HVAC Emergency Service Call: York RTU No Heat (Commercial Packaged RoofTop Unit) Furnace Not Heating

แชร์
ฝัง
  • เผยแพร่เมื่อ 3 ม.ค. 2025

ความคิดเห็น •

  • @ricecity7601
    @ricecity7601 2 ปีที่แล้ว +22

    *Used to supplement the up stairs when it gets hot outside this works very well and **Fastly.Cool** Also works good when the upstairs gets too hot in the Winter from the heater.*

  • @joshuaricks7730
    @joshuaricks7730 3 ปีที่แล้ว +20

    Brother whenever you got a situation like that, always take a look at the heat exchanger. If you have a rust spot on it with a hole it can cause roll out.

    • @Jason-wc3fh
      @Jason-wc3fh ปีที่แล้ว +1

      Yes. Examine the flame carefully before the blower motor starts and compare any changes in how the flame responds. Also take off the back panel to examine the heat exchanger for any cracks. There's also no way a roll out would be bad enough to get to that relay to melt it. There would be many other major signs of heat damage. The relay failed from bad connections that created excessive heat from the current of the inducer fan

  • @hvacrnortheastern2110
    @hvacrnortheastern2110 3 ปีที่แล้ว +6

    You go ask yourself why the rollout switch was jump out could be heat exchanger has a cracked l would pull off the panels for the heat exchanger very important .I would check it and monitor the flame to see if there and wave when the blower comes on if everything checks ok get a new roll switch it's going to fail and your going be up there in the middle of the winter. Great video .

    • @drewc7479
      @drewc7479 3 ปีที่แล้ว +1

      Gas pressure too had a call last week unit tripping on rollout ended up checking it fire at 4in WC I set it down to 3.3 but overfiring did its damage to the heat exchanger

    • @mason122122goodman
      @mason122122goodman 3 ปีที่แล้ว +2

      Missed a lot of things. Didn’t amp inducer motor to find out why the relay burnt up. Didn’t check gas pressure, temp rise blower amps or even the heat exchanger. Could’ve been over firing or heat exchanger is rusted out but didn’t check.

  • @hvacir9176
    @hvacir9176 ปีที่แล้ว +3

    Good luck changing heat exchanger on york RTU

  • @Livingcomfortinc
    @Livingcomfortinc 3 ปีที่แล้ว +2

    It’s the best feeling in the world when you get them going !

  • @derrickgarcia303
    @derrickgarcia303 3 ปีที่แล้ว +10

    Best practice to shut gas off rather than DC when on heating mode. Shutting the gas off allows the indoor fan to continue to run to cool the heat exchanger to prevent warping and stressing it. Grab that remote and crack one open😁

  • @johnnyb8629
    @johnnyb8629 3 ปีที่แล้ว +5

    I see a rollout jumped the first thing i do is visually check the heat exchanger. I do that before putting any new parts on the unit.

  • @jrh86
    @jrh86 9 หลายเดือนก่อน

    Brilliant as always

  • @chrisvas8743
    @chrisvas8743 3 ปีที่แล้ว +7

    Why didn’t you check the heat exchanger

    • @yzy17
      @yzy17 3 ปีที่แล้ว +7

      Mentions the flame may have rolled out and burnt the wiring but doesn’t look into why the flame may have been rolling out. Definite call back here.

    • @johnpadua9115
      @johnpadua9115 3 ปีที่แล้ว +3

      I was just thinking the same thing. Either a bad heat exchanger or a air leak on the sides where the heat exchanger mounts the the unit. So when the blower comes on it hits the flame. .

    • @mason122122goodman
      @mason122122goodman 3 ปีที่แล้ว +3

      Didn’t check heat exchanger. Didn’t amp inducer motor to see why the relay burnt up. Didn’t check gas pressure, temp rise and amp all components. Did all that shit talk about hacks but failed to complete his job to 100%. Big picture

    • @yzy17
      @yzy17 3 ปีที่แล้ว +2

      Normally I don’t care much but he shouldn’t be focusing so much on showing off his tools and how pretty his new part was compared to actually repairing the unit. This isn’t as bad as jumping out a safety, but if you ask me this is just as irresponsible. If that roll out is defective and gets stuck closed with a bad heat exchanger (that he didn’t check), he could be risking everyone in that church’s health.

  • @harneepchahal9626
    @harneepchahal9626 2 ปีที่แล้ว

    Good to see u din't ignored the jumper wire....

  • @Brendan_Clancy
    @Brendan_Clancy 3 ปีที่แล้ว +2

    Probably jumped out the rollout because York is notorious for having sketchy rollouts. A continuity test will show the switch as closed, but there’s enough resistance to interrupt the safety circuit. Every single time I have a York no heat call I replace the rollout

  • @CouchDad09
    @CouchDad09 ปีที่แล้ว +1

    Jumper man finds a jumper on the unit lol

  • @jrh86
    @jrh86 ปีที่แล้ว +1

    Yehh no excuses fof that jumper, we had a guy who we called dangerous Pete as he was suspected of doing just this.

  • @winkhvac62
    @winkhvac62 ปีที่แล้ว +1

    Thanks for the video

    • @JumpermanTech
      @JumpermanTech  ปีที่แล้ว

      You're very welcome & thanks for watching!

  • @jamienegrete2841
    @jamienegrete2841 3 ปีที่แล้ว +2

    Thanks for the video . It’s very helpful. My church currently has not heat on all 4 of the furnaces. I’m about to open it up and take a look. I will follow the order of operation you showed us and check for current . Any way thanks for the videos

  • @TomSanborn-y3n
    @TomSanborn-y3n 13 วันที่ผ่านมา

    If your rollout is jumped or tripped, do you need to always check your heat exchanger your gas pressure on those rooftop units for the York you got the pilot sending tube with a vent at the bottom you need to make sure that’s clear 100% of the time whenever you have a rollout jumped or tripped You need to do a lot more investigating other than removing it and replacing or relay

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC 3 ปีที่แล้ว +3

    You can have continuity across the roll out and it still wouldn't work. High impedance. High resistance = lower voltage

  • @toyinorodare4072
    @toyinorodare4072 3 ปีที่แล้ว +1

    Please Recommend a book to read for Chiller Maintenance and Repair

    • @Brendan_Clancy
      @Brendan_Clancy 3 ปีที่แล้ว

      Check out Herbert Stanford’s book on chillers. One of the best around. Best bet is to get enrolled at JCI chiller class

  • @kiefbox4908
    @kiefbox4908 4 วันที่ผ่านมา

    Why are you all even watching these videos if you will just correct him on everything he does. You know it all. No need to go to youtube and watch hvac videos.

  • @philcantv6011
    @philcantv6011 2 ปีที่แล้ว +1

    thanks for sharing 👍

  • @trae7887
    @trae7887 ปีที่แล้ว +1

    Lol there’s a-lot wrong here but this video is super old,after watching one of his newer videos. He seems a-lot more knowledgeable about hvac and the dangers as a whole. But that flame is definitely bright orange. Which is a big no

  • @izzybell11
    @izzybell11 3 ปีที่แล้ว +6

    Great tutorial. Interesting and helpful video. As always great job JMT. ⭐️⭐️⭐️⭐️⭐️

  • @alexeytech1495
    @alexeytech1495 3 ปีที่แล้ว +1

    Well done 👍 troubleshooting material.

  • @alvarolucio8264
    @alvarolucio8264 9 หลายเดือนก่อน

    Boa Noite estas placas de controle são padrões pra todas as máquinas ou cada uma tem.seu modelo? A parte de aquecimento a gás se precisar fazer brasagem corre risco de explosão?

  • @smittyplugs
    @smittyplugs 3 ปีที่แล้ว +3

    How could you feel good about the service call without checking the heat exchanger????
    They should have called a professional….

  • @garrettfeetham8707
    @garrettfeetham8707 2 ปีที่แล้ว +1

    The roll out could of been jumped because of high resistance but basics teach us the roll out did it’s job and locked the unit out for safety. You should of checked that heat exchanger before you left.

  • @sergioramirez9025
    @sergioramirez9025 ปีที่แล้ว

    Can you do a tutorial of the tools in that bag

  • @cason9573
    @cason9573 ปีที่แล้ว

    I knew what was wrong before I started the video it’s a York!

  • @dyung0007
    @dyung0007 3 ปีที่แล้ว

    I see alot on rtu up here in north Kentucky areas it must York it's heating problem check the exchanger.

  • @dml3883
    @dml3883 2 ปีที่แล้ว

    Out of curiosity why did you not check the heat exchange

  • @kennethlobo4420
    @kennethlobo4420 3 ปีที่แล้ว

    Great video. God Bless. Love ur laughter

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC 3 ปีที่แล้ว

    Looks like that condenser coil had some staining in the lower portion of it at the beginning of the video. Looked like oil staining.

  • @stantheman121352
    @stantheman121352 3 ปีที่แล้ว +1

    Isn't it possible that jumper was left behind on accident

  • @chadazzano7441
    @chadazzano7441 3 ปีที่แล้ว

    So I was sent to replace a heat exchanger , roll out switch , fan limit , high limit , igniter, flam sensor and ignition bored. It’s a York from the 90s. ( I didn’t originally diagnose just doing the hard work for a older tech) . I replaced everything and went to burn off and the inducer runs continuously but no ignition. I’m not getting 24 off the bored to any of the switches. So I switched the bored with an identical unit to see if that’s the problem and it’s not. Unit has no pressure switches. Can someone point me in the right direction? Also what does “ IR” mean on the wiring schematic?

    • @realSamAndrew
      @realSamAndrew 2 ปีที่แล้ว

      It's been a year. Nobody answered. Did you figure it out? Can you share what you found out?

    • @antonalderliesten1421
      @antonalderliesten1421 2 ปีที่แล้ว

      Was the gas off to the unit?

  • @thesilentonevictor
    @thesilentonevictor 3 ปีที่แล้ว

    Great video jmt

  • @migueldominguez4311
    @migueldominguez4311 2 ปีที่แล้ว

    Fantastic!
    Hey jumper man
    Can you do your videos in español??

  • @MC...
    @MC... 3 ปีที่แล้ว +1

    🤘🤘🤘🤘🤘🤘🔥🔥🔥🔥🔥🔥

  • @BarefootBill
    @BarefootBill 4 หลายเดือนก่อน

    I wouldn't want you working on my RTUs.

  • @franz5177
    @franz5177 3 ปีที่แล้ว

    Nc vid

  • @DanielGomez-yz1mw
    @DanielGomez-yz1mw ปีที่แล้ว

    Please visit a barber and do not complain about other people’s work

  • @steveblake8766
    @steveblake8766 3 ปีที่แล้ว

    #173 Thumbs uP

  • @silvioperez4397
    @silvioperez4397 2 ปีที่แล้ว

    Crack heat exchanger 💯