Hi Mr Bon, i love watching your instructional videos i just wondered how would you charge the extra refrigerant, if you could not determine the pipe length, does the auto charge procedure automatically detect the correct refrigerant charge ?
mr bon juat wanna ask when i want to do auto charge should i open valve to release gas from compressor first or dont open the valve and auto charge it and then release the gas from compressor ?
I have worked on the vrv 2 and 3 a lot but I have not worked on vrv 4 yet.Please why do you have to do all these settings(auto charge and test run) after you have replaced the main Pcb.On vrv 2 and 3 Is straight forward you don't need to do anything. What is auto-charge by the way?Is it something to do with the refrigerant being recharged into the system? PLEASE advise.thank you
What is the reason for E2 error in Daikin vrv4 outdoor unit and how to rectify?and also three times second inverter compressor changed but again second inverter compressor grounded
E2 you need to check the high pressure switch and high pressure sensor reading. Compressor replace 3 times!suggest you release all the gas,make the pipe calculation ,and recharge gas with correct quantity.
When new air con is done,u can gauge the amount of refrigerant needed to be charged by measuring the pipe lenght and pipe size. Auto charge can only charge 4kg of refrigerant.
Hi Mr Bon, i love watching your instructional videos i just wondered how would you charge the extra refrigerant, if you could not determine the pipe length, does the auto charge procedure automatically detect the correct refrigerant charge ?
U3-Test run execution failure. This error appear when we do the test run after replace new pcb. Try it twice is same error U3. Use the new installation method, Auto charge and after that test run. The unit but to normal.
My name is Mohamed Al-Sadiq Mohamed, VRV refrigeration and air conditioning technician. I am from Egypt. I want to travel to work and work hard. I need help
Wouldn't mind shadowing you for a few weeks with fault finding on different systems 👍👍
Thanks
great teacher nobody like him for me
thanks
Welcome
It is a very nice tutorial, Sir Bon...I've learned another trouble and how to rectify it..thanks..
Thanks
Hi ,this video is just in time, I will have to change the main board to Daikin. Thanks
This is vrv4- A , auto charge system.
your videos big help for us.Thank you sir...
Thanks
Could you please let me know the details about that copper line connected to pcb
Sir what would be reason Daikin VRV liquid line is freezing, I check solenoid and sensors and ohms reading look acceptable.
As always
Great jo brother 👍
Thanks bro
Hi Mr Bon, i love watching your instructional videos i just wondered how would you charge the extra refrigerant, if you could not determine the pipe length, does the auto charge procedure automatically detect the correct refrigerant charge ?
Hi, May I ask for Daikin R407c, ds2 and ds3 which button should be on?
mr bon juat wanna ask when i want to do auto charge should i open valve to release gas from compressor first or dont open the valve and auto charge it and then release the gas from compressor ?
Sir if panel fault no need gas recharge? Just to observe the to1 to po9 only?
After reset if U3 , u need to do .
Hi. Do you have U3-10 in the manual?
Correction.
The model is RXQ16AYM.
Thanks
I have worked on the vrv 2 and 3 a lot but I have not worked on vrv 4 yet.Please why do you have to do all these settings(auto charge and test run) after you have replaced the main Pcb.On vrv 2 and 3
Is straight forward you don't need to do anything.
What is auto-charge by the way?Is it something to do with the refrigerant being recharged into the system?
PLEASE advise.thank you
VRV 4 auto charge system, when you replace the main pcb, this procedure is compoundsery. by manufacturer.
Thank you Mr Bon to share you knowledge
Do u conduct any course for water cooled package / air cooled package unit?
Hai sir.
RXYTQ12U7YF. unit this same pcb noghing is showing.means no green light and no display.it means pcb is fault??can you plz reply me
Check incoming first
Hi I got the same model and it show f6 error on the peu controller. Can advise please? Thanks I advance
May system overcharge
Or check liquid pipe thermistor
老板谢谢你每次用心讲解
如果是换其他电板也是一样要这样做吗
也是vrv4 还是只是换你这样的电板才需要这样做 谢谢
VRV4 有两个款
1)有Auto charge
2)没有Auto charge
这个video 是 vrv4 有auto charge,所以要这样做。
如果没有auto charge, 只需要test run 就好。
@@BonMj 老板要怎样分辨哪一个款式是有没有auto charge谢谢
@@Lee-mu2jc你注意看service valve那边(check gas 的地方右手边),有个进gas 的service port.
你注意看我video,蓝色pipe就绑在那个service port.
Great 👍sir
Thanks
Thank you sir❤❤
Welcome
Superb sir.
Thanks
请问Auto charge 出现 P9 过后,是不是就说明gas已经足够,不用再进了?
其实auto charge 最多可以进4kg.
如果新装的VRV要先算pipe的长度,在auto charge之前要先进gas,然后再auto charge.
如果像这个video,只是换电板,程序上一定要做auto charge,但是过程是很快的,应为gas是足够的。
对,P9是完成了auto charge.
So great video
Thanks
Hi Mr Bon, if a model RXQ14TY1 VRV4 after replace the main pcb are we can test run without auto charge first?
Depend by error, if no error no need
What happens when the three displays are fixed but do not turn off?
Comunication problem
What is the reason for E2 error in Daikin vrv4 outdoor unit and how to rectify?and also three times second inverter compressor changed but again second inverter compressor grounded
E2 you need to check the high pressure switch and high pressure sensor reading.
Compressor replace 3 times!suggest you release all the gas,make the pipe calculation ,and recharge gas with correct quantity.
Release means reclaim in to a reclaim cylinder , don't want to release" could be misunderstood !
Hello nice Job bro 🇹🇷👍🛠️
Thanks bro
how to do troubleshoot daikin vrv 3 cu side ice
Check indoor EEV, gas pressure
@BonMj OK sir thanks
What is the voltage between f1f2
Around16v
@@BonMj thank you
Great video, by the way, when auto charge active, is this gonna cause the system over charged?
When new air con is done,u can gauge the amount of refrigerant needed to be charged by measuring the pipe lenght and pipe size.
Auto charge can only charge 4kg of refrigerant.
For this case the the auto charge just run for awile and stop.just a bit charge in only
Hi Mr Bon, i love watching your instructional videos i just wondered how would you charge the extra refrigerant, if you could not determine the pipe length, does the auto charge procedure automatically detect the correct refrigerant charge ?
Hi mr.bon please help we was replacing the main pcb.after that ua is appear please help.what the next step
PCB setting correct?
Yes mr. Bon with thanks
老师请问RSQ14TAYM,出U4. 3fcu,第一台没 连接后两台会走,第一台给他一对一会走,三台连接等一台出U4,CU,PCB可以reset故障吗?我有打电话去间,他们说reset电 就ok了,电我关了两天喽!都不可以😂😂😂
是关CU的电对吧!
开回,按reset button 超过5秒
我比较担心是comunication wire 没有接对
1对1=可以
1对2=可以
3台接一起不可以。
你花点时间check 3台fcu comunication wire 有接对吗
@@BonMj cu/fcu都关2天
@@BonMj 都连接对。
RXYMQ8ARY16
Will auto gas charging be done in this model sir
Sorry.this model i not sue,but in the cu should have the auto charge instruction if this is auto charge system
Halo Mr.bon,untukVRV A apabila ada additional indoor perlu melakukan prosedur Auto charge juga ?
Ya...
Thank you sir
Welcome
❤️❤️
Thanks
💪👍👍
Thanks
Hi sir please tell me 99 settings video
MERCI GREAT JOB
Thanks
Hello brother
We are getting UF 01 error code during test run mode
My mchine is new vrv x
Can it be problem if we do not provide earthing
Check all the valve make sure is open.
Restart your test run
Thank You
You're welcome
Bon,,,, very 👍 job,,, mate,,,,, I have question. Those DS1 and DS2 setting what there for ? Can you help me that please
Thanks.
This pcb for all model.
DS1 and DS2 is model setting
@@BonMj thanks Bon…. I really appreciate!!!👍
@@kcomfortsystemshvac7060 welcome
super nice 👌👌👌
Thanks
Thanks a lot
Welcome.
How could you ensure pcb board faulty? Can you elaborate more?
❤
Thanks
-I'm Myanmar Citizen.
-I want to work and learn from you.
-I'm in Singapore now!
What was the error meaning and wht did we get the error
Just reset it and pretend nothing is wrong?
U3-Test run execution failure.
This error appear when we do the test run after replace new pcb.
Try it twice is same error U3.
Use the new installation method, Auto charge and after that test run.
The unit but to normal.
exelente pagina muchas gracias
Welcome
Mr Bon isn't need to auto charging first before test run for all VRV 4 models?
No, for Auto Charge system only, depend by model
Thanks your reply Mr Bon
Is machine run automatically after test run ??
After test run aircon stop running.
You need to on indoor .
@@BonMj understood
@@BonMj Bon I am h fresher with 1 year experience can i get job in Singapore as Aircon technician from abroad
@@MYDUBAI78628 👍
@@BonMj guide m sir how to i apply from abroad
Good Day Sir Bon...How can you rectify the Error Code U9 on Daikin VRV 4 unit? ..If you have a video for this error, its better....Thanks
U9 mean other fcu got problems
@@BonMj Yes Sir...some of the units had a problem
Thank you very much sir, What about error code LC - 14 . AND F6 -02
LC-14 transmission error master cu inverter pcb
@@BonMj thank you very much.
Hi mr bon, i have to change both the INV1 pcb and the CU pcb but the problem Still exist, do you have an idea plz
Please tell me
E3 daikin vrv 3
Check high pressure switch
Explain sir Aircon bypass settings
Thanks
🙏🙏🙏
Sir how to fix daikin vrv 3 ac AH error code
This hot water system?
Not hot water system.
@@bulbmandai2024please check indoor pcb
Ok sir is this complint about indoor section?
@@bulbmandai2024 ya.may be
Bon sar pleas help me u1-16
Phes Cheng but problam not sold 🙏
Very nice video sir,u2 error code in what is problem,thank you sir
Check inverter pcb voltage
Only mastar dip swich setting
Only mastar dip swich setting malti outdoor selev 1 dip swich setting yas o no
Bagus ah you...
Terima kasih master
Help sar
Bon sar vrvx u7 11
Check outdoor to outdoor unit connections
Hello
Why am I in your country I can get a job
And English after use hind best long before
My name is Mohamed Al-Sadiq Mohamed, VRV refrigeration and air conditioning technician. I am from Egypt. I want to travel to work and work hard. I need help
Please sar 🙏😊
VRV 感觉好难(⊙o⊙)for me
不会难,换了pcb要auto charge然后再test run
Thank you