10 Ton Carrier RTU Intermittent Cooling… Almost A Call Back. Good Thing I Waited
ฝัง
- เผยแพร่เมื่อ 4 มี.ค. 2024
- Got a work order for an RTU not cooling normally affects one large room , here’s what I found #hvac #carrier #airconditioning #hvacrepair
- แนวปฏิบัติและการใช้ชีวิต
Man I hate wirenuts, all hail the Wago style connectors
Yep, apparently wire nuts were hard for someone to install correctly here.
Thanks for the video. I know alot of techs that would have packed up early and not stayed to monitor. I'm sitting in a corn field watching a couple wall hangers do their thing, watching yoyr video lol.
Monitored operations ✅ Been bitten a few times. Thanks for watching and commenting 👍
Nicely done! Very helpful. Keep these intermittent troubleshooting videos coming.
More to come! Thanks for viewing
Excellent work Sir. Definitely warm for the start of our week down here. Sweating again in the welding shop .. Cheers
Thanks, it’s starting to fell like FL again
That what experience is all about tech good job
Thanks silentonevictor 👍
Very nicely done. A true professional....not done....until you are done...very detailed and an understanding of operations....bravo buddy
Thanks Jason, appreciate your comments bud 👍
Great Video. Good Job and Nice Work. Thank you for sharing.
Thanks for watching!
Great video Subcool . Hanging barely great catch. I like the low volume guitar riffs in the background in the beginning.
Thanks, I do enjoy some electric guitar with some overdrive gain 🎸
Good catch, it pays to be thorough.
Yes, it did this time
Great troubleshooting!!!
Thanks for watching!
5:12 - Kevin Malone: I always set it to 69°F.
A couple of Wago connectors on the sensor cable would have prevented this problem‼️
Looking at the wire nut while screwing it on would have prevented it too 😀
Nice-
Thanks for watching
Hey guys. Quick question, I just graduated from Brownson in SoCal and I was wondering why the EMS control board needed the control relays at all? Could it not be wired to the RTU’s control board directly? Like a thermostat could be? 😅 I can see the S/S relay for the VFD being its own deal and needs a way to open and close but the other relays? Is that to try and isolate circuits or should I go back to school lol. 😅
Congratulations, good question. The added benefit of those relays are they have an override switch (top right red switch) that the controller doesn’t have
@@subcoolHVAC is that to be able to bypass an individual circuits call and force that load to energize?
Yes, just flip the switch to close the switch.
Rip out BS EMS system and install a normal T.stat
Whoa whoa , what about all the $ they’re saving us ? 🤣 If it was allowed I would
@@subcoolHVACThe sales people convince management they will save a ton of money. Plus it makes jobs for monitoring people. School districts are major customers.
💯
what a horrible device. in germany u CANT build machines like that. u never allowed to sell such a crap. sorry, i have to say, wow
What do they build and sell in Germany ?
Excellent!
Thanks for watching!