Diagnosing Daikin Errors

แชร์
ฝัง
  • เผยแพร่เมื่อ 28 ส.ค. 2024
  • Some steps I go through to verify an error on a Daikin VRV III system.

ความคิดเห็น • 36

  • @Modello40
    @Modello40 3 ปีที่แล้ว +3

    Thanks for your service help dude. Relatively new to the service side of ac after 20 years of new installs. Seem to come up with a lot of the common faults (u4, u2..etc) recently had L9, E5. It’s nice to see you going through the steps to check things. Nice to know I’m following the same steps. Keep up the good work dude

    • @Modello40
      @Modello40 3 ปีที่แล้ว

      @Zrow Crow I did. Inverter board had gone.

    • @Modello40
      @Modello40 3 ปีที่แล้ว

      @Zrow Crow none required as far as I know. Only check i did, was to make sure the inverter wasn’t coded out. :)

    • @javeedhvactechnician7760
      @javeedhvactechnician7760 3 ปีที่แล้ว

      th-cam.com/video/FpuUXpV6BDA/w-d-xo.html

  • @subaru0014
    @subaru0014 5 ปีที่แล้ว +2

    Awesome video.. you know ur stuff man! I love the video daikin is a bit more harder to deal with than Mitsubishi..

  • @capitolrefrigerationheatin7501
    @capitolrefrigerationheatin7501 6 ปีที่แล้ว +7

    Seems like your average tech cannot work on a daikin, they must have a busy tech support phone line

  • @bmiadmin5784
    @bmiadmin5784 8 หลายเดือนก่อน

    Since so much problems with this brand, changed with other brands, now no problems!!!!

  • @craigladewig3158
    @craigladewig3158 5 ปีที่แล้ว +8

    Nice explanation, I hate Daikin VRV systems. Where can I find the sheet of codes you referenced

    • @tcphvacr9950
      @tcphvacr9950  5 ปีที่แล้ว +4

      Craig Ladewig www.daikin.com/products/ac/services/error_codes/pdf/sm-ts3_p1-6_errorcode.pdf
      And download the Daikin Service App, available on Apple and Android. You can plug in the error codes, and it will even give you the troubleshooting flow diagram.

    • @javeedhvactechnician7760
      @javeedhvactechnician7760 3 ปีที่แล้ว

      th-cam.com/video/FpuUXpV6BDA/w-d-xo.html

  • @joeshearer1247
    @joeshearer1247 6 ปีที่แล้ว +5

    Would it be that much more to put a lcd display on the board? Sheeesh

  • @riddlebergerbrothers8348
    @riddlebergerbrothers8348 3 ปีที่แล้ว +2

    Where did you get your inverter board tester at?

    • @tcphvacr9950
      @tcphvacr9950  3 ปีที่แล้ว

      It’s an older style tester that was used to test boards, can’t get that style anymore. I like it better than the newer ones.

    • @javeedhvactechnician7760
      @javeedhvactechnician7760 3 ปีที่แล้ว

      th-cam.com/video/FpuUXpV6BDA/w-d-xo.html

    • @Darny1able
      @Darny1able 7 หลายเดือนก่อน

      thanx ill check it out u in queensland.
      i generally look for a balanced voltage from the inverter board.
      am in sunny u.k but worked in perth 1990 doing fridge a/c
      fun times with a weekly wage packet in cash.😂

    • @Darny1able
      @Darny1able 7 หลายเดือนก่อน

      got that wrong u got american accent

  • @madman198585
    @madman198585 3 ปีที่แล้ว +1

    Good job done

  • @Darny1able
    @Darny1able 7 หลายเดือนก่อน

    were u get the that inverter checker from. Ta

    • @tcphvacr9950
      @tcphvacr9950  7 หลายเดือนก่อน

      From the local Daikin Service Representative. They don’t make them anymore, but Refco makes an inverter checker now that does the same thing, and it’s much smaller, will fit in a tool bag. Here’s a link from Trutech Tools, much cheaper than Amazon:
      trutechtools.com/Refco-Inverter-Check-Kit-wData-Flow-Monitor_p_4930.html

  • @satishdhiman706
    @satishdhiman706 5 ปีที่แล้ว

    I want to know about Daikin VRV lV
    Indoor remote have coming E2
    Other indoor remote LC
    Outdoor unit coming LC-14
    Still compressor not working
    How I do diagnose?

    • @tcphvacr9950
      @tcphvacr9950  5 ปีที่แล้ว

      Download the Daikin Service app on Android or Apple, and go to "fault codes" and type in LC-14. It will tell you you have a "Master Outdoor Unit First Inverter PCB Communication Fault", meaning there is a communication error between the main PCB and first inverter compressor. It will also give you a flow diagram for troubleshooting. As far as the E2, That is an earth leakage detection fault. The small earth leakage board could be lit, detecting either something grounded (bad compressor), or a bad main board, or a bad earth leakage board. Service manual will also tell you how to troubleshoot these faults.

    • @javeedhvactechnician7760
      @javeedhvactechnician7760 3 ปีที่แล้ว

      th-cam.com/video/FpuUXpV6BDA/w-d-xo.html

  • @michaelgatlin9046
    @michaelgatlin9046 4 ปีที่แล้ว

    What is your experience with a L1 error?

  • @moali2812
    @moali2812 4 ปีที่แล้ว

    How would I get those troubleshoot sheets u have

    • @tcphvacr9950
      @tcphvacr9950  4 ปีที่แล้ว +1

      You can download the PDF of the service manual, and print out the sheets that you want to take with you for troubleshooting, like I did. Go to www.daikinac.com, and select Resources>Manuals>Service Manuals, and find the product you need.

    • @javeedhvactechnician7760
      @javeedhvactechnician7760 3 ปีที่แล้ว

      th-cam.com/video/FpuUXpV6BDA/w-d-xo.html

  • @satishdhiman706
    @satishdhiman706 5 ปีที่แล้ว

    Hello sir

  • @musashaikh8161
    @musashaikh8161 5 ปีที่แล้ว

    Sir please vrv gas pump down video a and trick