Brand : Daikin VRV3 model : RXQ18PAY13 this video to show you high pressure sensor reading. please like, share, Subscribe my You Tube channel. #Daikin #VRV3 #VRV #VRV4
Thank you so much this was a cut and dry to the point to troubleshoot this particular issue I am having. Great job sir and thank you again. Subscribed to your channel
Great job again showing the steps and locations. Where I work we have a lot of Pfannenberg system's that cool VAV drive systems' down, like 100 of them. I took a bran new system to my shop and (OHM'ED ) out everything, fans, temp sensor's , heater's, transformer's. Any wires I was forced to cut where replace by male/ female terminals . I have a book with every reading I carry when one goes down I have info instantly. " usually blown fuses 1 and 2" bad transformer. If I worked on Daikin VRV3 I would do the exact same thing. Note : I have all the reading's almost memorized by know, that book was the time and life saver.
Hello sir bon! How to replace a soldered/fix high/low pressure switch in the system,,,is the refrigerant came out when we cut or we need to close the suction and discharge valve? Thanks sir bon 🙏
Sir Bon the VRV 3 which i did weeks ago, the pressure sensor installed is thread type, its not a welded or braze type. so i never use torch to install it
Sir , so if standard for sensor like this or transducer the 3 wire check must be red to black the reading must read kohms and from red to white must be mohms ? If from red to white we measure is kohms then it is faulty ?
Thank you very much.Sir my question would be that the E3 error still exists after the replacement.High pressure sensor good.What could be the reason? The reset button on the panel needs to be pressed for 5 seconds?
Hello I am curious if I could get some help on reyq168taydu (vrv 4 I believe) error code is ja-07. I need help locating high pressure sensor. Is it the same as in vrv 3? Thanks in advance
I can't find ohms reading in the service manual (SiUS34 - 801A_b) on that sensor, only voltage checking between black & white, and without reading voltage values either 😩
@@BonMj not yet but will, I have been watching your tube channel for a while, thank you for sharing, I'm only a 3rd year apprentice and was trouble shooting alone. Check the transistors on the main PCB I was doing what my senior technician told me to do and we have the same results.
Update, I tested the windings on MC1 I recorded 300 to 400 which is under the specification that they can requires. We locked out MC1 and set Mc2 to primary until we swap compressors.
Thank you very much for your generosity I salute you and god bless you for everything you have taught me.
Thanks
@@BonMjbefore Error code
Very good teacher..marcos from Brazil...
Thanks
Thank you so much this was a cut and dry to the point to troubleshoot this particular issue I am having. Great job sir and thank you again. Subscribed to your channel
Thanks bro
Thanks boss, nice content, your video help me a lot to learn about vrv error.. Please continue to make more video for vrv..
Thanks
Thank you very much for your beautiful mind to share your knowledge to ones. Thank you
Thanks
Great job again showing the steps and locations. Where I work we have a lot of Pfannenberg system's that cool VAV drive systems' down, like 100 of them. I took a bran new system to my shop and (OHM'ED ) out everything, fans, temp sensor's , heater's, transformer's. Any wires I was forced to cut where replace by male/ female terminals . I have a book with every reading I carry when one goes down I have info instantly. " usually blown fuses 1 and 2" bad transformer. If I worked on Daikin VRV3 I would do the exact same thing. Note : I have all the reading's almost memorized by know, that book was the time and life saver.
Good job, ur video's are very helpful for me
Thanks bro.
Please share.🙏
Hello, very informative video, I have a HP Sensor which reads R to B = 0L and R to W = 0L. Would you class this as faulty.
Very nice video,how to baypas vrv outdoor unit to emergency time,thank you sir
Thanks.
Check my video
IG in the state good working
Very good job.. you now your job
Thanks bro
Plz add subtitle in your videos..and plz make your other future videos in english so that anyone can learn from your works.Thank you.
Everything is easy if you know what needs to be done. 👍
Thanks bro. 👍
Good job sir
@@vinodnavalpawar7362 thanks bro
I had the same problem, I measured the white to red wire and it came up to be 17 M ohm. Is 17 M ohm still ok?
thainks veriy nice yor video
Thanks bro
Good job sir job
Thanks
Thank you my teacher
Thanks
I like your vedio sir
Thanks bro 🙏
Good sir
Thanks
Thank you very helpful
Thanks
boss, do you do residential multisplit service and repair?
Suparb bro🙌🙏
Thanks bro
🇹🇷🛠️🤳👍 nice Job bro
Thanks
Thank you sir 👌👌👌
Thanks
GOOD JOB
Thanks
thank you bon sir
Welcome
Good
Thanks
Good sar love you
Thanks.
Hello sir bon! How to replace a soldered/fix high/low pressure switch in the system,,,is the refrigerant came out when we cut or we need to close the suction and discharge valve? Thanks sir bon 🙏
Yes, close the service valve and empty the gas at cu side or do recovery .
@@BonMj next to that we do the reprocess then do a auto charge sir bon is it right? 😁 thankyou sir bon for notice me godbless always 🙏🙏🙏
Sir Bon the VRV 3 which i did weeks ago, the pressure sensor installed is thread type, its not a welded or braze type.
so i never use torch to install it
👍
What is good ohm for this HPS ?
thank you so much
Thanks
Sir i have one qution vrv3 single compreser i change and allso i change invater board but compreser not cooling y
Any error
Sir , so if standard for sensor like this or transducer the 3 wire check must be red to black the reading must read kohms and from red to white must be mohms ? If from red to white we measure is kohms then it is faulty ?
Yes
Thank you very much.Sir my question would be that the E3 error still exists after the replacement.High pressure sensor good.What could be the reason? The reset button on the panel needs to be pressed for 5 seconds?
Press reset button more than 5second.
After reset the error is clear
Thank you!
Greetings from Hungary!
@@zsoltbitaroczki5045 👍👍welcome
U can replace main PCB last option
We must welding the pipe sir ?
Yes
I already test high pressure sensor because the remote i find E3 error code, i find 94 K ohm and 4.5 ohm. What my pressure sensor is good?
And i have another question to you, my last compressor not running sir, can you give me a tips or answer about that problem? Thanks before
Last compressor is 3rd compressor
Will the reading of the low pressure sensor remain the same?
Sir
Yes.
Thank you sir and can i ask one...
The earth leakage pcb was red led coming what's the problem
Daikin Vrv?
@@BonMj yes Daikin vrv 3
@@karthikmurugan8622 H2P led on
Or H3P led on
@@BonMj this is slave unit 2 08hp all led is off
But master unit is H2p and H8p led is standard sir but CRC is E3 showing
@@karthikmurugan8622 Master unit H2P led on mean got error.
👍🇮🇳😘
Sir , You Have Release the gas either pump down the machine ? Answer plz
Cant pump down. Cos high pressure is internal.u can lock the service valve and release it.
But,We Can't Transfer gas from master to slave ?
@@alfacoolspareparts not recommend
@@BonMj If you ever get caught releasing R410a refrigerant to atmosphere here in the UK 🇬🇧, you will be taken to court and get heavy fine.
@@m.haslam8495 wow.....
Sir, You Have Release the gas , either pump down the machine
How to check vrv x basic trouble shooting.
The easy way is follow the error code.
Can the high pressure sensor makes the compressor not to run
For vrv will have error code.
For super inverter may be the compressor unable to run high load.
Sir, Why Different ohm From Red And White ? Answer plz
M ohms
Hello I am curious if I could get some help on reyq168taydu (vrv 4 I believe) error code is ja-07. I need help locating high pressure sensor. Is it the same as in vrv 3? Thanks in advance
High pressure sensor wire connection at Control PCB X32A.
The high pressure sensor locate On top of the compressor (the top one)
Do you know daikin VRV U9 fault ? And how to repair it
Try to check indoor unit
Ok sure
I can't find ohms reading in the service manual (SiUS34 - 801A_b) on that sensor, only voltage checking between black & white, and without reading voltage values either 😩
The simple way measure the ohm.
I already change few.
@@BonMj Of course, but I meant I didn't find in the manual the ohms value that parts must have.
@@JuanTodoli understand
Sir mau tanya.. kl utk daikin vrv III kode error nya JA. Bagaimana cara mengatasi nya ya? Dan apa penyebab nya ? Mohon petunjuk nya sir. Terima kasih
Check high pressure sensor
@@BonMj thank you so much sir..
And i already subscribe your channel
I have a E5-01 on vrv replaced inverter board and still have the same e5-01 possible bad compressor
Do you check out put voltage from inv pcb
@@BonMj not yet but will, I have been watching your tube channel for a while, thank you for sharing, I'm only a 3rd year apprentice and was trouble shooting alone. Check the transistors on the main PCB I was doing what my senior technician told me to do and we have the same results.
@@marcoferreira226 👍👍
Update, I tested the windings on MC1 I recorded 300 to 400 which is under the specification that they can requires. We locked out MC1 and set Mc2 to primary until we swap compressors.
What tester is he using
Multimeter
Sir how to settle E2 error code vrv 3 . ISO off also but still have current in L2.
Check isolator income and out going voltage
Sir how you replace the sensor this sensor is brazing type or nut type?
Brazing
@@BonMj sir it means first you pump up this condenser unit how is pump up please reply
I use checker.
I will update how i use checker to read the reading.
老师这种pressure sensor只有VrV有?普通机有么?
有
Daikin RZR model 有。
Inverter 应该没有
@@BonMj 谢谢老师
You forgotten to tell everyone to recovr the gas and to brase the new sensor in then regad system
How to replace this device?
Welding
@@BonMj Is it necessary to remove all refrigerant from the system?
@@tebbink no .
Only Condenser .