GAS PRESSURES PART 1, a gas tutorial all about standing, working and operating pressures for ga.s.

แชร์
ฝัง
  • เผยแพร่เมื่อ 15 ต.ค. 2024

ความคิดเห็น • 193

  • @lifeintheuk4854
    @lifeintheuk4854 หลายเดือนก่อน +1

    GOD bless u sir, you u are the best ever teacher very easy way of teaching

  • @mohammednadeem7274
    @mohammednadeem7274 3 ปีที่แล้ว +12

    Another amazing video Derek, don't know why they've changed working pressure to operating pressure confusing our little brains. 😂😂, this was a brilliant video & well presented like always whether its in the classroom with you or watching you on videos you're always the top Tutor.. 👍👍😀😀

  • @fredhines8169
    @fredhines8169 ปีที่แล้ว +1

    This bought back memories...I did my Indentured Gas Apprenticeship in the 1960s when we still had "town gas". In those days the apprenticeship was from leaving school at just 15 to 21, almost 6 years. But, in those days we learned everything about gas, from how gas was made, how it was distributed throughout the district gas mains, how and why gas holders were built. etc, etc... It was a great apprenticeship, taught me well, and gave me a good living... oh, and it was quite common to get a clip round the ear off your fitter if you gave him some lip... Great times.

  • @sarkodiejacobdarkwah4675
    @sarkodiejacobdarkwah4675 2 ปีที่แล้ว +2

    You are such an incredible technical instructor. You’ve assisted most of us initial assessment understanding the practical know how to the industry.

  • @ahmadjavaherian1366
    @ahmadjavaherian1366 2 ปีที่แล้ว +2

    Great video , I was a bit confused before watching the video about the Permissible Drop but now I'm fully understood , Thanks Derek

  • @anthonygaunt8974
    @anthonygaunt8974 3 ปีที่แล้ว +3

    I think I’ve watched nearly all of your tutorials I now fully understand what you are saying keep up the good work and keep them coming Derek kind regards Tony gaunt🤗

  • @gf5328
    @gf5328 3 ปีที่แล้ว +5

    You are a legend! Thank you so much and very appreciated.
    You are actually extremely helpful and clear on explaining. Everything spot on.

  • @asoreng4030
    @asoreng4030 3 ปีที่แล้ว +1

    You are a very good teacher.. down to basic and then you build up knowledge for learners to understand.Thank you

  • @phoneblaster
    @phoneblaster ปีที่แล้ว

    ...a great video Derek. Keep up the amazing videos you take the trouble and time to make. Just to give you some insight as to why they have changed 'working pressure' to now 'operating pressure. I know this video is I guess over two years since you made it, bvut I have just come across it now. That is'enough of the waffling, lets get right into it' as you say.
    1. Working pressure:
    Well, working pressure is not a 'dare I say' a 'standard' . Unless ofcourse 'all' appliances were made to 'operate' at a specific given @ Rate of figure. Design, materials, size, etc will no doubt differ from for a start manufacturer to manufacturer as well as country to country.
    Operating pressure:
    So they rightly come up with the term 'operating pressure'.. This can now be used as a means of 'standard', covering all types of appliances as the manufacturers have stenciled the 'working/operating' pressure on the unit.
    2. Standing pressure
    The 'standing pressure' is there as a form of supply and demand. Just to illustrate , lets bring in a water/shower pump. Say I connect up the water pump to the water Mains supply and Not an Overhead water Tank ! What will happen ? Depending on the regular 'usage', the pump will burn out , and that is within say 1 week. If you are lucky maybe 2 weeks. Why is that? It is because the 'standing' pressure is not meeting the 'operating' pressure of the pump. So the pump manufacturers as part of their design have used the 'standing' pressure as part of the formula to manufacture their different pumps. But the 'standing' pressure is Not the water Mains supply, but a water Tank. This will ensure there is enough water to meet the 'standing' pressure for that particular water pump. Hope my waffling helps. lol

  • @stewartharrod1706
    @stewartharrod1706 3 ปีที่แล้ว +1

    Outstanding video so clear and the details are perfect
    It's finally printed into my brain
    You deserve more commendation for your work 💪

  • @mohammednazir8307
    @mohammednazir8307 2 ปีที่แล้ว +1

    Brilliant video derek. Revising for my Initial assessments. Thanks for giving us the understanding of not just carrying out standing & operating pressure but to understand why we have these figures in place i.e 21+-2. Trainee at tomkat gas training center. 🙂

  • @mj0n4id36
    @mj0n4id36 3 ปีที่แล้ว +2

    Great video on tightness testing and pressures at the meter. Everything explained nicely and easy to understand. From now on I will try to refer to working pressure as operating pressure!
    Does anyone else take ages filling a u-gauge with water and trying to level it at zero and get soaked whilst doing it or is it just me 🤣. Thanks Derek 👍🏻
    Asian Jon. Training.

  • @TonyRayner-v5w
    @TonyRayner-v5w 8 หลายเดือนก่อน

    Always brilliant derek

  • @hamzaparvais3948
    @hamzaparvais3948 2 ปีที่แล้ว

    Really injoy watching easy to understand thanks keep the good work up

  • @piotrmarchwacki3414
    @piotrmarchwacki3414 3 ปีที่แล้ว +1

    Very informative video. Thanks Derek 👍😀

  • @hafizimran6021
    @hafizimran6021 3 ปีที่แล้ว +1

    Excellent video 👍

  • @juliananthony278
    @juliananthony278 ปีที่แล้ว

    Thank you for all your videos derick

  • @coolsandeepuk
    @coolsandeepuk 3 ปีที่แล้ว +1

    Good video for proper understanding let by and all test thanks Tom

  • @leonardbalint4930
    @leonardbalint4930 3 ปีที่แล้ว +1

    Thank you Derek, like always I really enjoyed your videos, the explanation very clear

  • @93_rafael
    @93_rafael 3 ปีที่แล้ว +2

    What a legend. Thank you for sharing your knowledge

  • @forevershine.uk1681
    @forevershine.uk1681 3 หลายเดือนก่อน +1

    Nice job ❤

  • @g7mks383
    @g7mks383 3 ปีที่แล้ว

    Great video on tightness testing and pressures at the meter very clear thanks.

  • @ceejay911do2
    @ceejay911do2 3 ปีที่แล้ว +1

    As allways absolute amazing mate ✌️👍😊well explained !never seen a better trainer !!you have the German in you 😘Connor

  • @MrJJMcD
    @MrJJMcD 8 หลายเดือนก่อน

    Derek great video.
    Since this video was posted there has now been a small change the operating pressure is now from 18.5mb - 23mb. Dont know why?

    • @tomkatgastraining
      @tomkatgastraining  8 หลายเดือนก่อน

      I have done a video on it have a look on the channel for it 👍🏻

  • @7dayplumbingservices195
    @7dayplumbingservices195 3 ปีที่แล้ว +2

    Great video again thanks . Are you planning to do videos on chimneys ( a long and interesting topic...)

  • @advancestarcleaningandmain3015
    @advancestarcleaningandmain3015 3 ปีที่แล้ว

    thank you DEREK FOR YOUR GREAT SERVICE ,GREAT TEACHING

  • @salvopalali5206
    @salvopalali5206 2 ปีที่แล้ว

    These videos are so helpful sir

  • @AmjidKhan-h6b
    @AmjidKhan-h6b 2 หลายเดือนก่อน

    Hi Derek,
    Much appreciated providing these types of training videos it helps us new entrants a lot. I have a question in regard to one of your comments below stating the maximum flow rate of a meter is 3.5m3, I am confused as the meter on a G4 or U6 states 6m3h?
    Could you please explain how and why it’s 3.5m3 and if possible which BS document thanks.

    • @tomkatgastraining
      @tomkatgastraining  2 หลายเดือนก่อน

      I think if you watch the video again it will make more sense. The 3.5 m3 isn’t the maximum the meter can make it’s the maximum being used for working pressure

    • @AmjidKhan-h6b
      @AmjidKhan-h6b 2 หลายเดือนก่อน

      Thanks again it makes sense now.
      Really appreciated Derek 👍

  • @billy882in1
    @billy882in1 2 ปีที่แล้ว

    Clear Explanation on every thing regarding pressure, thanks Derek! ‘Bilal M’ trainee tomcat.

  • @michaelrose5040
    @michaelrose5040 3 ปีที่แล้ว

    Always top videos off Derek

  • @abuadammemon3968
    @abuadammemon3968 3 ปีที่แล้ว +1

    Very good and appreciated
    Now if you can make some video on Regulations, ID,At Risk,responsibility of Landlord, Gas suppliers, and engineers,
    Thank you Derek
    Bless you 🙏

    • @tomkatgastraining
      @tomkatgastraining  3 ปีที่แล้ว

      All ready have check out my channel you will find them there

  • @chrisjones4500
    @chrisjones4500 2 ปีที่แล้ว

    Great video...thanks Derek.

  • @Lion-jz1xz
    @Lion-jz1xz 2 ปีที่แล้ว

    Thanks again Derek for sharing this helpful information with us it’s been very easy for me to understand that, also wondering where to getting a U_gauge like you’re using it in this video 🙏

    • @tomkatgastraining
      @tomkatgastraining  2 ปีที่แล้ว

      I get our u gauges from BES but most plumbers merchants or eBay sell them

  • @raul835
    @raul835 3 ปีที่แล้ว +2

    Never knew why it had to be 19-23.. I do now. Thanks for plugging another wee gap in my knowledge.

    • @stuartcoulthurst8377
      @stuartcoulthurst8377 3 ปีที่แล้ว

      Used to be 20-22 until National Grid/BG got fed up of being called out to 19 and 23 mb working pressures

  • @1981kurczak
    @1981kurczak 3 ปีที่แล้ว

    great !!! well explained , Tom good job

  • @oluwasolaogunshemi5785
    @oluwasolaogunshemi5785 3 ปีที่แล้ว

    I am indeed very grateful for this explanation

  • @fzalos2327
    @fzalos2327 7 หลายเดือนก่อน

    I hope i will learn too Derek

  • @1414141x
    @1414141x 2 ปีที่แล้ว

    Yes, you did say that if you have a drop you then test the carcass whcih is allowed a zero drop. This basically means the drop allowance is on an appliance that is fitted. (assuming no smell)

  • @andrewthomas332
    @andrewthomas332 3 ปีที่แล้ว

    explained in easy steps. thanks Tomkat

  • @efrygasservices6169
    @efrygasservices6169 3 ปีที่แล้ว

    Very simple explanation pal 👍

  • @themadhatter4761
    @themadhatter4761 3 ปีที่แล้ว

    Great video as usual, could you please explain the following in your next video:
    Why is any MB drop allowed on appliances, it’s a gas leak!
    What is the correlation between type of meter and size of MB dropped allowed.
    Again great channel. 👍👍

    • @tomkatgastraining
      @tomkatgastraining  3 ปีที่แล้ว +1

      Have you not Sean my video on gas meters? More information coming on Wednesday so look out for that 👍🏻

  • @brendonoreilly2143
    @brendonoreilly2143 3 ปีที่แล้ว

    Great content Derek can u just ask if the operating pressure at the meter is wrong what action would you take? And what would cause it? Thankyou.

    • @tomkatgastraining
      @tomkatgastraining  3 ปีที่แล้ว +1

      You would get in touch with Cadent because it could be poor gas pressure or broken regulator

  • @eazyrat
    @eazyrat ปีที่แล้ว

    Thanks. Why is it the case a drop is allowed with existing appliances connected? I may be completely stupid, but a drop is a drop no? Gas is escaping. Isn't that a problem? The wording the books and everyone uses seems to confuse things. Plenty of engineers seem to think if there is a drop on an existing system with old appliances and its within range then that's ok. Even the books don't explicitly make it clear that if you test with appliances on you have to ensure the the drop is on the appliance by isolating the appliance. The books split criteria for pipework into new and existing when really they should just say no drop is allowed and if you find one you have to ensure it's on the appliances.

  • @monikanader9454
    @monikanader9454 3 ปีที่แล้ว +1

    Great video, thank you 👍

  • @ianbrown4939
    @ianbrown4939 3 ปีที่แล้ว

    GREAT STUFF DEREK THANKS

  • @Burncash1510
    @Burncash1510 3 ปีที่แล้ว

    Derek your a legend keep the vids coming!

  • @vladimirstafasani4630
    @vladimirstafasani4630 3 ปีที่แล้ว

    Good video well done 👍
    What is the difference between working pressure and operating pressure?

    • @tomkatgastraining
      @tomkatgastraining  3 ปีที่แล้ว +1

      Nothing they are the same thing 👍🏻

    • @vladimirstafasani4630
      @vladimirstafasani4630 3 ปีที่แล้ว +1

      @@tomkatgastraining thank you that’s what I thought just wanted second opinion 👍

  • @richardhodgson7443
    @richardhodgson7443 3 ปีที่แล้ว

    Thanks again, great video. For operating pressure at meter, would you put all appliances on maximum at same time if you have more than one in property, say a boiler and cooker. Or just one appliance at a time? Thanks

    • @tomkatgastraining
      @tomkatgastraining  3 ปีที่แล้ว +2

      All will be reviled on Wednesday in part 2 😁👍🏻

    • @raul835
      @raul835 3 ปีที่แล้ว +1

      @@tomkatgastraining bring it on

  • @hosseinkarimzadeh3085
    @hosseinkarimzadeh3085 3 ปีที่แล้ว

    thanks for good explin and show how to do test working test and standing test

  • @salcarlito5319
    @salcarlito5319 2 ปีที่แล้ว

    @Derek, in Gas college they always told us the first thing you do before testing is using a volt stick on the meter on the anaconda I believe. no gas engineer ever does it though lol, do they have a point? is it uk reg? I think one in a million engineers got shocked or something one day

    • @tomkatgastraining
      @tomkatgastraining  2 ปีที่แล้ว +1

      Yep they are correct it’s not law but is best practice it’s for your own safety

    • @salcarlito5319
      @salcarlito5319 2 ปีที่แล้ว

      Yeah, it’s probably best practice but your video is to show us how do the tightness test and it is very informative, thanks for your videos, you’re doing great work.

  • @willlomas2725
    @willlomas2725 2 ปีที่แล้ว

    Thank you Derek.

  • @abcd-by6rw
    @abcd-by6rw ปีที่แล้ว

    Question, when you are performing the pressure test on the ECV, how do you know that it is the ECV that is at fault and not another part in the system?

    • @abcd-by6rw
      @abcd-by6rw ปีที่แล้ว

      ps thank you for video!

  • @nazirmohammed7285
    @nazirmohammed7285 3 ปีที่แล้ว

    Excellent video 5*

  • @Benji-gq9gx
    @Benji-gq9gx 2 หลายเดือนก่อน

    Im an apprentice but boss said that you can have good pressure at the boiler(call it 19mb) but still low gas rate when gas rating a boiler(seeing how much gas the boiler uses on max rate over a certain time). So gas pressure doesn't necessarily change if the gas rate does?
    I understand if you add up the amount of gas passed through the meter over a set time, whilst the boiler is on maximum, this will give you the gas rate? If thats correct does that mean if the gas rating came out lower than should be, that it could be inadequate gas reaching the appliance because of incorrect pipework sizing? Or it could be a boiler fault or fluing issue? But you could find this out by taking gas pressure at the boiler and if thats no lower than 18mb it would show that the boiler or fluing is at fault not the pipework?

    • @tomkatgastraining
      @tomkatgastraining  2 หลายเดือนก่อน

      @@Benji-gq9gx gas rates on boilers change with modulation and so does the inlet pressure and as long as you have less than a 1 mbr drop between working at the meter and inlet at the appliance and FGA is within tolerance and manufacturer instructions you could deem it safe

    • @Benji-gq9gx
      @Benji-gq9gx 2 หลายเดือนก่อน

      @@tomkatgastraining I'm still confused. 21 plus or minus 2 at the meter. So lowest allowed is 19 at meter. Then your allowed 1mb drop at the appliance. So this means the inlet pressure at boiler should never be lower than 18?
      However some boiler manufacturers say their boilers can be lower

    • @tomkatgastraining
      @tomkatgastraining  2 หลายเดือนก่อน

      @@Benji-gq9gx the lowest working pressure at the meter is 18.5 mbrs now if you suspect low incoming pressure. Even though the manufacturers say their boilers can work at lower pressures it will be at the gas valve p1 not at the inlet test point of the gas isolation valve

    • @Benji-gq9gx
      @Benji-gq9gx 2 หลายเดือนก่อน

      @@tomkatgastraining you mean the lower pressure will be at the gas valve inside the boiler not the isolation that often has a test point just underneath the boiler?

    • @tomkatgastraining
      @tomkatgastraining  2 หลายเดือนก่อน +1

      @@Benji-gq9gx correct

  • @Benji-gq9gx
    @Benji-gq9gx 8 หลายเดือนก่อน

    So can i clarify pls. Working pressure/operating pressure is taken at the actual appliance and also the meter and allowed a drop of 1mb?
    Also what is the difference between a let by test and standing pressure? Surely in a letby your testing the section of pipe all the way from the ECV and throughout all the pipework up until the appliances in the house(so just the pipework in system with all appliances off).surely this area being tested is exactly the same in the letby and the standing pressure test?

    • @UndisputableFact
      @UndisputableFact 4 หลายเดือนก่อน

      let by test is testing the ECV to ensure it's working correctly when closed and isn't letting gas past it.
      Temperature stabilisation allows the gas pressure to stabilise before the tightness test.
      Tightness test is a test to ensure that there is no escape of gas from the installation downstream of the ECV and the installation is gas tight.
      Standing pressure test is to see what the standing pressure of the installation is and indicates whether or not the meter regulator is working.
      Working pressure, now renamed as Operating Pressure, is done both at the meter, and then at the appliance, to ensure that there is not more than 1mbar of pressure drop between the two when the appliance is running at full capacity (the exception being a cooker hob).
      working/ operating pressure is the same thing.

    • @Benji-gq9gx
      @Benji-gq9gx 4 หลายเดือนก่อน

      @@UndisputableFact surely standing pressure would/should be the same at the meter as at an appliance? If gas has nowhere to go because no leaks and no appliances are running then surely the pressure would be evenly distributed throughout pipework?

    • @UndisputableFact
      @UndisputableFact 4 หลายเดือนก่อน +1

      @@Benji-gq9gx yes standing pressure will be the same everywhere in the installation while no appliances are running.

    • @Benji-gq9gx
      @Benji-gq9gx 4 หลายเดือนก่อน

      @@UndisputableFact thanks

  • @ek6868
    @ek6868 3 ปีที่แล้ว +1

    Tanx for the upload plz if you could can you do fault finding on combi boilers,tanx

    • @tomkatgastraining
      @tomkatgastraining  3 ปีที่แล้ว

      Take a look at my videos called inside a boiler case they show lots of of information on fault finding

    • @ek6868
      @ek6868 3 ปีที่แล้ว +1

      @@tomkatgastraining tanx topman tamkat👍

  • @Ivan.Atanasov.
    @Ivan.Atanasov. 2 ปีที่แล้ว

    Derek, I have the following question: if I have a let by 5mbar/min and leak of 5mbar/min (for example) would I ever find out and how?

    • @tomkatgastraining
      @tomkatgastraining  2 ปีที่แล้ว +1

      Well that would be very unlikely and very unlucky if you did. I would expect a report smell of gas if you had a 5 mbar drop.

  • @lostinthoughtscalminsilenc8167
    @lostinthoughtscalminsilenc8167 3 ปีที่แล้ว +1

    Do you do standing pressure then working inlet and burner (if not zero gov)
    Just because I’ve seen another TH-camr day do working then standing

    • @tomkatgastraining
      @tomkatgastraining  3 ปีที่แล้ว +1

      You can do it in any order you like because each test isn’t affected by the others.

    • @lostinthoughtscalminsilenc8167
      @lostinthoughtscalminsilenc8167 3 ปีที่แล้ว

      @@tomkatgastraining thanks for reply

    • @lostinthoughtscalminsilenc8167
      @lostinthoughtscalminsilenc8167 3 ปีที่แล้ว

      Have you covered any chimney/flue vids?

    • @tomkatgastraining
      @tomkatgastraining  3 ปีที่แล้ว +1

      @@lostinthoughtscalminsilenc8167 th-cam.com/video/jE3XUmpJVzo/w-d-xo.html that’s part 1 of 2

    • @lostinthoughtscalminsilenc8167
      @lostinthoughtscalminsilenc8167 3 ปีที่แล้ว

      @@tomkatgastraining any idea when you’ll do part 2. Your videos are my go to for revision as you explain really well

  • @1414141x
    @1414141x 2 ปีที่แล้ว +1

    I don't understand why they say add the two (water gauge) readings together and divide by 2. As long as you have zero'd the meter prior to any test the readings will be identical on either side - so you can just go off the positive side on the LHS. Just seems to be complicating matters. They should state you always zero the meter prior to any test ! I think its just making it confusing by adding the extra arithetic....

  • @chuck22uk
    @chuck22uk 10 หลายเดือนก่อน

    Thankyou Derek

  • @abchannel3737
    @abchannel3737 3 ปีที่แล้ว

    Excellent 🌹

  • @rayhurrell1722
    @rayhurrell1722 3 ปีที่แล้ว +1

    Ray Hurrell brilliant

  • @basharedais100
    @basharedais100 ปีที่แล้ว

    You the man bro..👍

  • @eazyrat
    @eazyrat 2 ปีที่แล้ว

    thanks. if you zero the u gauge then wouldn't the readings always be the same either side? what's the point in doing the calculation of bother sides ÷2 if both sides are the same?

    • @tomkatgastraining
      @tomkatgastraining  2 ปีที่แล้ว +1

      If you have ever done it you will find it normal for them to have different readings

  • @waerdie2
    @waerdie2 9 หลายเดือนก่อน

    If a six ring cooker do you put on 5 rings to get operating pressure

  • @aaronjoyce1980
    @aaronjoyce1980 3 ปีที่แล้ว

    Great vid again Derek 👍 Aaron j trainee 😁

  • @RandomAsh71
    @RandomAsh71 2 ปีที่แล้ว

    Are you allowed to leave the u gauge attached to the meter unattended when you go and start up the boiler to check working pressure?

    • @tomkatgastraining
      @tomkatgastraining  2 ปีที่แล้ว

      As long as it is stable and not going to fall over yes you are

  • @lostinthoughtscalminsilenc8167
    @lostinthoughtscalminsilenc8167 3 ปีที่แล้ว +1

    When doing working pressure do turn all appliances on? Or is that on if when testing inlet?

    • @tomkatgastraining
      @tomkatgastraining  3 ปีที่แล้ว +1

      You have to have a minimum flow rate through the meter of 0.5m3 to a maximum of 3.5m3 for working at the meter but at the appliance it’s just that appliance running

    • @lostinthoughtscalminsilenc8167
      @lostinthoughtscalminsilenc8167 3 ปีที่แล้ว

      @@tomkatgastraining so only test working pressure with each appliance on highest setting?

    • @tomkatgastraining
      @tomkatgastraining  3 ปีที่แล้ว

      @@lostinthoughtscalminsilenc8167 working pressure at the meter can be done with all appliances running as long as it doesn’t exceed the maximum flow rate or just one as long as it’s not less than the minimum

    • @lostinthoughtscalminsilenc8167
      @lostinthoughtscalminsilenc8167 3 ปีที่แล้ว

      @@tomkatgastraining okay great thanks

  • @kasimrehman2918
    @kasimrehman2918 3 ปีที่แล้ว

    Hi, when doing working pressure for the cooker, wouldnt you need to put the oven on full rate also?

  • @AhmedAhmed-zj4zd
    @AhmedAhmed-zj4zd 3 ปีที่แล้ว

    Thanks a lot darek

  • @Chatterisdotbiz
    @Chatterisdotbiz 3 ปีที่แล้ว

    I’m just an interested viewer, ( ex industrial process operator) regarding the U tube manometer, when would their be an occasion when one side scale reading be a different reading than the other side ?

    • @tomkatgastraining
      @tomkatgastraining  3 ปีที่แล้ว +1

      When it hasn’t been zeroed correctly or not level

  • @samir0007085
    @samir0007085 3 ปีที่แล้ว

    Many thanks
    It’s for me I have requested Sir thanks

  • @mattl9702
    @mattl9702 3 ปีที่แล้ว

    Why test the standing pressure and is there actually a requirement to do so?
    Please let me know if I’m wrong, but I was always under the impression the meter governor operated whilst gas was flowing through it-not whilst standing.

    • @tomkatgastraining
      @tomkatgastraining  3 ปีที่แล้ว

      The standing pressure is a test to prove the regulator is working and how much gas you have. It’s one of those tests gas engineers don’t do because they think it’s not necessary. All the tests are there for engineers to determine if the installation is safe so if an engineer thinks there are no problems with the incoming supply then no need to do standing pressure.

    • @mattl9702
      @mattl9702 3 ปีที่แล้ว

      @@tomkatgastraining thanks for your response.
      I thought “operating” (working) pressure is the test that proves the regulator is working correctly? Not the standing pressure. I’m sure the regulator only “regulates” when gas is flowing through it not whilst “standing”?

    • @tomkatgastraining
      @tomkatgastraining  3 ปีที่แล้ว

      @@mattl9702 because you can have up to 75 mbrs on low pressure and up to 2 bar on medium pressure the standing pressure shows you if the regulator is regulating it down when the appliances are not running. It also shows when you have low incoming pressure.

    • @mattl9702
      @mattl9702 3 ปีที่แล้ว

      @@tomkatgastraining So the regulator reduces pressure from ~75mbar to what pressure? Not trying to be a clever clogs, I’m curious.
      The reason I ask-I once got into a big debate with Transco years ago over the same subject. I was arguing the “standing pressure” seemed too high on a domestic property. To cut a long story short they disagreed and told me the working pressure was fine therefore all was ok. I’ve never tested the standing pressure since-that was roughly 20 years ago!

    • @tomkatgastraining
      @tomkatgastraining  3 ปีที่แล้ว +1

      @@mattl9702 the regulator has 2 tests to see if it’s working which as you know are standing and working pressure. You can get a regulator working at 23 mbrs but if you leave it when the appliances are off it could rise to over 30 mbrs if the regulator is passing. As you know most gas engineers don’t care about standing and working pressure at the meter but as a trainer I have to show my trainees the correct procedures for testing safety devices and with a regulator being also classed as a safety device I have to show the correct testing methods.

  • @sarbjitkahlon903
    @sarbjitkahlon903 3 ปีที่แล้ว

    Hello sir I have one question....,,
    There is a imperial meter ,but can find type on it what means that ????
    Is it G4 u6 E6 what type of meter is it ??

    • @tomkatgastraining
      @tomkatgastraining  3 ปีที่แล้ว

      Yes the number is the type of meter the imperial is a u6 meter or a u16

  • @AnEyeScream
    @AnEyeScream 2 ปีที่แล้ว

    Thank you, Nikola Ditsov

  • @hosseinkarimzadeh3085
    @hosseinkarimzadeh3085 3 ปีที่แล้ว

    If you can tell if the boiler is work how much i have read gas in gage that mean drop thanks

  • @jugbirsingh6999
    @jugbirsingh6999 3 ปีที่แล้ว

    Thanks on to part 2 now

  • @4157longb
    @4157longb 2 ปีที่แล้ว

    If there’s excessive gas pressure at the appliance what impact would this have?

    • @tomkatgastraining
      @tomkatgastraining  2 ปีที่แล้ว

      The only way you can get excessive pressure at an appliance is when the meter regulator has failed and this could lead to an ID situation.

  • @lostinthoughtscalminsilenc8167
    @lostinthoughtscalminsilenc8167 2 ปีที่แล้ว

    Hi mate, when doing inlet at boiler and combustion. If I’m using a fga can I use them at the same time? Would I just isolate the gas put my probe in and attach my hose to inlet then put boiler to max and turn gas back on?

    • @tomkatgastraining
      @tomkatgastraining  2 ปีที่แล้ว

      Not really sure what you are asking but inlet pressure is done with heating and hot water not high and low. High and low rates are for fga unless the boiler manufacturers say so

    • @lostinthoughtscalminsilenc8167
      @lostinthoughtscalminsilenc8167 2 ปีที่แล้ว

      @@tomkatgastraining so you’re saying when doing inlet it does not need to be on high?
      My boss does them both at the same time? So I was just asking how I could do that? Would I just isolate gas put hose on inlet and probe in flue and put to full rate? As I use fga as a pressure guage

    • @tomkatgastraining
      @tomkatgastraining  2 ปีที่แล้ว

      @@lostinthoughtscalminsilenc8167 depends on the equipment you use. I just do them separately

    • @lostinthoughtscalminsilenc8167
      @lostinthoughtscalminsilenc8167 2 ปีที่แล้ว

      @@tomkatgastraining okay np, but when you do inlet you isolate gas first right?
      Is it bad if I can’t find where inlet is I don’t isolate the inlet so I can’t find where gas is coming out of then I isolate and put hose on?

    • @lostinthoughtscalminsilenc8167
      @lostinthoughtscalminsilenc8167 2 ปีที่แล้ว

      If not how else can you find where it is? 🤣

  • @-V-K-
    @-V-K- 3 ปีที่แล้ว

    How can you have 23 mb (standing P) when the regulator is set to cut off at 21 mb ?

  • @MSKChess
    @MSKChess 3 ปีที่แล้ว

    what is the lowest working pressure you can have at meter outlet at peak demand?

    • @tomkatgastraining
      @tomkatgastraining  3 ปีที่แล้ว

      It’s shouldn’t go below 19mbrs but Cadent engineers are told it can go as low as 15mbrs if the safe operation of the appliances are not affected in peak demand

    • @MSKChess
      @MSKChess 3 ปีที่แล้ว

      @@tomkatgastraining Yes because there is an allowable 4mb drop across the meter installation at peak demand (BS 6400-1 6.2 for pressure absorption) which means that conceivably you might have something as low as 14mb inlet working pressure at the appliance, crazee! :D

    • @tomkatgastraining
      @tomkatgastraining  3 ปีที่แล้ว

      @@MSKChess it dose say 15 Mbrs as minimum is 19 mbrs minus 4 is 15 working at the meter but also says this would only happen if pipe work is undersized for the appliance but like you say crazy 👍🏻

    • @MSKChess
      @MSKChess 3 ปีที่แล้ว

      @@tomkatgastraining yeah in the notes it assumes one millibar drop for pipework, so four for the meter and one for the pipework giving 14 millibar at the appliance inlet. Maybe a Vokera I think can safely run as low as 14mb, but those big Worcester boilers require at least 18mb according to MI's. XD

    • @MSKChess
      @MSKChess 3 ปีที่แล้ว

      btw I know you guys are a training establishment but do you do breakdowns? some vids on fault finding would be awesome, your fan MSK XD

  • @chrisjones4500
    @chrisjones4500 2 ปีที่แล้ว

    👍👍

  • @stephp2751
    @stephp2751 3 ปีที่แล้ว

    differential manemometer or u guage but?? do you know the difference?

    • @tomkatgastraining
      @tomkatgastraining  3 ปีที่แล้ว

      I know the difference but can you spell it. What are you getting at I have no clue what you are on about 🙄

  • @manjsingh6500
    @manjsingh6500 3 ปีที่แล้ว

    Thanks.

  • @arturprzybyl5147
    @arturprzybyl5147 2 ปีที่แล้ว

    Thanks

  • @mohammednazir8307
    @mohammednazir8307 3 ปีที่แล้ว

    Thanks you 🙂

  • @plumbertime
    @plumbertime 3 ปีที่แล้ว

    I think they should just get rid of allowable drops on domestic as once you disconnected everything and see the hobs leaking 3mb who really re connects it and what customers ever say ok Hob leaks gas but it’s fine!

    • @MSKChess
      @MSKChess 3 ปีที่แล้ว +1

      if you have proven that the leak is not on the pipework and the appliance is correctly sited and the room is adequately ventilated and there is no smell of gas then it should never reach a point where you have an immediately dangerous situation as there will never be an explosive mixture, some companies do have a zero tolerance approach to any gas leak regardless if its on an appliance. What gas engineer is going to feel good about leaving a 3mb drop on an appliance, hardly any, but British standards allow for it.

  • @yassheatingservice8035
    @yassheatingservice8035 7 หลายเดือนก่อน

  • @bilalm18
    @bilalm18 2 ปีที่แล้ว

    👍🏼

  • @suewarrington8155
    @suewarrington8155 2 ปีที่แล้ว

    👍 Sue Warrington

  • @mgbroadsterJ
    @mgbroadsterJ 2 ปีที่แล้ว

    I wouldn't trust those volt sticks. I'm finding it difficult to find a quality one which works below 50 volts .

  • @aliebrahimi974
    @aliebrahimi974 2 ปีที่แล้ว

    Ali 👌👌👍👍

  • @olitonottero7620
    @olitonottero7620 ปีที่แล้ว

    17:40 A gas flow rate of 3.5 m3/h should give you (3.5/0.095=36.8) 36.8 kW.
    A minimum gas flow rate of 0.5 m3/h should give you (0.5/0.095=5.3 ) 5.3 kW.

  • @carsonwilliams6319
    @carsonwilliams6319 3 ปีที่แล้ว

    👏🏻✅

  • @robertmoughtin6421
    @robertmoughtin6421 3 ปีที่แล้ว

    I also have no clue why they keep changing the standards

  • @M20DAN
    @M20DAN 3 ปีที่แล้ว

    Tomkat 👍🏻

  • @olitonottero7620
    @olitonottero7620 ปีที่แล้ว

    17:55 MOP: meter operating pressure

  • @christanker4635
    @christanker4635 3 ปีที่แล้ว

    Chris tanker 👍

  • @SuperWayneyb
    @SuperWayneyb 3 ปีที่แล้ว

    👍🤓👍

  • @M20DAN
    @M20DAN 2 ปีที่แล้ว

    tomkat👍