Hello We have problem with ge/AF650 or danfous speed controller. when it starts up to 40hz speed. It stops and displays an alarm (WARNING/ALARM 7, DC over voltage) and 2nd time alarm (WARNING/ALARM 8, DC under voltage) Please how is the solution? Thanks
1. Symptom: Motor is not reaching maximum speed, Possible cause: Frequency limits set wrong. Test: Check output limits in parameter 4-13 Motor Speed High Limit [RPM], parameter 4-14 Motor Speed High Limit [Hz], and parameter 4-19 Max Output Frequency. Solution:Program correct limits. Possible cause: Reference input signal not scaled correctly. Test: Check reference input signal scaling in parameter group 6-0* Analog I/O mode and parameter group 3-1* References. Solution:Program correct settings 2. Symptom: Motor speed unstable Possible cause: Possible incorrect parameter settings. Test: Check the settings of all motor parameters, including all motor compensation settings. For closed-loop operation, check PID settings. Solution: Check settings in parameter group 1-6* Load Depen. Setting. For closed-loop operation, check settings in parameter group 20-0* Feedback.
Hi Iam facing error in VLT Danfoss FC102. 250Kw DC over Voltage A7 I have increased the Ramp Down time from 8sec/15sec but still the problem same as per your informative video their in no any option in the hardware for Brake Resistor could you pls help me
Error 199 Internal MCO fault: If such an error should occur, please contact your dealer and report the error number displayed to the technical service department.
Hello
We have problem with ge/AF650 or danfous speed controller. when it starts up to 40hz speed. It stops and displays an alarm (WARNING/ALARM 7, DC over voltage) and 2nd time alarm (WARNING/ALARM 8, DC under voltage)
Please how is the solution?
Thanks
1. Symptom: Motor is not reaching maximum speed,
Possible cause: Frequency limits set wrong.
Test: Check output limits in parameter 4-13 Motor Speed High Limit [RPM], parameter 4-14 Motor Speed High Limit [Hz], and parameter 4-19 Max Output Frequency.
Solution:Program correct limits.
Possible cause: Reference input signal not scaled correctly.
Test: Check reference input signal scaling in parameter group 6-0* Analog I/O mode and parameter group 3-1* References.
Solution:Program correct settings
2. Symptom: Motor speed unstable
Possible cause: Possible incorrect parameter settings.
Test: Check the settings of all motor parameters, including all motor compensation settings. For closed-loop operation, check PID settings.
Solution: Check settings in parameter group 1-6* Load Depen. Setting. For closed-loop operation, check settings in parameter group 20-0* Feedback.
Hi’ Auto on indication on and off automatically what does its mean?
Can you explain about option detection alarm
how i adjust quick stop time on parameter 3-81 i
Alarm led glows vfd stops with text message 1A0. What does 1A0 means
Hi Iam facing error in VLT Danfoss FC102. 250Kw DC over Voltage A7 I have increased the Ramp Down time from 8sec/15sec but still the problem same as per your informative video their in no any option in the hardware for Brake Resistor could you pls help me
If the alarm/warning occurs during a power sag,
use kinetic back-up (parameter 14-10 Mains
Failure).
@@controlsSystemsofficial could you pls guide me
@@controlsSystemsofficial thank you for your prompt support
I have an alarm on my danfoss vlt internal MCO error[A199]
Please how can i solve it ?
Error 199
Internal MCO fault:
If such an error should occur, please contact your dealer and report the error number displayed to the technical service department.