  • Danfoss VLT Micro drive FC 51 VFD Warnings, Alarms, Trip Locks, Errors and cause of problems overview.
    If you are watching our videos first time subscribe to our TH-cam channel this will help us to make more videos and don’t forget to click the bell icon button you will never miss our latest videos.
    Welcome to controls and systems TH-cam channel.
    The following Warnings, Alarms, Trip Locks, Errors and cause of problems are covered in this videos is:
    (Live zero error , Mains phase loss , DC over voltage,DC under voltage,Inverter overloaded,Motor ETR over temperature,Motor thermistor over temperature,Torque limit, Overcurrent,Ground fault,Short circuit,Control word timeout,Brake resistor short-circuited,Brake chopper short-circuited,Brake check,Power board over temperature, Internal fault,Control voltage fault,Current limit,Copy fail,Parameter database busy, and more....)
    DANFOSS OTHER VFD DRIVE VIDEOS:
    1.Danfoss VLT Micro Drive FC 51 Name Plate Sticker: • #Danfoss VLT Micro Dri...
    2. Danfoss VLT Micro Drive FC-51 Parameter Settings: • #Danfoss VLT Micro Dri...
    3. DANFOSS FC 51 VLT Micro drive Settings: • #DANFOSS FC 51 VLT Mic...
    4. Danfoss VFD Drive LCP SIMULATOR Tool Overview: • Danfoss VFD Drive LCP ...
    5. Danfoss VLT VFD Drive FC 301 and 302 Warnings and Alarms 11 to 20: • Danfoss VLT VFD Drive ...
    6. Danfoss VLT VFD Drive FC 301 and 302 Warnings and Alarms: • #Danfoss VLT VFD Drive...
    7. DANFOSS VLT-6000 HVAC VFD Drive Basic Setting Parameter Part-1: • #Danfoss #VLT 6000 #HV...
    8. Danfoss VLT Automation Drive FC-301/302 Setting Parameters Part-1: • #Danfoss FC 301/302 Vf...
    9. DANFOSS INVERTER FC-301 / 302 Setting Parameters (Part-2): • #Danfoss Inverter #FC3...
    10. DANFOSS INVERTER FC-301 / 302 Setting Parameters (Part-3): • #Danfoss #Inverter #FC...
    11. DANFOSS INVERTER FC-301 / 302 Setting Parameters (Part-4): • #Danfoss #Inverter FC ...
    DANFOSS VFD SETTINGS & ERRORS BLOG:
    1.DANFOSS FC-304 VFD DRIVE PARAMETER SETTINGS: shorturl.at/zKPZ9
    2.DANFOSS FC-304/302/301 VFD DRIVE PARAMETER SETTINGS PART-2: shorturl.at/cikyD
    3.DANFOSS VLT 6000 VFD DRIVE PARAMETER LIST shorturl.at/DKQ69
    4.DANFOSS VLT 2800 VFD DRIVE PARAMETER LIST: shorturl.at/jknxT
    5.Danfoss VLT VFD Drive FC 301/302 Warnings and Alarms 1 to 10: rb.gy/yqo52
    6.Danfoss VLT micro drive FC 51 Name Plate: rb.gy/370qv
    7.VFD DRIVES TROUBLESHOOTING: rb.gy/n6jwm
    To Know More Information, follow our Blog, if you want any query's please contact us & follow our social media sites for regular updates.
    Gmail controlsandsystemscbe@gmail.com
    SOCIAL MEDIA SITS:
    Blogger: controlsandsys...
    TH-cam Shorts: www.youtube.co...
    Facebook: / controlsandsystemscbe
    Facebook Group: / 790234542517226
    Twitter: / controlsandsys1
    LinkedIn: / controls-systems-10774...
    Tumblr: / controlsandsystemscbe
    Instagram: / controlsandsystemscbe
    Slides Share: www.slideshare...
    Pinterest: / controlsandsystemscbe
    Will we hope this video is useful to you, if you have any queries feel free to comment below, we will meet in another good video , thank you for watching our videos, have a great day.

ความคิดเห็น • 24

  • @rajeshmg321
    @rajeshmg321 ปีที่แล้ว

    Good video❤👍👍
    Thank you sir thank you for uploading this video

  • @AR-TV0996
    @AR-TV0996 2 หลายเดือนก่อน

    How can we fix DC over voltage warning alam 7 in FCD 302

  • @suhailjamadar7267
    @suhailjamadar7267 2 ปีที่แล้ว +1

    Al -048 gate dirve voltage fault. What's the solution for this

  • @ridwansaputra1540
    @ridwansaputra1540 ปีที่แล้ว

    W8 , I can’t figure it out , could you help me?

  • @gerardallendelacruz1257
    @gerardallendelacruz1257 ปีที่แล้ว

    how to fix or troubleshoot alarm 9 sir inverter overload

  • @thailottery1986
    @thailottery1986 ปีที่แล้ว

    Alaram. 16 motor good

  • @baskarbaski4056
    @baskarbaski4056 6 วันที่ผ่านมา

    Alarm 46 missing

  • @luisbolado1729
    @luisbolado1729 2 ปีที่แล้ว

    Excuse me
    Can you tell me how can solve the alarm 08 (DC Under voltaje)?

    • @controlsSystemsofficial
      @controlsSystemsofficial  2 ปีที่แล้ว

      WARNING/ALARM 8, DC under voltage
      If the DC link voltage drops below the undervoltage limit, the frequency converter checks if a 24 V DC back-up supply is connected. If no 24 V DC back-up supply is connected, the frequency converter trips after a fixed time delay. The time delay varies with unit size.
      Troubleshooting
      • Check that the supply voltage matches the frequency converter voltage.
      • Perform an input voltage test.
      • Perform a soft charge circuit test

  • @produitsdeamazon8650
    @produitsdeamazon8650 11 วันที่ผ่านมา

    error34😭

  • @mohammedazif3076
    @mohammedazif3076 ปีที่แล้ว

    Feedback error a61 is caused by what problem

    • @controlsSystemsofficial
      @controlsSystemsofficial  ปีที่แล้ว

      Warning/Alaram 61: Feedback Error,
      An error between calculated speed and speed measurement from the feedback device.
      Troubleshooting:
      1.Check the settings for warning/alaram/disabling in parameter 4-30 motor feedback loss function.
      2. Set the tolerable error in parameter 4-31 motor feedback speed error.
      3. Set the tolerable feedback loss time in parameter 4-32 motor feedback loss timeout.

  • @shamidshimid9248
    @shamidshimid9248 2 ปีที่แล้ว

    What is w12 warning in drive

    • @controlsSystemsofficial
      @controlsSystemsofficial  2 ปีที่แล้ว

      Warning 12: Torque limit,
      Cause of problem:
      Torque exceeds value set in either parameter 4-16 Torque Limit Motor Mode or parameter 4-17 Torque Limit Generator Mode.

    • @shamidshimid9248
      @shamidshimid9248 2 ปีที่แล้ว

      @@controlsSystemsofficial thank you sir

    • @shamidshimid9248
      @shamidshimid9248 2 ปีที่แล้ว

      Please tel me , what shal I do now, what changes I want to do, warning 12 it is 4-16 is100% 4-17 is 100%. And warning no 7 also coming over dc voltage

  • @rockyvideos4014
    @rockyvideos4014 2 ปีที่แล้ว

    Can you tell me how to resolve alarm 7

    • @controlsSystemsofficial
      @controlsSystemsofficial  2 ปีที่แล้ว

      ALARM 7, DC overvoltage,
      If the intermediate circuit voltage exceeds the limit, the frequency converter trips after a time.
      Troubleshooting:
      1.Connect a brake resistor,
      2.Extend the ramp time,
      3.Change the ramp type,
      4.Activate the functions in 2-10 Brake Function,
      5.Increase 14-26 Trip Delay at Inverter Fault,
      The fault may be caused by mains distortions. Installing Danfoss Line Filter may rectify this problem

  • @Edilawit9
    @Edilawit9 2 ปีที่แล้ว

    please bro is soliving alarm light solving problem and errors code 85

    • @controlsSystemsofficial
      @controlsSystemsofficial  2 ปีที่แล้ว +1

      Error 85 is Key disabled :
      Please Check the parameter 0-40 [Hand on] Key on LCP is:
      [0] Disabled or
      [1] Enabled

  • @rajeshkumar-fp6vs
    @rajeshkumar-fp6vs 2 ปีที่แล้ว

    Sir what is Alarm 68 please

    • @controlsSystemsofficial
      @controlsSystemsofficial  2 ปีที่แล้ว +1

      The ALARM 68 is not Available in FC-51 model Fault List,
      This ALARM 68 in only present in FC-102 model fault List:
      Before Clear this error please go through the FC-102 model manual,
      ALARM 68, Safe Stop activated
      Safe stop has been activated. To resume normal operation,
      apply 24 V DC to terminal 37, then send a reset signal (via
      Bus, Digital I/O, or by pressing the reset key).

  • @thailottery1986
    @thailottery1986 ปีที่แล้ว

    Without motor same alaram

  • @9981493224
    @9981493224 ปีที่แล้ว

    Pw show after press menu key
    Model is fc51