Thank you for the video. Please kindly answer this question👉👉Why doe a Cummins generator controller(ps0600) reset the running hour and change the genset configuration by itself? Thanks!
Dear Sir Thank you for chosen DIY & Fix it Your controller may not programmed / calibrate well , By pressing ok and reset key you are gonna start calibration I wish to have PS0600 or PS0500 to make a You Tube video.
@@northjayhoon9789 Grateful to your support🙏 I tried to enter into configuration mode and seen "J16-9 SENSOR SEL" changed into "Not connected" inside Genset configuration after the reset. When the reset occurs again the configuration is changed and due to this when a remote start signal is received the DG cranks but fails to start. Hopefully waiting you next video on 0ps600 controller.🙏
Sir, can I ask for a wiring diagram of the same unit. Our unit at site is P200-2. We have a problem with our fuel solinoid voltage supplies.no voltage showing whilst starting and engine won't start. Thank you sir
Thank you for your enquiry! If your generator's controller indicates/ warning high battery alarm, definitely you need to check DC alternator . An alternator's output is controlled by an integrated voltage regulator, which is designed to prevent overcharge. You may have a faulty voltage regulator and it does over charge your battery.
th-cam.com/video/GseWzLig-k0/w-d-xo.htmlsi=QXbhe2sQkUUZg2r0
Thanks for the idea🌟
Yes another idea thanks again broooo........
Hi sir, useful and informative
So nice of you
Very helpful Sir. Thank you
Happy to help
Congratulations 🎉
Thank you for the video. Please kindly answer this question👉👉Why doe a Cummins generator controller(ps0600) reset the running hour and change the genset configuration by itself? Thanks!
Dear Sir
Thank you for chosen DIY & Fix it
Your controller may not programmed / calibrate well ,
By pressing ok and reset key you are gonna start calibration
I wish to have PS0600 or PS0500 to make a You Tube video.
@@northjayhoon9789 Grateful to your support🙏 I tried to enter into configuration mode and seen "J16-9 SENSOR SEL" changed into "Not connected" inside Genset configuration after the reset. When the reset occurs again the configuration is changed and due to this when a remote start signal is received the DG cranks but fails to start. Hopefully waiting you next video on 0ps600 controller.🙏
Thankyou for the video, please do the testing by Multi metre
Noted!
Thanks sir .very informative
Thanks for liking
thank you so much ,then the first relay before the fuel relay is call what?
SAR Stands for start aid relay, SAR relay is controlled by GSC .
SAR supplies power for the Glow plugs .
Sir, can I ask for a wiring diagram of the same unit. Our unit at site is P200-2.
We have a problem with our fuel solinoid voltage supplies.no voltage showing whilst starting and engine won't start.
Thank you sir
Greetings
Thank you for your request
Please send me an email to
north.jayhoon@gmail.com
I will send you the wiring diagram.
All the best
Thanks
You're welcome!
Good evening my volvo D9 generator say engine can bus fault emergency stop hardware any ideas how to fix it please
CAN Controller for CAN Bus may be faulty
Check the wiring
Check the Controller unit
@northjayhoon9789 will do thanks a lot 👍🏻👍🏻
Hello sir.new subcriber.
Welcome!
How to problem alarem high volteg battrie ....?
Thank you for your enquiry!
If your generator's controller indicates/ warning high battery alarm, definitely you need to check DC alternator .
An alternator's output is controlled by an integrated voltage regulator, which is designed to prevent overcharge.
You may have a faulty voltage regulator and it does over charge your battery.
Good
👏👏
❤