpermanTech Sounds like the rest of the units come next :)

    • @JumpermanTech
      @JumpermanTech  ปีที่แล้ว +1

      @@svdleer We just lost another one today! This is getting crazy!

    • @svdleer
      @svdleer ปีที่แล้ว

      @@JumpermanTech sounds like limit of run hours is reached : fail now

  • @abdullah_q8171
    @abdullah_q8171 ปีที่แล้ว +1

    Very hard to work with vrf

    • @JumpermanTech
      @JumpermanTech  ปีที่แล้ว +1

      Definitely. Thanks for watching & stay tuned for new videos every week🔧⚡️

  • @craighvac1808
    @craighvac1808 ปีที่แล้ว

    You will be working on these units several times per month, LG makes absolute junk. Inverter boards go all the time, you have a lot of units to deal with

  • @nadeembukhari7973
    @nadeembukhari7973 ปีที่แล้ว +2

    Excellent, thanks for sharing.

    • @JumpermanTech
      @JumpermanTech  ปีที่แล้ว

      Thank you & thanks for watching! Stay tuned for new videos every week🔧⚡️

  • @szachty1
    @szachty1 10 หลายเดือนก่อน

    if you loosing compressors on lg mv most likely your piping is downsize , check your header sizes twining the condensers .. good luck LG is piece of shit , I did tons of vrf system in NYc

  • @nadeembukhari7973
    @nadeembukhari7973 ปีที่แล้ว +2

    Suggestion. Use hand pull out tool to take out the heavy compressor.