2 Bad Compressors In Weeks WHY? Freezer Down

แชร์
ฝัง
  • เผยแพร่เมื่อ 19 ม.ค. 2025

ความคิดเห็น • 155

  • @fshn76
    @fshn76 7 หลายเดือนก่อน +9

    Good video! You weren’t kidding about the problems. Can’t complain about 11° at the end. Probably the best it’s ran in years.

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน +4

      Hard to say. Hopefully it stays running

  • @ErickHernandez93
    @ErickHernandez93 7 หลายเดือนก่อน +5

    Gotta remember if its a freezer superheat is to be checked once box is at least at 0°f brother
    U did all u could man, outstanding 🙌

    • @ErickHernandez93
      @ErickHernandez93 7 หลายเดือนก่อน +2

      You know evap superheat 4-8°f and compressor between 20-30°f is a happy place but its even tolerable up to 48°f is it’s in harsh equipment with neglected maintenance equipment

    • @ErickHernandez93
      @ErickHernandez93 7 หลายเดือนก่อน +2

      As always! Killing Rick! 🙏

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน +1

      I learned not to touch super heat until 5* from set point, or you’ll be doing it again because it will flood when at temp. The one saving Grace was it had liquid injection, but I don’t know if it was even working correctly. It probably was gummed up with shit. I couldn’t feel any temperature changes. I should’ve used my thermal imager, but I was doing a lot of other things that I didn’t show, one of them was the dam bees.

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC 7 หลายเดือนก่อน +5

    Very nicely done Rick.....basically performed a start up type repair. Everything but the kitchen sink.

  • @timbrown9305
    @timbrown9305 6 หลายเดือนก่อน +3

    Very systematic... Nice! Those site glasses bubble on a hot freezer until the freeze gets down to temp and quits boiling all refrigerant too early in the evap. in my experience... superheat is high until then as well for this reason. Love your videos you are definitely a guy who really understands his trade.

    • @HVACRSurvival
      @HVACRSurvival  6 หลายเดือนก่อน +1

      Thanks for the support 👍👍. I agree the superheat is definitely high at pulldown. I don’t adjust superheat until box it at temp. Far as charging I’m not as worried about waiting.

    • @timbrown9305
      @timbrown9305 6 หลายเดือนก่อน +1

      @@HVACRSurvival The company before you wasn't worried about ANYTHING!🤣

  • @elBusDriverKC
    @elBusDriverKC 7 หลายเดือนก่อน +4

    How many hours did this job take? I mostly do commercial rooftop compressor replacements. Between driving to the site, unloading all my equipment, getting in the building, getting to the ladder, climbing the ladder to the roof, hauling all tools to the roof including the new compressor, then doing the compressor job itself can take 8+ hours. Then when you throw in problems like you had in this video, the clock keeps running. I can only imagine this took a few days to get back in working order.

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน +1

      Because I had to come back and this job was over an hour away I had two full days in it. Normally, it would not take that long, but there was way too much moisture to let it go.

    • @ayoutubewatcher7009
      @ayoutubewatcher7009 6 หลายเดือนก่อน +2

      That’s a 3 day job for me

  • @JesseDoesHVAC
    @JesseDoesHVAC 7 หลายเดือนก่อน +5

    So im not the only one! Ive had issues with my 557s not zeroing out pressures leaving like 14psi reading when zeroing pressures lol even the wireless probes have been doing the same thing

  • @frankmesias1949
    @frankmesias1949 7 หลายเดือนก่อน +3

    The way you explain everything.. thank you so much

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน +1

      Thank you, I hope to prevent dumb things like this from happening but that only works if the person wants to learn from there mistakes. This person might never see the video 🤷‍♂️🤔

  • @elparmful
    @elparmful 7 หลายเดือนก่อน +18

    Was that an overnight vacuum?

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน +5

      Yes

    • @Youngbl33zy
      @Youngbl33zy 7 หลายเดือนก่อน +11

      2 day vacuum. Charged the customer 48h x $110h for the vacuum pump working. $5,280 in labor 😛

  • @HVACR559
    @HVACR559 5 หลายเดือนก่อน +2

    APPOIN doesn't sell the CCT/VCRT O-rings outside of getting the VCRT rebuld kit. Wasn't paying that price for a kit I didn't need. Went looking for something else.
    I've been using 'HSN O-Rings, also known as HNBR (Hydrogenated Nitrile Butadiene Rubber)' the green O-rings, for a couple of months now and I'm not going back.
    No need to leave them loose to get the core out, tighten them down normally the O-ring won' get in the way of the core. If you're tip is properly adjusted you will get the core every time. The chemicals don't break them either.
    APPION is still the best. I tried the JB's but the side port didn't work. The FP are way too big. It's bad enough with the APPION VCRT's. DAIKIN you have to un-bolt and bend pipes, LG you have to just about remove the Eletrical box.
    Size #108 Fitts perfectly.

  • @786otto
    @786otto 7 หลายเดือนก่อน +7

    You also have clueless like me watching 😂 Just enjoying how well you can fix things.

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน +2

      I watch things I don’t know about, it’s all good 👍 😊😊

  • @FPHA697
    @FPHA697 7 หลายเดือนก่อน +3

    Great job brother! Do what you can is all you can do!

  • @Ted_E_Bear
    @Ted_E_Bear 7 หลายเดือนก่อน +3

    Rick , I think you are a great tech , so intelligent!

  • @commenter5469
    @commenter5469 7 หลายเดือนก่อน +2

    I work in lots of heavy equipment A/C systems. I use Oil eater to wash the coils ( mostly condensers, but some evap. also) - was thinking about maybe doing experimenting and washing the coils with that on stationary coils, to do less damage. The non bubbling dish detergents might be a good idea also.

  • @marknaravas318
    @marknaravas318 7 หลายเดือนก่อน +5

    Rick, I watch a bunch of these hvac channels and you have the deepest, hardest, most incredibly screwed up stuff to work on. Definitely one of the best techs out there to get this nuclear POS running.

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน +1

      Thanks for the kind words of support 👍👍

  • @commenter5469
    @commenter5469 7 หลายเดือนก่อน +8

    Well Rick - that was super rookie mistake, about that suction filter!
    You knew better!

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน +1

      I didn’t want to heat up the reversing valve.

    • @sherwinalvarez7365
      @sherwinalvarez7365 7 หลายเดือนก่อน +1

      Idk kind of close to the 3way valve

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน +1

      I took the chance, but I cheated and cut it out 🤫😎 a pipe cutter didn’t fit. I keep pipe brushes in my torch kit to clean out shavings if they get in there. At that point they system was a miss what am I out.

    • @commenter5469
      @commenter5469 7 หลายเดือนก่อน +2

      I carry fire blanket with me. Saved me many times. You can even get something like that from Harbor freight welding section. Also I carry old license plates and pieces of aluminum flushing for the same purpose.

  • @user-ge5le4ku6j
    @user-ge5le4ku6j 7 หลายเดือนก่อน +2

    like your workmanship. i miss r11 to flush the system.

  • @halverde6373
    @halverde6373 7 หลายเดือนก่อน +4

    Freezers need suction accumulators.
    I never sold a low temp condenser without one.
    Or a medium temp.
    Guess what, never had a compressor wash itself out.
    That's why you had a lot of oil in the high side too.

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน +3

      I don’t like the whole design. It’s absolutely idiotic to put two different systems on one breaker so when the one system trips, it takes out the other not to mention you tie yourself up with one condenser coil. The whole design is crap.

    • @brnmcc01
      @brnmcc01 7 หลายเดือนก่อน +1

      A lot of oil in the high side can be from the system being low on refrigerant, like when that cap tube line blew, and then the pressure switch set very wrong, the compressor wasn't shutting off. When the compressor is running in a vacuum, and there's not enough gas flow velocity in the low side of the system, there's not enough to push the oil back up from the box up to the roof.

  • @ChuHur
    @ChuHur 5 หลายเดือนก่อน +1

    Wow. What a great teaching video. Great job.

  • @michaelmckenna9022
    @michaelmckenna9022 5 หลายเดือนก่อน +1

    I recently used those apions, they work nice.

  • @LilyRoseElectric
    @LilyRoseElectric 7 หลายเดือนก่อน +1

    Great 🎉job 👏 amazing 👏 craftsmanship ...proud of you

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      Thank you very much!

  • @subcoolHVAC
    @subcoolHVAC 7 หลายเดือนก่อน +1

    11 degrees and out 👍 Thanks for the video!

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      Thanks for watching!

  • @zwspiller7888
    @zwspiller7888 7 หลายเดือนก่อน +1

    Need Mike Rowe for this one! Great video as always Rick!

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      Thank you very much!

  • @duaneimlay5680
    @duaneimlay5680 7 หลายเดือนก่อน +1

    Good video, good walk through of you thought process

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      Glad you liked it! Thanks for your feedback!

  • @ronaldclark8187
    @ronaldclark8187 7 หลายเดือนก่อน +1

    Good video.
    Really dirty system.
    Ya had to clean up someones previous changeout.
    That HP drop was significant.

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      Yep doing another one today 😩

  • @brnmcc01
    @brnmcc01 7 หลายเดือนก่อน +1

    That was pretty good, your suction line temp showed around 37 degrees. Basically for a low temp unit, I don't worry too much about the superheat while it's pulling down, but a low temp compressor doesn't like return gas above 40 degrees F. You were well below 40, so I think it'll live plus it has the airflow of the condenser fans over it.

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      Thanks for the tips!👍👍

  • @throttlebottle5906
    @throttlebottle5906 7 หลายเดือนก่อน +1

    one of those days where your super prepared for the job... 🤣🤣 nothing right, out of everything, SHTF to the end. lol

  • @wd8557
    @wd8557 7 หลายเดือนก่อน +1

    I would have rather done what you did than to trace down a leak. Another great video.

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      Great point! But I did that to. 🤣

  • @terryh8421
    @terryh8421 7 หลายเดือนก่อน +1

    Well done Rick, good work!

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      Thanks for watching

  • @stephenbullock-yn3vh
    @stephenbullock-yn3vh 7 หลายเดือนก่อน +4

    Great work 👍

  • @ironon3257
    @ironon3257 6 หลายเดือนก่อน +1

    Hello my friend
    What cause making a compressor run reverse? Please Can you tell me more about this situation? Thank you

    • @HVACRSurvival
      @HVACRSurvival  6 หลายเดือนก่อน

      If it doesn’t have a capacitor it can be reversed phasing. If it does have a capacitor, the capacitor could be wired incorrect causing it to go in reverse

  • @johnwalker890
    @johnwalker890 7 หลายเดือนก่อน +1

    Good job Rick......

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      Thanks John! Have a good weekend!

  • @jewellhirsch1694
    @jewellhirsch1694 4 หลายเดือนก่อน +1

    Are you Mr. HVAC still available? What about just estimate? Did you make an hour just curious from Tallahassee Fred

  • @jrc630
    @jrc630 6 หลายเดือนก่อน +1

    Great job

  • @Gcanno
    @Gcanno 7 หลายเดือนก่อน +1

    Thank you.

  • @delvinwooten3213
    @delvinwooten3213 4 หลายเดือนก่อน +1

    Great Video I see you are a Testo manifold User have you seen used the fieldpiece manifold set?

    • @HVACRSurvival
      @HVACRSurvival  4 หลายเดือนก่อน +1

      @@delvinwooten3213 nope. I have the FP probes. There good but I don’t like how big the field piece manifold is.

    • @delvinwooten3213
      @delvinwooten3213 4 หลายเดือนก่อน

      @@HVACRSurvival😂 yeah it’s about the size of a tablet

  • @SeanMackBuffaloStyle
    @SeanMackBuffaloStyle 7 หลายเดือนก่อน +3

    It was probably short cycling during hot gas defrost....I've found a few systems overcharged going off on high pressure safety during defrost....masterbilt only opens the eev 50 percent in hot gas defrost and can't be reprogrammed

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      That’s crazy but since there’s no TXV outside is likely why.

    • @Thermoelectric7
      @Thermoelectric7 7 หลายเดือนก่อน +1

      It's not hot gas defrost, it's reverse cycle. Flips the evap and condenser around like a typical heatpump.
      Would be interesting to see what it's doing for metering, might just check around the EEV and go through a fixed orifice or something.
      Can't imagine that'd cause short cycling, as you get plenty of heat from the "condenser" to keep the pressure up

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      You’re probably on the right track, there’s so many things I would’ve done differently. I didn’t go into all the details of how much stuff was screwed up. I should’ve put out a timeline, but there was a lot of half ass hackery going on and stuff was being done in the rain storms.

    • @SeanMackBuffaloStyle
      @SeanMackBuffaloStyle 7 หลายเดือนก่อน +1

      @Thermoelectric7 the Evaporator fans don't run in reverse cycle like a heat pump, your not condensing, just robbing heat. That sounds like hot gas defrost to me.
      Short cycling on high pressure safety during defrost. If you restrict the Eev to 50 percent in defrost, your charge has to be perfect with no receiver.

    • @Thermoelectric7
      @Thermoelectric7 7 หลายเดือนก่อน

      @SeanMackBuffaloStyle the reversing valve is what makes it reverse cycle, not hot gas. Hot gas defrost just dumps the discharge line past the expansion valve. Reversing valve swaps the evap and condenser. Hot gas would have 3 pipes going to the evap. Reverse cycle only needs two.
      It will 100% be condensing in the evaporator when in defrost. You don't need the evap fans running when it's a block of ice. All that discharge gas will condense as it melts the ice and warms the coil up. At which point it passes backwards through the metering device, into the condenser on the roof, evaporates, and is recompressed.
      Reverse cycle defrost pulls heat from the condenser on the roof and environment to defrost. Hot gas just uses the heat from the compressor. Massive difference.
      It'll never trip on HP in a reverse cycle defrost, unless the termination isn't working right, at which point your scenario would be right and it would run high head as there's no more ice in the coil to melt.

  • @stevencossaboon3237
    @stevencossaboon3237 7 หลายเดือนก่อน +1

    Nice job Rick.

  • @joshua.sookoor2025l
    @joshua.sookoor2025l 7 หลายเดือนก่อน +1

    Great video rick & job, nice troubleshooting, did you work on this equipment a few months ago, because it looks familar, i think this unit was a hussman, damm the compressor was loud at first but it shut off, the noise.

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      No, I worked on one of their other stores. They have several so they have the same equipment and every building is the same.

    • @joshua.sookoor2025l
      @joshua.sookoor2025l 7 หลายเดือนก่อน +1

      @@HVACRSurvival or ok, because at the end of the video i noticed it was a masterbuilt

  • @zunar_j5_933
    @zunar_j5_933 7 หลายเดือนก่อน +3

    Did a compressor initially burn out and contaminate the system and was never flushed out? Then subsequent compressors got wrecked? Edit: never mind, bet it was the pressure switch config if das shaft was broken.

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน +4

      First they replaced the reversing valve then a short time later the pressure switch broke and dumped the charge. Then the pressure switch was replaced and I believe they set it up incorrectly, then the discharge line cracked and dumped the charge again, they repaired that then the compressor burned out shortly after that, then they replace the compressor and it snapped off the shaft a couple weeks after that. because the guy that replaced the compressor didn’t check the pressure switch, I believe it short cycled until it broke.

    • @zunar_j5_933
      @zunar_j5_933 7 หลายเดือนก่อน +2

      @@HVACRSurvival man…what a cluster! Well done on the fix!

  • @calebburns4346
    @calebburns4346 7 หลายเดือนก่อน +1

    I learned with my testo probes that i have to periodically take them off and make sure there still reading zero. Had a intellagen freezer not long ago that i was checking the suction transducer and almost called it a bad suction transducer, until i took my probe off and found that even though i Zero'd it prior it was at -7 open to atmosphere. Zero'd again and then i was reading the same as the board.

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      I was setting up a freezer super heat two weeks ago and it was zeroed out before I went in there and when I got done, I thought it was set then rechecked it and it was completely off. I don’t believe these are compensated like they claim. At least not on the probes. They’re too cheap to be able to be that. When I got out my 557 it worked just fine so I don’t 100% trust the probes. Like you said though they really need zero out in the ambient temperature they’re gonna be operating in after they’ve stabilized in temperature.

    • @calebburns4346
      @calebburns4346 7 หลายเดือนก่อน

      @HVACRSurvival I am not really impressed with the pressure probes. I stick to only using them for reach ins or prep tables. Even then, i usually just get the analogs with short hoses. I don't know if the field piece probes have the same issues, but I may switch to the field piece. I've had the sman380s for 5 years now, and I have not had a single issue. In fact, I still have the original temp clamps they came with.

    • @brnmcc01
      @brnmcc01 7 หลายเดือนก่อน +1

      @@HVACRSurvival I like my new(ish) Fieldpiece Sman's, they are more bulky than the Testo, but this newer one seems to hold a zero pretty good. That was annoying with my older fieldpiece, I could zero it out, and then after like 5-10 minutes I would have to zero it again. Was so frustrating to always remember to turn on the gauges right away before even taking them off the truck, to allow enough time for them to "warm up" and stop drifting. I think the one I have now is the SMAN 380v, not 100% sure tho.

  • @crxshed
    @crxshed 7 หลายเดือนก่อน +1

    I have to ask if any of you guys have a good aluminium foil to wrap on armaflex to protect from uv?

  • @eastcoast186
    @eastcoast186 7 หลายเดือนก่อน +1

    Thanks for the video

  • @atch_n_sons
    @atch_n_sons 7 หลายเดือนก่อน +2

    Keep setting that bar Rick. WWRD

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      Hardly 😂. But thank you!

  • @markjohnson9964
    @markjohnson9964 7 หลายเดือนก่อน +1

    You do awesome work

  • @SombraLocs
    @SombraLocs 4 หลายเดือนก่อน +1

    I've never seen a reversing valve on a freezer. What is that blue marker that you use?

  • @sherwinalvarez7365
    @sherwinalvarez7365 7 หลายเดือนก่อน +1

    You're awesome too Rick.

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      You’re too kind, thanks for watching!

  • @SombraLocs
    @SombraLocs 4 หลายเดือนก่อน +1

    You can't pull moisture out of POE oil?

    • @HVACRSurvival
      @HVACRSurvival  4 หลายเดือนก่อน

      Not like you can with mineral oil and a vacuum pump. POE oil doesn’t want to let go of the moisture as easily. The filler drier is the only way.

  • @vornelas82
    @vornelas82 7 หลายเดือนก่อน +1

    That was a fun video to watch. Thanks 🙏

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      Glad you enjoyed it! Thank you for reaching out! Your feedback it’s important!

  • @thesilentonevictor
    @thesilentonevictor 7 หลายเดือนก่อน +1

    Rick saved the day again

  • @pattyPIMPIN
    @pattyPIMPIN 7 หลายเดือนก่อน +1

    Those Masterbilt MAC units suck, I would have replaced that DTC as well

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      I had another composure on a Mac unit go bad today. I’m ordering the liquid injection valve.

  • @zekenzy6486
    @zekenzy6486 7 หลายเดือนก่อน +1

    Great video. Thank you for sharing. Have a nice weekend. May I ask, why freezer use 3 way reversing valve heat pump ? and for freezer, which high , low pressure , Super heat, subcooling number is good ?

    • @Boraxo
      @Boraxo 7 หลายเดือนก่อน

      Defrost?

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน +2

      The reversing valve is used to melt the frost from the evaporator coil. Just like a heat-pump defrosts.

  • @DW-bo3qw
    @DW-bo3qw 7 หลายเดือนก่อน +1

    Gotta love those Mac units

    • @DW-bo3qw
      @DW-bo3qw 7 หลายเดือนก่อน +1

      Also I believe those units come with sporlan csg driers factory installed I don’t believe you need a bi flow drier for this unit

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      It’s the same design as a heat pump

  • @Bruceman17
    @Bruceman17 7 หลายเดือนก่อน +1

    This customer must have deep pockets! How much time did it take you to do all of this and are you running other calls on these days?? I average 12-14 hours a day running 5-8 calls while adding more Work orders cause theres always something else broken 😅 ( I do hot side and beverage machines too btw)

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      I normally run 4-6 calls if they are easy.

  • @lincolnhunt9558
    @lincolnhunt9558 7 หลายเดือนก่อน +1

    never heard of a 4 way reversing valve on a walk in cooler or freezer. Does the outdoor coil have a separate metering device for the defrost cycle?

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน +1

      Nope. But the EXV only opens 50% from what I’ve read in the comments.

    • @Thermoelectric7
      @Thermoelectric7 7 หลายเดือนก่อน

      Only place I've ever seen it is on fancy gelato freezers. Reverse cycle is way quicker than hot gas or electric on a single unit like that so helps limit the impact on product temp by means of a short defrost cycle. Neat stuff. Way more efficient too.

    • @brnmcc01
      @brnmcc01 7 หลายเดือนก่อน

      @@HVACRSurvival Yeah, that's to provide some restriction to build up pressure to provide some heat in the coil. I don't like those kind of systems, the problem is, in the winter on a cold windy day, you get about one good blast of hot gas, then the heat is gone, and even then, you still need electric heaters for the drain pan and drain line, so it's a waste. I have only used electric defrost since the late 1990's. Last one that I worked on, they were using a Bryant 4 ton heat pump for a condensing unit with 2 Larkin evaporators and a receiver remote mounted on the roof beside the unit. Was a real shitshow to get that working correctly. It wasn't a freezer per se, it was a meat cooler, with box temp control set to 30 cut in, 28 cut out. Even though that's not a freezer, anytime you have a desired box temp of less than 35, you can't use off cycle air defrost anymore.

  • @EverythingHVACR
    @EverythingHVACR 7 หลายเดือนก่อน +7

    Nice job, Rick! You got shit meter leads 😅

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน +1

      Wtf ever. Them are the best I’ve ever had and they’re made in the USA

    • @EverythingHVACR
      @EverythingHVACR 7 หลายเดือนก่อน +2

      @@HVACRSurvival 😆 you said it. Had me laughing.

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      I got it now 🤦 I’m slow sometimes

  • @PhilJackZen
    @PhilJackZen 7 หลายเดือนก่อน +1

    Why not flush the system?

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      Works it works good for line sets, but not so much for the condenser or evaporator coil.

  • @lavina58
    @lavina58 7 หลายเดือนก่อน +1

    Nice video. Great job 🙌👍😊👌🍀

  • @commenter5469
    @commenter5469 7 หลายเดือนก่อน +3

    That sight glass was burned upon brazing.

  • @Ramirez.A91
    @Ramirez.A91 7 หลายเดือนก่อน +1

    How long have you been in the trade?

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      1995

    • @Ramirez.A91
      @Ramirez.A91 7 หลายเดือนก่อน

      It really shows. Thank you for the awesome videos!

    • @daleborg9070
      @daleborg9070 7 หลายเดือนก่อน +1

      @@HVACRSurvival That is about the time I got out of the trade because of injuries. Did a lot of work for that company you were servicing.

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      The store have their own maintenance guys, which they still do, but just like us they can’t find good qualified people so they only have a few guys now and now they us to take care of their several stores which are all spread out over Ohio.

  • @BLUE_COLLAR_REFER
    @BLUE_COLLAR_REFER 7 หลายเดือนก่อน +1

    What a Big ol McKnightmare

  • @dougking7592
    @dougking7592 7 หลายเดือนก่อน +2

    Nice video for not intending to be, site glass looked way better brother

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      Thanks. I’m updating my stock on Monday

  • @promisel1964
    @promisel1964 7 หลายเดือนก่อน +2

    you can only polish it so much

  • @SombraLocs
    @SombraLocs 4 หลายเดือนก่อน +1

    27:38😂😂😂😂

  • @ryanmarlatt5726
    @ryanmarlatt5726 19 วันที่ผ่านมา +1

    5 psi cut off. Nothijg lower. The scrolls dont like it

  • @HardKnocks101
    @HardKnocks101 7 หลายเดือนก่อน +1

    Walgreens

  • @edwardgaddis8333
    @edwardgaddis8333 7 หลายเดือนก่อน +1

    Good Ole Mac units. I hatem!

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน +1

      Shit dressing with special sauce. Just throw two True condenser units up there with regular Txv’s and call it a day… when these things get old they waste more money on maintaining and repairing them than what they saved by putting them in to begin with.

    • @edwardgaddis8333
      @edwardgaddis8333 7 หลายเดือนก่อน +1

      @HVACRSurvival brother you're preaching to the choir. I've stood on the roof with a ops manager and asked why, his answer it's what McD wants. When I knew he was doing a remodel I asked don't use a Mac unit and if you must make it Heat Craft. He ends up putting in RPG/Master Junk. Some bean counter made this decision with in McD Corp and it stuck. If they used standard I could just run to a local vendor and boom fixed on the day but oh nooooooo....so a control board goes bad walk in down well guess what call a refrigerated truck out because the board need maybe 48 hrs to get here. Dumb!!!! Rant over lol

  • @jonnymac31
    @jonnymac31 7 หลายเดือนก่อน +1

    Cool man

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      ✌️ hey John!

  • @phxrus
    @phxrus 7 หลายเดือนก่อน +1

    Acid away with every compressor change

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      I debated using it. I’ve used it in the past and never had a problem.

  • @snidelywhiplash8923
    @snidelywhiplash8923 7 หลายเดือนก่อน +3

    You're a magician, not a technician.

    • @HVACRSurvival
      @HVACRSurvival  7 หลายเดือนก่อน

      🤣😂👍👍

    • @Youngbl33zy
      @Youngbl33zy 7 หลายเดือนก่อน +1

      No, hes just a standard technician. You must’ve been let down by below standard technicians.

    • @snidelywhiplash8923
      @snidelywhiplash8923 7 หลายเดือนก่อน +1

      @@Youngbl33zy Nope, that's never happened to me. I hire contractors by reputation and customer references I trust, not by price.

  • @mikefrayman5224
    @mikefrayman5224 6 หลายเดือนก่อน +1

    Hi, I dislike Masterbuilt

  • @steveblake8766
    @steveblake8766 7 หลายเดือนก่อน +1