Daikin A1P Board

แชร์
ฝัง
  • เผยแพร่เมื่อ 13 ก.ย. 2024
  • Changing out an A1P board after troubleshooting an E9 error.

ความคิดเห็น • 26

  • @smferreiro2610
    @smferreiro2610 ปีที่แล้ว

    If I remember correctly, the identical red ones are for the compressor's crankcase heating elements. They are interchangeable.

    • @tcphvacr9950
      @tcphvacr9950  ปีที่แล้ว

      The crank case heaters are specific to each compressor, they are turned on and off based on conditions for each compressor. Switching them could cause damage.

    • @smferreiro2610
      @smferreiro2610 ปีที่แล้ว

      @@tcphvacr9950 I also rather keep connections as they are set in the factory... but what you mention must be model-specific. The Daikin VRVs I've serviced all have crankcase heaters on full-time.
      As a matter of fact, the manual states that turning on the equipment in cold weather requires pulling up the mains six hours earlier to ensure all compressors' oil is on temperature.

    • @smferreiro2610
      @smferreiro2610 ปีที่แล้ว

      @@tcphvacr9950 I guess we can follow the tracks in one A1P and see if they are switched by independent mini-relays, or if they are both turned on by the same one.

  • @suryanijonitunandar7225
    @suryanijonitunandar7225 3 ปีที่แล้ว +1

    Hi Sir, How to replacement pcb A1p for master. Thank you

  • @ramiropedronzengedu3786
    @ramiropedronzengedu3786 2 ปีที่แล้ว

    hola como estais es que tengo un problema en la instalacion se me ppresenta la codigo de averia L1 que puedo hacer

  • @braddavis5871
    @braddavis5871 3 ปีที่แล้ว

    wish Daikin had VRV classes locally I pay my own way

    • @tcphvacr9950
      @tcphvacr9950  3 ปีที่แล้ว

      Where are you located?

    • @braddavis5871
      @braddavis5871 3 ปีที่แล้ว

      @@tcphvacr9950 New Orleans, Mid South Equipment isn't having anymore classes for a while and Houston is my only other option.

  • @dinurangakarunathilaka5389
    @dinurangakarunathilaka5389 6 ปีที่แล้ว

    Do you know how to factory reset the program pcb.(once we did some programs by mistake and later on forgot them.)

    • @dinurangakarunathilaka5389
      @dinurangakarunathilaka5389 6 ปีที่แล้ว

      A1P PCB

    • @tcphvacr9950
      @tcphvacr9950  6 ปีที่แล้ว

      DINURANGA KARUNATHILAKA I believe you should contact Daikin support for that, because once you reset you will have to recommission the system all over again. You should be able to check what you’ve done by reading the service manual and going through specific checks outlined in it.

  • @hope9525
    @hope9525 5 ปีที่แล้ว

    Hello sir, Can you tell me? how to bypass normal compressor and run inverter compressor

    • @tcphvacr9950
      @tcphvacr9950  5 ปีที่แล้ว +1

      If it is a two module system, you can't do it. If it is a single module system with one inverter and one standard, hold the BS1 button for 5 seconds until H1P becomes solid, press BS2 39 times, press BS3 once, and H7P flashes, press BS2 once and H6P flashes, press BS3 once and H6P becomes solid, and then press BS3 again to activate the setting.

    • @hope9525
      @hope9525 5 ปีที่แล้ว

      Thank you sir, but it's triple module vrv3. In this case what can I do? That means 3unit, 6inverter, 6 normal.

  • @rajveerraju2646
    @rajveerraju2646 4 ปีที่แล้ว

    Broo thermostat showing u 4
    What i will do please tell me

    • @tcphvacr9950
      @tcphvacr9950  4 ปีที่แล้ว +1

      Rajveer Raju you have an indoor unit or BS box powered down. You need to find out which one it is and turn it on.

    • @rajveerraju2646
      @rajveerraju2646 4 ปีที่แล้ว

      @@tcphvacr9950 thanks sir
      Today i will chek

  • @titodiaz6433
    @titodiaz6433 4 ปีที่แล้ว

    do u charge fee for info need help some times like to talk to someone

    • @tcphvacr9950
      @tcphvacr9950  4 ปีที่แล้ว

      Tito Diaz I don’t take calls to help, nor do I charge fees. I will however read messages and if I can, give help when I know the answer. I don’t mind sharing the knowledge, but don’t have the time to field calls. Send me a message via TH-cam and I’ll let you know if I can help.

  • @mikecapps8723
    @mikecapps8723 6 ปีที่แล้ว

    Where are you located? If I may.

    • @tcphvacr9950
      @tcphvacr9950  6 ปีที่แล้ว

      mike capps St. Louis, MO

    • @stevenhonory5051
      @stevenhonory5051 5 ปีที่แล้ว

      @@tcphvacr9950 Hi guy sorry what the problem compressor is not running in side remote control no fault

  • @suadbekteshi4861
    @suadbekteshi4861 3 ปีที่แล้ว

    i have Pj error code

    • @tcphvacr9950
      @tcphvacr9950  3 ปีที่แล้ว

      If the A1P has been replaced, the dip switches aren’t set correctly. There should have been paperwork with the board showing your model and setting positions. Make sure you don’t have your “on” and “off” backwards.