Great explanation sir.. But I think the O2 increases when we go through backward derection of flue gas. I.e O2 at Eco outlet area should greater than O2 at Eco inlet area.
Sir,, I'm in NTPC as Diploma apprentice trainee. Your vedios are really helpful for me to understand all equipment that i see on site. Like deairator, O² analyser Esp much more.. Senior manager DGM AGM are very cooperative,, They teach me and made my understanding on site.. 😊🙏🇮🇳
You are so lucky dear, this type of opportunity comes in your life, don't waste this a single minute of time & learn more about power plant by senior sir, and try to share your knowledge also who is Lerner.
Sir plz make a video on clinker formation low temperature and high temperature both also explain different condition of clinker formation mention how to over come or precaution during during start up,if any equipment fail during operation like Id , fd, hotbox or during running operation
Sir agar APH leakage hua to cool air tube k andar chle jayega jisse O2 analyser to oxygen % kam dhikhana chahiye but ap bol rhe h ki oxygen 8% show karega ye samaj ni aya
Dear Sir You said in furnace temperature was 500to 550 approx then how sulphur content remains outside the furnace I think all sulphur combustion process already done in furnace I am working in 600 MW pf boiler temperature approx 1200 C then please clear me how sulphur skip the combustion process
Due to Acid due point, sulphuric acid start condensing at below 120°C and deposited on Boiler part, due to acidic in nature corrosion formation on Boiler part ultimately damage the part, on this topic video is ready very soon I'll upload this video. Thanks dear
Which fuel used, if their ignition temperature below this value then no problems, but if coal fuel it's always installed between Economiser and Air Preheater.
Hello sir ji yadi O2 Analyser 3 gala denge yek Economiser air APH ke bich air economiser ke pahle air tisara APH ke bad to kisme kitna dikhayega air kyo kam jyada dikhayega APH leakese nahi h phir bhi kyo kam jyda dikhayega
Bahut best
Hum aapki puri video dekhunga
Bahut hi knowledgeable video hoti hai...
Thanks a lot
More valuable information in this channel. Thanks
Thank you so much❤
Informative channel.
Thanks❤
For operation and efficiency engineer, this video is very important.
Very good answer
Thanks a lot
Sir mashallah... superb... awesome...
Thanks a lot dear
Really informative lacture bhiya
Thanks dear
Kuch naya sikhne ke liye mila
Thanks ☺️
Chandan ji good
Thank you so much
Very very best sir
Thanks a lot dear
Informative lecture..... Thank you Sir.....
Thanks dear
Love your videos👍👍
Thanks a lot ♥️
Realy big fan of you your way of teaching is so simply awsome❤
Thanks bro
Very informative video Sir...
Thanks 🙏😊
Most welcome dear ♥️
Very Informative Video
Keep it Up Sir🙏👍
Thanks a lot dear ♥️
Thank you, Valuable information sir ji...
Thank you so much dear
Just amazing.... Great teacher
mst video sir.
Thanks a lot dear
Doing an awesome job, pathakji
Thank you so much
Great
Thanks for this kindness
Most welcome
ThanQ sir,,, u are the master...
Most welcome dear ♥️
Excellent explanation👌👌👌👌👏👍👍
Thank u so much 👌 for valueable information. 🙏
Most welcome❤
Thank you sir ji 😍😘
Most welcome dear
Very nice information vedio
Thanks
Very useful information
Excellent
Nice video sir
Thanks a lot dear
Very good
Thank you
Sir keep doing informative video
Thank you
Very Very thanx sir
Most welcome dear
Great explanation sir.. But I think the O2 increases when we go through backward derection of flue gas. I.e O2 at Eco outlet area should greater than O2 at Eco inlet area.
Thanks dear
I got the same doubt here ..
Very well explained
Thanks
Thenks
Most welcome
Best information sir
Sir,,
I'm in NTPC as Diploma apprentice trainee.
Your vedios are really helpful for me to understand all equipment that i see on site.
Like deairator,
O² analyser
Esp much more..
Senior manager
DGM
AGM are very cooperative,,
They teach me and made my understanding on site..
😊🙏🇮🇳
You are so lucky dear, this type of opportunity comes in your life, don't waste this a single minute of time & learn more about power plant by senior sir, and try to share your knowledge also who is Lerner.
Excellent video
Good knowledge
Thank you so much sir 🤗🙏
Most welcome dear
Very good, sandar
Thanks a lot
Super sir g
Thanks a lot dear
Sir.. Insulation kei upar video banaiye.......
Bahut jald hi bna dunga dear is topic pr, av pahle Ka kuch commented video h m sbka comments pr work krunga, please wait for the video.
Thanks
Great sir 💐
Nice bro
Thanks a lot
Super sir
Thanks dear
Sir plz make a video on clinker formation low temperature and high temperature both also explain different condition of clinker formation mention how to over come or precaution during during start up,if any equipment fail during operation like Id , fd, hotbox or during running operation
Sure dear, very soon m trying to provide video on this topic.
Yes sir pls make videos on aforesaid subject clinker formation and emergencey situations
5⅝
Thank you sir
Most welcome dear
But sir Hamare plant ka APH lnlet fue gas temperature is 315'c .. Us temperature pe to sulfur combustion hoga .. to kya O2 galat so karegaa....
150 MW
Superb sir....
DM plant ke liye ek video banaeye..full details..
I have already uploaded please check my playlists of DMP
Very good sir
Please define ash handling system and make video
Please check my playlist I have already uploaded on AHS.
Very informative video sir. Can you please provide video on FD ID and PA fan air capacity's or requirement.. Really Thank you for this Video.
Most welcome dear 🙂
M trying to provide video on your desired topic as soon as possible.
🎉 good
Why in afbc boiler adjacent compartment has pressure difference??
Very
Nice sir
Thanks dear
Thank you sir 🙏
Clinker prevent ke bare me video banaiye
Sir O2 analyser calibration video plz sir
Sure dear I'll make
Nice
Thanks a lot
Sir agar APH leakage hua to cool air tube k andar chle jayega jisse O2 analyser to oxygen % kam dhikhana chahiye but ap bol rhe h ki oxygen 8% show karega ye samaj ni aya
Please make a video on quantity of conveying air required for Ash conveying
Dearetor pe video banao, sir
Dear please check my playlist I have already uploaded video on deaerator
Dear sir please make a vedio on excess air calculation
Sure dear very soon I'll upload this video
Best video
Dear Sir
You said in furnace temperature was 500to 550 approx then how sulphur content remains outside the furnace I think all sulphur combustion process already done in furnace
I am working in 600 MW pf boiler temperature approx 1200 C then please clear me how sulphur skip the combustion process
Sir boiler drum level 50 kyu rkha jtahi
Sir please make a Video of Combined Cycle power plant complete process
Sir feed pump ecnomiser ke inlet me rahta ki outlet me .
Thanks 👍👍👍 sir boiler ka heating surface area ka formula and calculation chahiye
Sir why v ave to maintain 140deg at aph outlet...y not less than that ...plz reply..
Due to Acid due point, sulphuric acid start condensing at below 120°C and deposited on Boiler part, due to acidic in nature corrosion formation on Boiler part ultimately damage the part, on this topic video is ready very soon I'll upload this video.
Thanks dear
@@PowerPlantDiscussion thanks a lot sir, v r getting lot of information ..
Thanks sir
Eco outlet temp. Will be 300 to 340C
In power plant, So Sulphur react with Oxygen so it form SOx. So your information is partially correct.
So always oxygen reacts with sulphur
If Oxygen not react with sulfur then no point of SOx in flue gas,No environment pollution, FGD also not required in power plant.
Pls make video on both APH difference
Sir stackmonitoring keliye thoda video banaye ji
Sure dear I'll make
Sir can you plz make video on clinker formation reason in superheater zone of boiler and how to avoid it. I am working on baggas fired boiler
Sure dear I'll make video on this topic
Please make video of how to find excess air from co2 and how to find excess air f
Sir O2 analyzer ka calibration ka video bnaiye plz ki calibration k se kiya jata.
Sure dear I'll make
Good info.sir.This theory is apply on baggase fired boiler or not
Of course dear this theory may be applied for every boiler.
Sir our boiler anylizer installed before economizer (boiler outlet) its wrong or right and temp of flue gas in outlet 300-+50 degree.please ans
Which fuel used, if their ignition temperature below this value then no problems, but if coal fuel it's always installed between Economiser and Air Preheater.
Baggase
Please reply
Sir ji pressure design kya hota hai iske bare mein bataiye
how to prepare for boy exam and is there any book for that which can be done terry plz tell you
Thanks
Most welcome
Sir g hamare yaha gas fired boiler hain lekin ID fan nahi hain 163tph ka boiler h or O2 JUST BOILER FLUE OUTLET ME HAIN KIYA YE SAHI HAIN?
Oha temperature Kitna show krta h
Low pressure boiler me o2 analyser lagana hai to kaha par lagayenge sir ji
It's my humble request to you sir, which valve using after boiler and before turbine
Include MCV AND MSV VALVE
After Boiler main steam stop valve MSSV use krte h, before turbine Emergency stop valve ESV use krte h, jitna q smjh paya hu
Gate valve
MS VALVE motorised hota he
ESV valve hydraulic hota he.... Hydraulic pressure 150 tak hota he
what about rotary type APH in this case
Bolier hydraulic testing ka video banaiye details me
Sure I'll make
1 ton caol ka complete combination krne ke liye kitni air ki requirement hoti h. kaishe calculate krte h
th-cam.com/video/3tw3qYvOUZ4/w-d-xo.html
Sir 1 mujy builer ki capesti sy all seting ka formula btaye
But sir agar tube economizer की agar liake होती है to to क्या effect होगा?
Kindly make video on how to calculate excess air from CO2 and O2 ?
I have already uploaded search this topic by power plant discussion.
Sir hamera boiler 130 tph hai aur usme o2 analyser economiser ke inlet par hai why
Which fuel using and temperature of exact point
@@PowerPlantDiscussion petcock steam coal indian coal husk
105 working pressure and 505 steam temperature
Indian coal? Economiser Inlet temperature Kitna rhta h jaha O2 Analyser lga h
@@PowerPlantDiscussion 345 inlet 245 outlet
Hello sir ji yadi O2 Analyser 3 gala denge yek Economiser air APH ke bich air economiser ke pahle air tisara APH ke bad to kisme kitna dikhayega air kyo kam jyada dikhayega APH leakese nahi h phir bhi kyo kam jyda dikhayega
Yes bhayya I need to know that how to find excess air from co2
Yes co2, o2 from excess air provide vedio
I have already uploaded please check my playlist
O2 analyser farnes me kyo nahi lagate h yadi lagate h to kya problem hoga
Pls sir make video on how to find out boiler excess air.
Dear I have already uploaded on this topic please check my playlists of power plant operation
Coal Feeding main steam pressure ke upper set karte hai not on oxygen
Ok