Ilang Ilaw Sa Isang Switch At Ilang Appliances Sa Isang Convenience Outlet

แชร์
ฝัง
  • เผยแพร่เมื่อ 14 ต.ค. 2019
  • Sa video na ito ituturo ko sa inyo pano magcompute ng maximum load ng mga Electrical devices
    Welcome to Jun Aux TV if you enjoy watching this video don't forget to subscribe, like and hit notification bell thank you!
    Also visit my FB pages and group:
    JB Handyman Services
    ✓If you’re looking for the right person to fix the problem your facing in your home you can find it here, License Electrical Practitioner is available here, visit us
    Jun Aux TV
    ✓all about Electrical installation and Electrical devices reviews and safety awareness on Electrical
    JB Online Shop
    ✓you can buy product such as Electrical devices mostly on industrial devices
    www.facebook.c...
    Electrician For Hire
    ✓group of Electrician looking for a job and giving and taking ideas in one another
    JBLyricsVideo
    ✓its all about lyric video on popular music now a days
    Thanks for Watching hope you enjoy. God bless

ความคิดเห็น • 495

  • @lemueloliveros9690
    @lemueloliveros9690 4 ปีที่แล้ว +1

    Salamat sir malaking tulong ang mga vlog mo sa mga gaya kung walang alam sa electrical.

  • @galawangelectrical
    @galawangelectrical 4 ปีที่แล้ว +1

    salamat sa information lods, kelangan talaga alam yan lalo na ng mga electrician.
    pero my times kaya nasusunog ang isang outlet is loose, lalo na kung malaki ang load.
    malaki pero pasok naman sya sa allowable amps nya.

  • @kgpcodes
    @kgpcodes 4 ปีที่แล้ว +1

    Salamat. Nag-aaral ako ng load computation.
    Marami akong binili na Sonoff Pow R2. Nakakatulong talaga sa pag-estimate ng power consumption.

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      May special devices po ba kayo mam na ginamit?

    • @kgpcodes
      @kgpcodes 4 ปีที่แล้ว

      Jun Aux TV kelangan ko lang ng automation kaya gamit ko Sonoff. Example: water pump, fan, etc. May sensors din ako. Gamit ko HASS. Check mo Home Assistant.

    • @kgpcodes
      @kgpcodes 4 ปีที่แล้ว

      Jun Aux TV hindi naman sobrang special pero example yung pump eh mas OK kung may switch sa phone lang or isang smart switch sa banyo na pwedeng control yun. Ang mga Sonoff Pow actually eh pwede lang sa low wattage.

  • @julitocm964
    @julitocm964 4 ปีที่แล้ว +2

    Maraming salamat Sir , OK po ung demo nyo napakaganda at may natutunan talaga ako, sanapo meon pa kaung ibang mai video.

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Madame pa sir...hehe

  • @DonaldDuct503
    @DonaldDuct503 4 ปีที่แล้ว +3

    andami ko talaga nalalaman sa channel na toh thanks lodi 😉

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Salamat din po sir

  • @djphaxspider
    @djphaxspider 3 ปีที่แล้ว +1

    Electrician din po ako regstrd..pro pinapanood Kita lage..keep the good work..godbless

    • @junauxtv
      @junauxtv  3 ปีที่แล้ว

      Maraming salamat din po sir...

  • @emmanjasper9329
    @emmanjasper9329 3 ปีที่แล้ว

    ayos galing sir ganito mga videos dapat ang sinusuportahan lalo sa mga skilled worker ofw para hindi tayo mapag iwanan nang mga ibang lahi abroad..

  • @arleeterunez5545
    @arleeterunez5545 3 ปีที่แล้ว +1

    Good thanks galing may natutunan ako.

  • @rowlanddepot8885
    @rowlanddepot8885 4 ปีที่แล้ว +2

    sir thanks s yong video nkaka pulot idea god bless di k madamot sir

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Salamat din po sir

  • @kuyaemantv
    @kuyaemantv 4 ปีที่แล้ว +1

    Slamat boos electrician Hindi q rin po alam Salamat info may idea naq thanks

  • @hurtlocker717
    @hurtlocker717 4 ปีที่แล้ว

    Sir salamat ..may alam na ako sa video mo salamat sa guide at kaalaman mo sir...electrician po ako dito sa davao...amping always..

  • @ramilmejos3871
    @ramilmejos3871 4 ปีที่แล้ว +1

    Thank you Sir Jun😊 mayron na Naman kaming natutunan po sayo.

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Maraming salamat din po sir

  • @dexterlawa3065
    @dexterlawa3065 4 ปีที่แล้ว +1

    God bless you Jun. patuloy molang yang kabutihang ginagawa mo

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Maraming salamat po sir...God bless us all

  • @zayonastv2260
    @zayonastv2260 4 ปีที่แล้ว +13

    pls always set ur mind in standard set by PEC-Philippine Electrical Code, para safe. in doing some electricity stuff..

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Tnx for reminding us sir...tnx

    • @christophertagura9215
      @christophertagura9215 4 ปีที่แล้ว

      Tama ko po diyan sir

    • @riztuvpabondal2411
      @riztuvpabondal2411 4 ปีที่แล้ว

      @@reggie7725 I agree also with mr diy. I doubt also if meralco or napocor used GFCIs, ELCBs in their buildings/offices which are electrical safety device. During my vacation in Philippines, I've noticed they have now R-Y-B code on 13.8KV overhead feeder lines. Meralco required 10-12 awg solid earth or ground conductor/white insulation, together with 2 hot line stranded conductor with 8 awg with extra length for drip loop from weathercap and termination for meterbase for a 40 amps residential load.

    • @riztuvpabondal2411
      @riztuvpabondal2411 4 ปีที่แล้ว

      @@reggie7725 whatever company it is, as long as their design is in accordance with its national not international standards or requirements it can be. I've been working in certain projects HOLCIM, NATIONAL STEEL CORPORATION/GLOBAL STEEL more than decade and haven't seen in their installations. Perhaps they have now if they upgraded to IEC.

  • @gelbyahero8539
    @gelbyahero8539 4 ปีที่แล้ว

    Salamat sa video mo sir, nadagdagan yong aking kaalaman,
    Tanong ko nga pla anong purpose ng breaker, at kung paano ito mag automatic shutdown?

  • @jomarcarino2824
    @jomarcarino2824 4 ปีที่แล้ว +1

    salamat po sa mga video n ipipalabas po nyo nakktulong po samin yang mga pinapalabas po nyo

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      maraming salamat din po

  • @jovitodelamata2228
    @jovitodelamata2228 3 ปีที่แล้ว

    Thanks sa info sir. It was a clear presentation for a safety lightings.

  • @unicornsblog8092
    @unicornsblog8092 4 ปีที่แล้ว +1

    maraming salamat sir,dami ko pong natutunan sa inyo

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว +1

      Maraming salamat din po

  • @villasisargie3048
    @villasisargie3048 3 ปีที่แล้ว

    Salamat sayo idol sa genawa mong vedio my natotonan na nman amo

  • @joseprotacio5654
    @joseprotacio5654 4 ปีที่แล้ว +6

    if you do not understand consult the Phil. Electrical Code that is the only authority regarding electrical regulations

  • @lheoturtona5212
    @lheoturtona5212 4 ปีที่แล้ว +1

    salamat sir at pinagbigyan mo yung request ko salamat ng marami may natutunan nanaman ako salamat

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Salamat din po sir...

  • @opecons
    @opecons 5 หลายเดือนก่อน

    Ang 80% doon mo lang iapply sa breaker kasi yun ang nagtrip. Sa switches , at outlet rating hindi mo na kilangan applyan ng 80% basta hindi lalampas sa rating. Ex. 10A ang rating switch pwede mo lagyan ng 9.5A

  • @angelopaluyo
    @angelopaluyo 4 ปีที่แล้ว

    SALAMAT SIR SA LAHAT NG TUTORIAL MO.

  • @rolandcabales4624
    @rolandcabales4624 4 ปีที่แล้ว +1

    Sir Jun..thank u po.lagi ko pinapanood video mo..

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      maraming salamat po sir

    • @rolandcabales4624
      @rolandcabales4624 4 ปีที่แล้ว

      Sir jun.pwd po ba gawa kau Ng control Ng submersible pump na may kasamang float switch..thank u po sir jun

  • @bertapartv
    @bertapartv 3 ปีที่แล้ว

    Salamat sa mga kaalaman boss

  • @secret-jj2ji
    @secret-jj2ji 4 ปีที่แล้ว

    Tnx sa malupet mong lecture... ❤❤❤❤❤❤❤

  • @peemaktorralba1237
    @peemaktorralba1237 3 ปีที่แล้ว

    Galing Master,my nalaman ako sau, Salamat 👍👍

  • @jhunreyamorganda2200
    @jhunreyamorganda2200 4 ปีที่แล้ว +1

    Sir another learning nanamn thanks to your master

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Maraming salamat din po sir

  • @jerryqatarboy9156
    @jerryqatarboy9156 4 ปีที่แล้ว +4

    sir, ang pinaka safe sa isang swith wla po yan sa watage kase sobrang dami ang pede mo ikabit
    kng watage ang pgbabasihan, mahirap n yan e troubleshoot mdamay ang ibang ilaw kpag mg off ka ng breaker
    sa cercuit po tyo mg base
    10 to 12 lumps or bulb lng po ang pede ntin ikabit sa isang cercuit
    slmat

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Sir ilang amps OCPD mo sa 10 to 12 bulb sa isang circuit?

    • @mjlesly5702
      @mjlesly5702 4 ปีที่แล้ว

      tama ka sir. sa work ko. LED 15watts / 11pcs tapos breaker 15amps..

    • @victorianoarandid6234
      @victorianoarandid6234 4 ปีที่แล้ว +5

      Kung yang 10-12 bulb na sabi mo ang basihan para di masunog ang switch na 16amp ang capacity,ang wattage ng bulb mo ay 500? =6,000watts/230v=26amps,sunog ang switch mo na 16amps lang ang capacity.kaya dapat alam mo ang wattage hindi sa dami ng bulb.

    • @yhongromano8522
      @yhongromano8522 3 ปีที่แล้ว

      @@victorianoarandid6234 saan ka ba makakakita ng ilaw na 500w sa residential? ibig nya sabihin capacity ng CB

  • @angel050370
    @angel050370 3 ปีที่แล้ว +1

    Di na kailangan kwentahin pa yan kasi alam mo na ang capacity ng switch Ng i follow nyo ang PEC standard .kHit kayanin pa nya mataas na ampere ang pagbabasehan pa rin ang standard dahil iyon amg pina ka safe

  • @reynantecha9955
    @reynantecha9955 4 ปีที่แล้ว

    Salamat SA impormasyon kuya.. godbless po

  • @salemstvmixedvlogs
    @salemstvmixedvlogs 4 ปีที่แล้ว

    Maraming buzzer pero ako namumulot ako ng good idea para magamit ko rin in future

  • @roimandolado3656
    @roimandolado3656 4 ปีที่แล้ว +1

    God bless po gumaling ang pamamalat

  • @danza9914
    @danza9914 4 ปีที่แล้ว +2

    Sa Octopus po sir kaya nya po na reach yung maximum aphere rating nya dahil pag octopus po yung connection magkakaroon po sya voltage drop. Pag bumamaba ung voltage tataas ung current nag vavary po kasi ung voltage tsaka current kaya po na reach nya or nag exceed sya sa 8amps na rating kaya nasusunog sya 😊

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว +1

      Tama po kayo sir....

    • @jeromeb.6991
      @jeromeb.6991 4 ปีที่แล้ว +1

      pag bumaba ang voltage tataas ang current ? 🤔

  • @derickespinosa3643
    @derickespinosa3643 4 ปีที่แล้ว

    ayos boss,may natutunan nmn ako salamat po.

  • @leoawag578
    @leoawag578 4 ปีที่แล้ว +1

    Maraming pong salamat Jun sa clkear mong explaination.

  • @SirCapeTV1959
    @SirCapeTV1959 3 ปีที่แล้ว

    Thanks for sharing, new subscriber

  • @altvshow2281
    @altvshow2281 4 ปีที่แล้ว

    Good day. Boss mahilig ako mag DIY. Very informative mga toturial videos mo. May question sana ako, pwede ba ako maglinya ng 3gang switch with 3 convince outlet na naka top lang sa isang light switch?

  • @ramoncabayaojr.6528
    @ramoncabayaojr.6528 2 ปีที่แล้ว

    Boss good thanks galing mo

  • @yhongbuenaobra2721
    @yhongbuenaobra2721 4 ปีที่แล้ว +1

    galing mo master ..tuloy mo LNG yn sir

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Maraming salamat po sir...

  • @myteknik5051
    @myteknik5051 4 ปีที่แล้ว +2

    Ang galing u idol..

  • @juliusbornilla6504
    @juliusbornilla6504 3 ปีที่แล้ว

    More vedios pa master godbless.

  • @Project-xt9ki
    @Project-xt9ki 4 ปีที่แล้ว

    Thanks sa impormasyon ngayon ko lang di na laman. God bless

  • @blackycute123
    @blackycute123 4 ปีที่แล้ว

    Thanks sir sa pag explain kung bakit Max 10 c.o lang per circuit gagamitin :D

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Salamat din po sir

  • @cocoelgaming9812
    @cocoelgaming9812 4 ปีที่แล้ว

    May natutunan ako dahil.
    EIM AKO.......more videos to come

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Salamat sir

  • @b2bgarment878
    @b2bgarment878 4 ปีที่แล้ว +2

    God bless jun .sana mgpatoloy kp gumawa ng tutorial vedio marami . My tanong lng ako regarding circuit breaker .for example un outdoor breaker k is 30 amper..kailangan b un main breaker k s indoor ay 30 dn

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว +2

      Yes sir...same amps po dapat

  • @gideontuason5941
    @gideontuason5941 3 ปีที่แล้ว

    Salamat idol sa pag reply sakin nun nakraan..

  • @georgearpas9904
    @georgearpas9904 4 ปีที่แล้ว +1

    Ok master my natutunan

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Salamat sir

  • @alejandroreyes3784
    @alejandroreyes3784 3 ปีที่แล้ว

    tnx po sa information

  • @felmorm.2562
    @felmorm.2562 4 ปีที่แล้ว +1

    thanks sa info idol 👍👍

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว +1

      Salamat din po sir

  • @lyricstv4342
    @lyricstv4342 3 ปีที่แล้ว

    Sir salamat po sa idea.. Ask kang po pwd ba lagyan ng switch tv.. Amplifier..mega vision.. Lagyan ko sana ng switch pwed po bha?...kung pwed po anong switch po ang gagamitin.. Salamat po

  • @boybilliones3149
    @boybilliones3149 3 ปีที่แล้ว

    Happy New Year,Sir.paano po ba maglagay ng 110 volts outlet from the existing 220 volts outlet.thanks

  • @roelnarbuada6078
    @roelnarbuada6078 4 ปีที่แล้ว

    magbasi tayo lagi sa P E C pero ok yong turo mo boss

  • @superlando_12
    @superlando_12 4 ปีที่แล้ว +2

    Me as an e&i technician hindi q inaadvice na ganun k.rami ang ilaw na gagamitin...tama ka po sir lung mg.babase tayo sa specification ng isang device kung ilan ang maximum capacity nya may point ka don kase tama yung computation mo sir...pero yung point q...mgmamatter pa rin ang haba ng cable na ggamitin sa isang circuit sir..isa pa during maintenance dagdag trabaho kase halimbawa ngkaproblema ang isang circuit ng ilaw na may 15 lighting fixture ibig sabihin imbis na m.bilis ang troubleshooting, sa dami ng ilaw na kinabit hustle pa..another thing na nakita q kung ganyan karami ay kung halimbawa ang switch ang bumigay...edi lahat ilaw m.wawalan ng supply...tsaka sir alam q gusto mo lng ibahagi ang k.alaman mo pero pwede bang respetohin mo nmn ibang electrician?..wag mong sabihin na d lahat ng electrician alam to..ampangit pakinggan sir..ang labas eh ikaw na ang magaling...baka maraming electrician na mas may alam pa sayo sir m.papahiya ka lng...hindi mo ako basher sir gusto q lng liwanagin na hindi lahat ng nk.k.panood nito mga baguhang electrician...yung ibang nk.k.panood nito matagal na sa larangan ng kuryente kaya sana wag ganyang mga caption....salamat sir..asallamu alaikom

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Tnx additional info sir at bahagi ng idea nyo about caption ko sa video na ito

    • @aliasmoba6216
      @aliasmoba6216 4 ปีที่แล้ว

      Tama po kau jan sir... lalo na sa switch.. not advisable na lagyan yan ng pagkadami daming lights...
      My standard procedure parin pong sinusunod mga electricians.... saka po ung caption nio tibay, hahaha..
      Pero salamat na din po sa info..

    • @adobosinigang1716
      @adobosinigang1716 4 ปีที่แล้ว

      Tama k po sir para lumalabas s caption nya sya lng ang may alam at magling eh halata nman n may binabasa kapg nagpaliwanag n bubulol p

  • @rhodsztv2511
    @rhodsztv2511 4 ปีที่แล้ว +2

    Ok lang po Master.. Salamat din.

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      slamat po

  • @penglomaad276
    @penglomaad276 4 ปีที่แล้ว

    Oks lang.. happy fathers day.

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Happy father's day 🎉 din po sir

  • @rse9125
    @rse9125 4 ปีที่แล้ว +1

    Sna mapansin mo tong tanong ko Sir Jun.. Ano po ba ung mga dapat na nka separate circuit.. like ACU? etc.. Residential

    • @purasuporras7713
      @purasuporras7713 3 ปีที่แล้ว

      Lighting 15 amp. Convenience outler 30 amps.ref 30 amps. Range 30 amps. Aircon 30 amps. Water motor 30 amps

  • @loycaavlis3232
    @loycaavlis3232 4 ปีที่แล้ว +2

    Sir,Hindi b pwedeng idirec nyo n lng kng Ilang ilaw at Hindi n kailangang isama nyo p ung computation nyo,KC kn mgkkbit ako Ng switch kailangan ko PNG mgcmpute.

  • @gerwinytac6781
    @gerwinytac6781 3 ปีที่แล้ว

    sir jun dapat 100 watts ang kwentada bawat ilaw para safety. request lng sir jun sana actual naman...

  • @ajseranas858
    @ajseranas858 4 ปีที่แล้ว +1

    thanx sa lecture,,,sana yung wire naman ang capasidad ng watts at amperes,,at yung computataion ng ohms power watts at voltages,please pa shout out po ako

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Noted po sir... maraming salamat po sir

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      May table din po tayo jan sir

  • @brendayamano3350
    @brendayamano3350 4 ปีที่แล้ว +2

    As per pec every circuit for lighting is 10pcs 100watts

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Mam pwd po ba malaman kung anong article po yan sa PEC para madouble check ko po..

    • @BOSSrye1985
      @BOSSrye1985 4 ปีที่แล้ว

      13 lights per circuit 8 outlet per circuit naman sa power!

  • @michaelabad9458
    @michaelabad9458 4 ปีที่แล้ว +3

    Sir dpat ang ituro mo under PEC para safe at standard.wl sa PEC tinuturo mo.

    • @chesnutz9756
      @chesnutz9756 4 ปีที่แล้ว

      Totoo, parang nanghuhula lang eh. Sinabi na ngang 16A ang kaya ng switch hanggang 50 pcs lang daw na LED ang kaya.

  • @regieryanrobin90
    @regieryanrobin90 4 ปีที่แล้ว +1

    Tama boss..

  • @allanbutial1351
    @allanbutial1351 4 ปีที่แล้ว +1

    Master may video kba .. ng 3 ilaw at tatlong outlet.. 3 way swutch po.. tas yung outlet para sa aircon.. thanks..god bless

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Kung katulad po sa sinabi nyo sir wala po pero may single2 lng tayo

  • @kalikotkima
    @kalikotkima 2 ปีที่แล้ว

    Pwd ba gamitin ung 10A 16A na outlet dun sa #12 wire na ung breaker 20A?

  • @skateforfunnotforfame2033
    @skateforfunnotforfame2033 4 ปีที่แล้ว +1

    maraming salamat sayo bro

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Salamat din po sir

  • @philpineda9184
    @philpineda9184 3 ปีที่แล้ว

    Sa convinience outley 8maximun at sa lighting outlet 10sa isang homerun.

  • @junnelouritztrazona4524
    @junnelouritztrazona4524 3 ปีที่แล้ว

    Sir jun? Tanong lang po,
    Example sa isang plate may 2 gang outlets, yung 2 gang outlets po ba ang carrier ng 2000watts or kada 1 Gang outlets may 2000watts

  • @antoniocunanan2237
    @antoniocunanan2237 3 ปีที่แล้ว

    Second thought kung minsan loose connction between adapter and plug itself kaya may burn out ung outlet.

  • @EvendimataE
    @EvendimataE 4 ปีที่แล้ว +2

    ma susunog ba outlet pag i overload...e di ba kaya may breaker para mag trip before pa masunog?...kung tama ang breaker computation at wire sizing dapat mag trip pag na abot na yung max at di masunog.....kung na susunog ibig sabihin may mali

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Ganto sir...ang isang outlet 10A lng po breaker mo is 20a halimbawa sinaksak mo sa outlet 12A na load overload na ang outlet mo pero ang CB mo hindi pa,hindi po talaga magtitrip cb mo sir

    • @sergemcmc5189
      @sergemcmc5189 4 ปีที่แล้ว +1

      @@junauxtv so 10A ba dapat parehas ang breaker at outlet sir??

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว +1

      Hindi po sir for individual outlet lng ung 10A sa breaker mo gamit ka ng 20A

  • @islahanon1993
    @islahanon1993 4 ปีที่แล้ว

    Please post more.😀

  • @benhursalasar8687
    @benhursalasar8687 4 ปีที่แล้ว +1

    may mas madali dyan total kino compute monaman ang wattage. unahin monalang computen ang total watts ng ilaw na dumaan sa switch. tapos divide mona sa 230 at ang labas nyan dyan mona malalaman.

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Ang pinag uusapan kasi sir capacity ng switch kaya switch ang unang computation natin

    • @bondocfamily7254
      @bondocfamily7254 4 ปีที่แล้ว +1

      Tama yun compute wattage divide by 230. Yun na.

  • @dengjaen4208
    @dengjaen4208 4 ปีที่แล้ว

    Sir wala po bang tutorial ng cable tray fabrication, like 90° bend?

  • @doydoymacul3239
    @doydoymacul3239 4 ปีที่แล้ว +1

    Ser tanong kulang 100 ilaw at30 bentelador anong laki ng Generator ang dapat gamitin ilang AMP

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      ilang watts yong efan mo sir?

  • @registeredmasterelectrician
    @registeredmasterelectrician 4 ปีที่แล้ว +1

    Please always comply with the Latest Philippine Electrical Code of the Philippines. Thank you.

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Noted po sir... salamat po

    • @registeredmasterelectrician
      @registeredmasterelectrician 4 ปีที่แล้ว

      @@junauxtv You're Welcome po sir. Tuloy nyo lang po yan maganda yan marami ka po matutulongan. Keep up the good work.

  • @b2bgarment878
    @b2bgarment878 4 ปีที่แล้ว +1

    Good job bro ,ask k lng ano b o gaano b kataas dapat ang outlet s Flor o ground

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      May post ako sa Facebook page natin sir Jun Aux TV din po name.... important guildlines title nandon lahat sir...

    • @jomarbald087
      @jomarbald087 4 ปีที่แล้ว +3

      30 cm boss

  • @marjorieabellana507
    @marjorieabellana507 4 ปีที่แล้ว +1

    Sir gud pm po halimbawa po naglilinya ka po na nakabukas po yung breaker sa main switch po pwd mo po bang hawakan ang isang linya may kuryente po ba yun at kung isang linya ay nakatugtong na po sa isang linya po i mean line 1 sa line 1 yung line 2 idudugtong mo pa lng gamit ang kamay makukuryente ka po ba salamat po sa Dios gandang gabi

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว +1

      Hi mam... technically meron pong way but kahit sinu pong license Electrical practitioner hindi po namin nirerecommend yan at hindi din po namin pinapractice...mas maganda po na safe po tayo palage...

    • @marjorieabellana507
      @marjorieabellana507 4 ปีที่แล้ว

      @@junauxtv sir salamat po sa Dios pwd mo po ba ituro kung paano po bumasa o gumamit ng tester po salamat po

  • @rodelioabing7437
    @rodelioabing7437 3 ปีที่แล้ว

    Sir meron kami ng 500 watts mercury lamp kaya ba ito sir sa isang switch

  • @dreambelieve3920
    @dreambelieve3920 4 ปีที่แล้ว

    Sir pag sinaksak Ang 10 amper sa 10 amper mag aapair Kang ba yun

  • @kakalikot3957
    @kakalikot3957 4 ปีที่แล้ว

    100 watts lang po ay bumibigay na ang switch after less thsn a month.
    kelangan mo na jan ng relay

  • @vegericecropstv5326
    @vegericecropstv5326 4 ปีที่แล้ว +1

    Bro dpnde pa kac yan sa haba ng wire n ggamitin, ,,pero galing saludo aq sau ,

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Yes sir... actually daming factor pa ang dapat iconsider..

  • @thelmasevial5686
    @thelmasevial5686 4 ปีที่แล้ว +2

    May 20 ako ilaw na 18 wats 1 lang breker 30a estrit light pwuede ba ako mag lagay sa getna ng breker

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Ano size ng wire mo sir?

    • @jomichgates1868
      @jomichgates1868 4 ปีที่แล้ว +1

      Sir...mataas na nga po rating ng breaker nyo...10A or 15 enough na po kc 360 watts lang po total load nyo...

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว +1

      Consider voltage drop kasi medyo may kalayoan yan... street light eh...the bigger the wire the higher allowable ampacity

  • @ryangaspar6638
    @ryangaspar6638 3 ปีที่แล้ว

    Hello po sna ma notice po ask ko sna ano po ba required amperes kpg s ref po sna po masagot thnk you po

  • @rigilkentsolomonjuanga3682
    @rigilkentsolomonjuanga3682 4 ปีที่แล้ว +5

    Sir, kada aircon ba isang breaker dapat?

  • @pinleonero6263
    @pinleonero6263 4 ปีที่แล้ว

    Sir San kinuha yung 0.8? Safety factor satin SA pinas standard?

  • @philnewsvlog5183
    @philnewsvlog5183 4 ปีที่แล้ว +1

    Nice master

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Salamat po sir

  • @theobserver9722
    @theobserver9722 4 ปีที่แล้ว +1

    Sir tanong lng..positive at negative saan po jn ung hot wire po..slamat sa if masagot po..

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Positive and negative sa DC lang po un sir.....

    • @jeromeb.6991
      @jeromeb.6991 4 ปีที่แล้ว

      pag AC walang polarity yun brad. Sa ibang bansa may color coding ang hot wire at return wire, pero ang purpose nun is para madali makita kapag may maintenance hindi sya polarity.

  • @mbp9012
    @mbp9012 4 ปีที่แล้ว +1

    Boss tanung ko lang po kung pwede isaksak ang 200amp inverter welding machine sa 20amp na outlet?

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Ano ang input amps sir ng welding machine mo sir?

    • @jessonraypan8921
      @jessonraypan8921 4 ปีที่แล้ว

      d pwde yan..dapat may sariling breaker ka jan..masyadong mataas yan boss

    • @ashleykate1286
      @ashleykate1286 4 ปีที่แล้ว

      @@jessonraypan8921 pwedi yan. Di naman sinasagad sa 200 amp ang welding machine. Di ka na makakahinang pag nag set ka 200.

  • @nielpulgo7364
    @nielpulgo7364 4 ปีที่แล้ว +2

    Sir tanung lang...yung multply by 230 saan mo nakuha yan..tanx

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว +1

      Ang nominal value sir ng 220 is 230v according to the code book sir

  • @myrnadaclagdeck4865
    @myrnadaclagdeck4865 4 ปีที่แล้ว +1

    may tanong lang,,sana makakuha ako ng explanation at anong gagawin..una may appliances akong galing europe gagamit din naman kami ng 220 230 watt dito sa europe.. at may 50 herz dahil sa pinas ay may 60 herz.ngayon ang mangyayari kailangan gagamit daw ako ng AVR..mayroon bang ibang paraan na hwag ng gagamit ng AVR...??? dapat ba namay separate na kuryente sa panel breaker ilang amphere at palitan ba ng malalaking wire..ano batalaga dapat palitan..?? thank you..

    • @renegacusan7090
      @renegacusan7090 4 ปีที่แล้ว +1

      Depende po kung ano appl.na 50hz.

    • @justinlouisenicomedez8671
      @justinlouisenicomedez8671 4 ปีที่แล้ว +1

      AVR: Automatic Voltage Regulator.. sir gamit kana lang ng avr kasi may effect lagi ang frequency sa appliances..mas hahaba kung explaine ko pa kung bakit.. advisable na dapat kung ano ang specification ng appliances dapat yun ang susundin..gagana naman yang appliances nyu sa 50hz to 60hz na same ang voltage or vice versa kasu masisira agad ang appliances.. hehehe

    • @purasuporras7713
      @purasuporras7713 3 ปีที่แล้ว

      220 volts 230 volts cguro ang ibig mong sabihin.gumamit kn ng AVR

  • @tadman2698
    @tadman2698 3 ปีที่แล้ว +1

    He bro magandang hapon tanong kulang dito saamin pag gabi 110v Lang a suplay ng korenty namin so ayaw umandar ung ref namin sa gabi
    Anoba ang pwidi ko bilhin na items para sa problima sa 110v
    My iba sabi saakin avr regulator daw 1000 pataas mas maganda daw
    Ung sa kaalaman mo ano ang solosion dito sa 110v na korenty sa gabi salamat sa isasagot mo bro

    • @junauxtv
      @junauxtv  3 ปีที่แล้ว

      Transformer sir...pero pwd din po ung avr sir...need mo lang mataas na wattage sir

    • @tadman2698
      @tadman2698 3 ปีที่แล้ว

      Ung 1000watts makaya niya ung ref na dalawa tag 150watts siya talagang sa umagalang umaandar

    • @tadman2698
      @tadman2698 3 ปีที่แล้ว

      Hello bro ung step-up & down transformer 500watts pwidi kaya

  • @randyflores4395
    @randyflores4395 4 ปีที่แล้ว +2

    Boss paturo naman kung pano malalaman kung 1ton ang aircon. God bless po!

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว +1

      Cg po sir...

    • @doods4301
      @doods4301 4 ปีที่แล้ว +2

      hahahaha ikunsulta pa daw ni Sir sa PEC.. 1 Ton A/C is 12000 BTU..,,,,12000 BTU is 4.7172 - HorsePower-Hour

    • @iandaligdig4520
      @iandaligdig4520 4 ปีที่แล้ว

      Naka base Ang aircon sa HP Hindi ton..

  • @juliusbornilla6504
    @juliusbornilla6504 3 ปีที่แล้ว

    Sana next naman master obout firealarm,

  • @rodelioabing7437
    @rodelioabing7437 4 ปีที่แล้ว

    It mean sir yung 500 watts mercury lamp ok yun gamitin

  • @jomelperez3169
    @jomelperez3169 2 ปีที่แล้ว

    Maganda rin mga video sir ..kaya lang medyo mahina boses mo sir.... medyo lakas lakasan mo sir boses mo .....salamat po...

  • @berg498
    @berg498 4 ปีที่แล้ว +1

    Sir sa standard po natin 100watts tayo per light..so 2,944 watts divide 100watts is 29.44..pwede po tayo maglagay ng 29 lighting bulb sa isang switch..share q lng po..if mali po aq pacorrect na lang po..salamat po..

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      ang pinag uusapan natin dito is capacity ng switch kung ilang watts na capable ihandle although doon pa rin babagsak sa 100watts kasi connected sa CB which is minimum VA for lighting.. thank you sir

    • @dennisjhoncarino8041
      @dennisjhoncarino8041 4 ปีที่แล้ว

      Saan naman po kinoha yong .8 na nasabe

  • @ricomartinez6982
    @ricomartinez6982 4 ปีที่แล้ว +1

    Sir anung kaibhan Ng rated capacity sa breaker at sa mga switches or convenience outlet?

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Sa breaker trip lang, sa switch at outlet more than sa rated amps masusunog na

    • @myteknik5051
      @myteknik5051 4 ปีที่แล้ว

      Ok po thnks po..watch ka din po ng videos ko thnks po

  • @chriztian133
    @chriztian133 4 ปีที่แล้ว

    Thank You Sir

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว

      Salamat din po

  • @StillLearning08
    @StillLearning08 4 ปีที่แล้ว +2

    Sir, tanong lang po. Pwede bang mag home run ng 12 tapos ang return ay 14? Saka san ko ilalagay ang switch sa 14 AWG or aa 12 AWG? Sana masagot mo Sir. Salamat.

    • @junauxtv
      @junauxtv  4 ปีที่แล้ว +1

      Hindi po dapat sa isang circuit isang wire size lng po

    • @benhursalasar8687
      @benhursalasar8687 4 ปีที่แล้ว +4

      dipendi yan kong ilaw 14 ang gawen mong home run at return pera sa mga outlet naman ay 12. pero dapat mong isepin din pag maramihang ilaw dapat 12 ang gamitin mosa home run. oh galing source to breacker.

    • @redentorromero7192
      @redentorromero7192 4 ปีที่แล้ว +5

      Example. Isang circuit yung wire papuntang breaker yun ang homerun boy....

    • @redentorromero7192
      @redentorromero7192 4 ปีที่แล้ว +4

      Yung current galing sa switch papuntang light... Yung ang return... Boy....

    • @jessonraypan8921
      @jessonraypan8921 4 ปีที่แล้ว +2

      @Andie Basarte ang homerun yun yung pupunta ng breaker..samantala ang return sa switch lang yan babagsak

  • @altvshow2281
    @altvshow2281 4 ปีที่แล้ว

    Boss jun ask ko lang kong pwede ako mag top ng line source sa isang switch para sa ref and washing machine?

    • @purasuporras7713
      @purasuporras7713 3 ปีที่แล้ว +1

      Di pede.seperate mo na ang ref. 30 ampers