Mini-Split Heat Pump: Nitrogen Pressure Test

แชร์
ฝัง
  • เผยแพร่เมื่อ 15 ธ.ค. 2024

ความคิดเห็น • 432

  • @JPN850R
    @JPN850R ปีที่แล้ว +6

    Of all vids out there, this was the most straightforward, easy to understand and had no nonsense to waste time.
    In 11 minutes, you've covered everything I needed to refresh my memory.

  • @mikemandus1403
    @mikemandus1403 3 ปีที่แล้ว +36

    Great video and good info. Only 1 issue, at 4:00 he forgot to mention he isolates the tank from the test by closing off the low pressure (blue) valve. You can see him close the valve off.

    • @stuzman52
      @stuzman52  3 ปีที่แล้ว +1

      Thanks Mike!

    • @johncorson6599
      @johncorson6599 2 ปีที่แล้ว

      I questioned that while watching the video and it was hard to see closing the valve .. saw your comment and it was spot on!

    • @robertbroussard4382
      @robertbroussard4382 2 ปีที่แล้ว

      He did that at ~ 2:45

    • @hafizhan8654
      @hafizhan8654 ปีที่แล้ว

      thank you!

  • @chicchoc9
    @chicchoc9 4 ปีที่แล้ว +7

    great video. I learned to do this as a DIYer from older youtube videos which were helpful, and allowed me to install 7 minisplits for myself and family members, but your videos are much better and more clearly explained.. i have another 2 units to do soon so i thought I would brush up.. Glad i found your videos.. you will allow many other DIYers to tackle this as well and save the $1000-2000 they would pay to have a pro do the work in a day... and although some pros are top notch, many others do not nitrogen test nor take the care that a caring DIY homeowner will. Subscribed.

    • @stuzman52
      @stuzman52  4 ปีที่แล้ว

      Thank you very much chicchoc9 s!

    • @matttzzz2
      @matttzzz2 ปีที่แล้ว

      Uhhhh are you licensed to install them!?

  • @youarehere1716
    @youarehere1716 4 ปีที่แล้ว +7

    That's as good as it gets! You explain it very well. Hopefully people are paying *close* attention because after you let refrigerant into the lines through the low-side of the gauge set and adjust the regulator valve to get the line pressure to 200 PSI, you *close off* the low-side valve of the gauge step, which cuts off the feed of nitrogen from the N2 tank, otherwise that would overcome the pressure lost by any leaks and be self-defeating. You don't mention that's what you're doing at that step though, you just crank the gauge blue (low-side) valve closed. and that's a really important step! My Daikin outdoor compressor installation manual says to pressure test at 550 PSI, but don't exceed that. Also recommends holding the pressure for 24 hours but I think it says minimu of 1-2 hrs.. Not sure if all mini-splits can handle 550 PSI, but from what I understand r410a generally reaches a pretty high pressure in mini splits. Anyway the higher PSI test might catch some leaks lower pressures won't, so why not?

    • @stuzman52
      @stuzman52  4 ปีที่แล้ว

      One can use higher pressure, but never exceed the test pressures of the indoor or outdoor coil and use the pressure which is lower. No particular reason for the lower pressure and even if there was a small leak at 200psi, it would have showed up.

    • @Froggability
      @Froggability 4 ปีที่แล้ว

      Ha ! I now notice multitudes of us in the comments have picked up on the “failure to close low side valve” , a mistake Stuzman is unlikely to repeat now

    • @Mike-01234
      @Mike-01234 4 หลายเดือนก่อน +1

      I just installed a Pioneer can't find any spec on the pressure just going to be safe and test to 200 psi check the flares waiting on a regulator picked up a 22cf tank at the welding store. Probably overkill I figured I can use it it to fill tires, and blow stuff off nice to have a high pressure tank don't have to fire up a loud compressor takes forever to fill.

  • @felizdao7913
    @felizdao7913 5 ปีที่แล้ว +4

    If you don't shut off the nitrogen tank, the pressure will keep up 200 psi until the nitrogen tank is depleted. Therefore, this is only good to check for leaking with bubble test or with other leak test devices.

    • @stuzman52
      @stuzman52  4 ปีที่แล้ว +1

      Feliz, you don't have to shut off the valve on the nitrogen tank. The valve is closed off on the manifold gauge set where the nitrogen is going through the compound gauge. If you want to close the valve on the nitrogen tank, you can but it's not necessary.

  • @balokurd17
    @balokurd17 3 ปีที่แล้ว +4

    I've never waited so long to find a leak ! Just a little tip : when you finally release your nitrogen outside, you can do it in one shot by quickly opening your valve, so it's gonna kick all the crap inside more efficiently

  • @EXOVCDS
    @EXOVCDS 6 ปีที่แล้ว +18

    I'm still watching and haven't read the comments... I'm at 4:43 . Could you close the valve on the source tank and watch for pressure drop? A small leak might not drop the needle if you have a constant feed of gas. Back to watching.

    • @EXOVCDS
      @EXOVCDS 6 ปีที่แล้ว +1

      Oops... I missed that you closed the low side valve. 9:30 you opened it again to drain the charge.

    • @stuzman52
      @stuzman52  6 ปีที่แล้ว

      Thomas EXOVCDS I knew you would catch it. Have you done much AC work since your boss will let you guys work on it? Oh, a little tidbit for you regarding R1234YF refrigerant. I figured out what YF stands for. You’re Fucked! Thanks for dropping in Thomas!

    • @EXOVCDS
      @EXOVCDS 6 ปีที่แล้ว

      LOL... that sounds about right (from what I have heard about that stuff). No way my boss is gonna invest in another machine to service those systems. We're still only dabbing with AC. Mainly for when heater cores are done... we have checked some vehicles with lack of AC complaints, but most ended up being control / input related faults as opposed to low on charge / leaks.

    • @satamanschmidt3428
      @satamanschmidt3428 6 ปีที่แล้ว

      I think I mentioned that to you Terry when I questioned you on the wisdom of buying a recovery system with this change coming around the corner. The two refrigerants are completely incompatible therefore you're going to need two machines.

    • @stuzman52
      @stuzman52  6 ปีที่แล้ว

      SATAMAN Schmidt Dennis, I appreciate your thoughts, but I was aware of the two refrigerant types having incompatibility and that you can’t use a R134a machine on R1234YF. I know that it’s flammable and very expensive. I’m not planning on working on vehicles with type refrigerant. EPA mandates that all USA vehicles must use this refrigerant by 2021, Recently I purchased a 2016 vehicle, but I made sure it uses R134a. There will still be quite of ‘new’ vehicles on the road in upcoming years. I realize that R134a will start to cost more as it is being phased out, but that will be a few years. Mercedes along with other European manufacturers have been using this R1234YF for a few now. There was a front end collision with a Mercedes and a refrigerant line split. This refrigerant spewed out onto a hot exhaust manifold and caught on fire. The car burnt to the ground. Mercedes is considering to switching back to R134a. So, who knows what the future may hold.

  • @salvatoregiovanni8967
    @salvatoregiovanni8967 13 วันที่ผ่านมา

    Very well done video. You are slow and methodical about the way you explain things so anyone can understand exactly what you’re doing. One tip, if this is indeed an r-410a heat pump (not an AC only system), your lineset’s flares will indeed see pressures in the 400-500 psi range in heat mode. So if you do a nitrogen pressure test, a higher psi test than what you did may show flare leaks that a lower test pressure may not.

    • @stuzman52
      @stuzman52  3 วันที่ผ่านมา

      Thanks for the comment and have a great day!

  • @satamanschmidt3428
    @satamanschmidt3428 6 ปีที่แล้ว +24

    Terry, I could be wrong but I think you did the pressure test wrong. Now I will admit that the soap bubbles proved that the system wasn't leaking, that's settled, but I feel that you needed to close the valve on the nitrogen bottle to prevent the bottle from replenishing the lost nitrogen there would be if there were any leaks. I don't think that closing the low side valve does much for you because you can't then tell if the leak is happening beyond the valve as the gauge is then isolated from everything downstream from the valve and the gauge itself is being replenished by the nitrogen bottle. For this test to be valid I think you need to close the valve on the nitrogen bottle.

    • @stuzman52
      @stuzman52  6 ปีที่แล้ว +15

      That's okay Dennis and we're all here to learn. When the valves on the manifold gauge set are closed, the nitrogen tank is isolated from the equipment. The gauges are then only reading the pressure inside the system. Even if there is a leak inside the system, the nitrogen tank is not going to replenish the system with any more refrigerant. It's the same if you were going to charge a system with refrigerant. With the valve on the refrigerant tank open, you charge they system. Do you turn off the tank supply valve to measure the pressure? No, because when the manifold gauge valves are closed, you're reading the equipment pressure which is isolated from the main supply pressure on the tank. Here is a link to how manifold gauges work th-cam.com/video/xGQ1OwqEppU/w-d-xo.html And here is a link to a master HVAC tech who is doing the same exact procedure th-cam.com/video/2REIP5Ddn60/w-d-xo.html There's no problem in turning off the main nitrogen supply tank, but it's really not necessary :)

    • @fixy247
      @fixy247 5 ปีที่แล้ว

      Brilliant video, just a question, if I close the nitrogen valve after pressurizing the system. If the pressure is sustained at 200 psi (as in the video), do I still need to do the soap leak test.
      Sustained pressure would mean there are no leaks in the system ?, kindly correct me, if am wrong.

    • @Froggability
      @Froggability 4 ปีที่แล้ว

      Your almost right , the answer: turn off the low side valve. And de-pressurise the nitrogen supply side. You then measure nothing but the machine to the low side gauge. With not the remotest chance of replenishing from the gauge set.

    • @DonBarthel
      @DonBarthel 2 ปีที่แล้ว +9

      He did turn off the gauge set to disconnect the system from the nitrogen bottle but he didn't mention that step. See it at the 4:00 mark.

    • @bkhoavo
      @bkhoavo ปีที่แล้ว +2

      @@DonBarthel 4:00 mark didn't show any turning to close. Thus causing question from lot of people.

  • @wyattoneable
    @wyattoneable 6 ปีที่แล้ว +8

    When everything is completed I want to see you in the air conditioned garage enjoying the cool air. Things are looking really good Terry.

    • @stuzman52
      @stuzman52  6 ปีที่แล้ว

      wyattoneable Yep, everything looking good Wyatt! Only thing left is doing a vacuum and firing it up. Of course for the closure on that video, I’ll be inside the garage. 😀👍

  • @reginaldsotero
    @reginaldsotero 5 ปีที่แล้ว +2

    this is the neatest, well-disciplined, professional installation ever , you rock the hvac industry Sir!

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว +1

      Thank you very much Ray!

    • @yeagermcbipper9008
      @yeagermcbipper9008 4 ปีที่แล้ว

      He's idiot and made multiple mistakes. Not purging his lines, not knowing how to used a high pressure valve. So many mistakes... this video should be taken down.

  • @unionse7en
    @unionse7en 6 หลายเดือนก่อน +1

    Good videos.. 1) He did not mention it, but he did shut off the supply of N2 to the system by turning the low pressure valve off...if you fail to do this the bubble test will still be valid, but the decay test won't be as N2 will still be supplied from the regulator. 2) You could purge the full line set and inside unit by waiting to tighten the upper flare fitting while you let some N2 into the system.. to remove air and moisture. This would give you the best decay test (less effected by temperature changes) I'm no HVAC expert just a Mech Engineer about to install a Mini split.

    • @stuzman52
      @stuzman52  6 หลายเดือนก่อน

      I forgot to mention about closing the low pressure valve, but it was done at the 4:00 timeline. Others have mentioned this also. Thanks for watching and for the comment! And good luck with the installation of your mini-split unit.

  • @tesos2866
    @tesos2866 2 ปีที่แล้ว +2

    While you were at it , I would have cracked the high side nut on the outdoor units and purged the line completely with nitrogen, then later when you get to vacuum testing you are only dealing with nitrogen in the lines.

  • @josephgraham1065
    @josephgraham1065 4 ปีที่แล้ว

    Sir you are a great instructor I have much more confidence on installing my own mini split dual zone after watching all your videos. Thanks for taking the time and sharing

    • @stuzman52
      @stuzman52  4 ปีที่แล้ว

      Thank you Joseph for the kind comments and for watching the videos! Since there are a lot of DIYs who are installing mini-splits, I wanted to give them all the information that would help them in having a successful installation. Good luck on your installation and I'm sure that it will be a great one!

    • @josephgraham1065
      @josephgraham1065 4 ปีที่แล้ว

      @@stuzman52 Well I live in Hawaii so everything is expensive here and I now have 2 kids in college so when my mitsubishi mr slim failed (after 17 years) they quoted me $4750 to replace. I got an off brand 18000 dual zone and with your videos I will save $2400. Much in part because you explained every step so well. Thanks Again I will let you know how the install goes when it gets here.

    • @stuzman52
      @stuzman52  4 ปีที่แล้ว

      joseph graham Sounds good Joseph! Let me know how it goes! 😀👍

    • @josephgraham1065
      @josephgraham1065 4 ปีที่แล้ว

      @@stuzman52 Sir I would like to tell you that I have successfully removed my old system and installed a brand new 18000 BTU Mini Split AC/ Heat Pump with 2 9K zones in the house. In great part because of your videos. Had a few minor problems but was able to get through all of them Thank you so much for taking the time to do these videos. I will be forever grateful and so will my kids when I can pay their tuition because you helped me save money.

    • @stuzman52
      @stuzman52  4 ปีที่แล้ว

      joseph graham That’s great to hear Joseph and glad to hear that you saved money to help your family. Always glad to help and have a great weekend coming up. 😀

  • @kerry4951
    @kerry4951 2 ปีที่แล้ว +2

    Excellent video, thanks for sharing!! Now I need to get my HVAC convinced to do a proper pressure test since I have had past issues with leaks. Id like to see a prolonged length of wait time, more then 15 minutes in my case

    • @stuzman52
      @stuzman52  2 ปีที่แล้ว

      Thank you Eddie for watching the video and for leaving a comment!

  • @cwarbucks
    @cwarbucks ปีที่แล้ว

    Great video, easy to follow, good camera placement.

    • @stuzman52
      @stuzman52  ปีที่แล้ว

      Thank you very much for the comment and have a great day!

  • @doddgarger6806
    @doddgarger6806 4 ปีที่แล้ว +11

    These things run in the 400psi range I would take advantage of having the ability to go at least to 400psi on the pressure test

    • @lordjaashin
      @lordjaashin 3 ปีที่แล้ว +3

      line set and evaporator coil on mini split don't ever see 400 psi in their entire life. so its not a good idea to go above 300 psi cause it will cause more leaks

    • @truthfiend6909
      @truthfiend6909 3 ปีที่แล้ว

      @@lordjaashin hmmm..not even for mini split heatpumps when your eveporator becomes your condenser in the heating season?... could've sworn all mini splits i've seen were all factory pressure tested by at least 500 psi high and 300 psi low

    • @floatybyboaty
      @floatybyboaty 3 ปีที่แล้ว

      Spot on.
      You have to Strength pressure test at 1.43 times, and 1.0 for Tightness Test. This is all dependant on the refrigerant used.
      R32 is pressure tested at 400psi (279.57 x 1.43)
      Testing is carried out in 15 minutes increments up to the max test pressure, then down to tightness test for a slong as possible.
      eg R134a at 32oC = 7 Bar x 1.43 = 10 Bar = 145 psi

    • @lordjaashin
      @lordjaashin 3 ปีที่แล้ว

      @@truthfiend6909 can't say for heatpumps but my mini split user manual only recommends max 250 psi on evap coil and suction line. don't know why.

    • @douglasgomez9047
      @douglasgomez9047 6 หลายเดือนก่อน

      could blow the Fittings with high Pressure the connections

  • @theblaze6682
    @theblaze6682 5 ปีที่แล้ว +4

    Looks like you did not close the bottle after getting the pressure you wanted. Maybe it’s safer to close it. Thanks for the video

  • @krashpass
    @krashpass 5 หลายเดือนก่อน

    WOW, JC Whitney, That takes me back a few decades. They still around??

  • @briansmith6135
    @briansmith6135 2 ปีที่แล้ว +1

    Just noted you didn't purge your hoses before adding the nitrogen to the system?

    • @stuzman52
      @stuzman52  2 ปีที่แล้ว

      HaHa, that's a good one Brian. I also didn't purge the line-set of air before introducing the nitrogen. Have a great day!

  • @Pinoyphilly
    @Pinoyphilly 5 ปีที่แล้ว

    where do I buy my nitrogen and tank? I already bought a nitrogen regulator. Thanks. This is the best and filled with clarity nitrogen testing video on TH-cam.

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว +1

      I had responded to another viewer with the same question so I'll just post a copy of it here for you Freddy. You can buy nitrogen for about $25-30 a tank. If you don't have a tank, then the company will allow you to buy one. I believe the price for the tank and fill it is around $110. When you empty the tank, bring it back and they'll give you another tank already filled. Give them the empty, pay the refill fee and you don't pay for the tank again. I did this through airgas which is in my city. I'm sure that you have one or a similar company if you want to get a tank of nitrogen.

    • @Pinoyphilly
      @Pinoyphilly 5 ปีที่แล้ว

      @@stuzman52 Thank you very much, Sir.

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว

      Freddy Panes Glad to help!

    • @cengeb
      @cengeb 4 ปีที่แล้ว

      @@stuzman52 yes, airgas is all over, lots of local locations

    • @stuzman52
      @stuzman52  4 ปีที่แล้ว

      @@cengeb For sure cengeb!

  • @doddgarger6806
    @doddgarger6806 4 ปีที่แล้ว +1

    Just installed a senville 9k myself held vacuum 2 hours solid, still did a soap and water leak test while running to be double sure... OCD...
    Works fantastic, 120° vent temp 50° ambient that's almost as hot as gas

    • @stuzman52
      @stuzman52  4 ปีที่แล้ว

      You did a great job Dodd! Congratulations!

  • @AKK105
    @AKK105 6 หลายเดือนก่อน

    A very informative and high resolution video. Can you recommend any textbook which explains all the pressure settings and procedures? I don't quite understand why this or that value of pressure are used. Thanks a lot!

    • @stuzman52
      @stuzman52  6 หลายเดือนก่อน

      Sure thing! I can highly recommend two books which can be purchased from www.acservicetech.com/ One of the books is listed for inverter mini-splits and the other is a/c book which also covers heat pumps. You can get both in paper or electronic version and you can get both with workbooks if you like. I have both books and they are filled with a wealth of information. They are also available on Amazon, but the price is the same. Good luck with your education on a/c systems.

    • @AKK105
      @AKK105 6 หลายเดือนก่อน

      Thanks a lot!

    • @AKK105
      @AKK105 6 หลายเดือนก่อน

      Are you a professor in university?

    • @stuzman52
      @stuzman52  6 หลายเดือนก่อน

      @@AKK105 I'm a retired electrical controls engineer. And have extensive background in other fields also. Have a great day!

    • @stuzman52
      @stuzman52  6 หลายเดือนก่อน

      @@AKK105 You are welcome!

  • @edsmith4414
    @edsmith4414 5 ปีที่แล้ว +1

    Amateur question: If I don't have a gauge set, could I connect the nitrogen directly to the mini-split port and use the gauge on the nitrogen regulator to read by ? I'm assuming I'd pressurize to 200psi on the regulator gauge, the shut the valve on the tank, and if it holds good for 15 minute or so, I'd be good to go ??
    Want to install a couple of mini-splits fro my own house, and can't really see buying a set of gauges since the unit is pre-charged. Already bought a 40cf bottle of nitrogen & regulator set + a decent Robinair vacuum pump & low micron gauge for the next step (evacuating the system before turning the gas loose). The line runs are short, so no extra freon will need to be added.

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว +1

      You could do that Ed but the gauges on the nitrogen bottle wouldn't have the resolution unless you had a pretty big leak. More importantly, you would be using a bubble/soap solution around the fittings to find the leaks. Good luck on your installation!

    • @edsmith4414
      @edsmith4414 5 ปีที่แล้ว

      @@stuzman52 OK...thanks for the reply ! And GREAT video by the way. Thanks for the time and effort you put into it.

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว

      Ed Smith Thank you very much Ed! 😀

  • @spelunkerd
    @spelunkerd 6 ปีที่แล้ว +1

    In a heat pump, I believe flow is reversed when switching from heating to AC. So, the high side must become the low side. In our home heat pump the two lines have different diameters, usually the low side is big diameter line and the high is small. If flow is swapped every season, why don't they have lines with the same diameter? Won't a big diameter high pressure line cause some kind of problem?

    • @stuzman52
      @stuzman52  6 ปีที่แล้ว

      spelunkerd Your operation about a heat pump is correct. Evidently the diameters of the lines isn’t an issue as all the lines I’ve seen on heat pumps have two different diameters. I don’t have a good answer to why they wouldn’t be the same. Good question!

    • @Froggability
      @Froggability 4 ปีที่แล้ว +1

      Because the larger line is always vapour and the smaller line is always liquid. Regardless of whether you’re in heating or cooling

  • @mcketim
    @mcketim 2 ปีที่แล้ว +1

    thanks for the video. Quick question. Do you need those yellow jacket gauges? The tank regulator holds at 200psi, isn't that telling you there is no pressure leak?

    • @stuzman52
      @stuzman52  2 ปีที่แล้ว +1

      You could get away without using the manifold gauges, but they do offer a higher resolution than the gauge on the regulator. Thanks for watching Tim and have a great day!

  • @issamadam9352
    @issamadam9352 2 ปีที่แล้ว

    Hi good job,but you didn't tell how to put back the Schrader valve.

    • @stuzman52
      @stuzman52  2 ปีที่แล้ว +1

      Thank you for watching the video. The schrader valve is installed in the next video after the system is pulled into a vacuum. You can watch the procedure here th-cam.com/video/vSw-AWqHW0Y/w-d-xo.html

  • @tulio3571
    @tulio3571 5 ปีที่แล้ว +1

    What is the difference between the nitrogen pressure test and the vacuum test ,what are they for? THANKS

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว

      Using nitrogen allows one to pressure test the system by using the gauges for a pressure drop which indicates a leak, or by using bubbles to find a leak. The vacuum test is to remove all the air which removes water vapor. Leaving air in the system will allow the water vapor to mix with refrigerant oil which creates an acid that can attack the metallic parts of the compressor such as the bearings. This of course would shorten the life of the compressor.

    • @tulio3571
      @tulio3571 5 ปีที่แล้ว

      @@stuzman52 . if i cant do the nitrogen because i dont have the equipment ,wouldnt a vacuum test tell me if i have a leak ? thank you

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว

      mt In theory, yes, but I can remember where I pulled a vacuum and left it overnight. Checked the next morning and gauges looked good. Charged it with refrigerant and about a week later, I discovered there was a very small leak. So, the nitrogen test has enough pressure to find those small leaks. You can do the job with just a vacuum, but just wanted you to keep the other info in mind.

  • @Jonehughes
    @Jonehughes 29 วันที่ผ่านมา

    Is this test that you are showing also pressurizing the ODU at the same time
    Or are you bypassing the ODU and just testing the line set and IDU

    • @stuzman52
      @stuzman52  26 วันที่ผ่านมา +1

      When the unit arrives, the outdoor unit will contain the refrigerant with the valves closed to keep the refrigerant inside the unit. When testing for leaks with nitrogen, you are checking all of the line-set fittings plus the indoor unit. Since the indoor unit has already been checked at the factory for leaks, one will concentrate on the line-set fittings. And the same holds true for the outdoor unit since it would have been checked for leaks at the factory.

    • @Jonehughes
      @Jonehughes 26 วันที่ผ่านมา

      ​@@stuzman52I'm not sure why I asked that question it's perfectly clear what you guys were doing I was thinking something else in my head but let me explain and hopefully you can give me a good answer The refrigerant was lost and the guy took it out and installed a new system he then called me over to come get it and it sat there for 5 or 6 hours after he took it apart and so the first thing I wanted to do was use the Allen wrench to close off the ODU from any outdoor debris and weather getting into it
      And then I sealed off the line set and also the IDU
      I want to test them now and see if I can find out how it leaked
      I didn't see any oil on anything not on the ODU IDU or line set so I couldn't tell automatically where it was leaking from
      I ordered a nitrogen bottle and a regulator
      And when it gets here I want to test the line set the IDU and the ODU
      If I hook it up the same way you did
      and just open up the ODU valves with the Allen wrench
      Will that work in testing the ODU also
      Or does the ODU contain some kind of oil or something else that might cause a problem if I pump in 200 psi of nitrogen

    • @stuzman52
      @stuzman52  24 วันที่ผ่านมา +1

      ​@@Jonehughes I assume that since he changed the outdoor unit, there was a leak in it. I wouldn't bother hooking it back up to the line-set as you can charge the outdoor unit by itself with nitrogen. Be sure to take the outside covers off to get access to all the plumbing and to the thermostatic valve, pressure sensors, etc. Good luck on what you find!

    • @Jonehughes
      @Jonehughes 24 วันที่ผ่านมา

      @stuzman52 thank you
      that's very helpful
      I don't know why I didn't think of that
      but that's why I have you 😍🥰

    • @stuzman52
      @stuzman52  24 วันที่ผ่านมา +1

      @@Jonehughes Glad to help and have a super great day!

  • @KevinRoisin
    @KevinRoisin ปีที่แล้ว +1

    Fantastic video, thank you for providing this resource. One question- at the start, do you need to remove the schrader core, or does the schrader core remain in the service port for the duration of the test, since it's a 1-way valve that lets the high pressure nitrogen in?

    • @stuzman52
      @stuzman52  ปีที่แล้ว

      Hi Kevin and hope you're doing well. The biggest reason to remove the schrader valve is for the next step where the air is removed using a vacuum pump. With the valve removed, it takes considerably less time since you won't have that restriction. You could leave the schrader valve in, but it would take longer to evacuate the system. Have a great day!

  • @briekhnaa
    @briekhnaa ปีที่แล้ว

    If valves O rings are damaged and charged. In that case how will we vacuum condenser , accumulator etc ?

  • @Mike-01234
    @Mike-01234 4 หลายเดือนก่อน

    You could also just use the regulator gauge by shutting the tank valve off the regulator gauge will go down if there is a leak.

  • @jrm163
    @jrm163 2 ปีที่แล้ว

    Good information! One question is, since the pressure doesn’t drop, why do we still need to do bubble test? They seem duplicate to me. Thanks!

    • @stuzman52
      @stuzman52  2 ปีที่แล้ว +1

      When using an analog gauges, it could take awhile to be able to notice a pressure drop. If I was using digital gauges, the pressure drop would have been noticeable earlier. With the bubble test, it's just another assurance, that there isn't a leak. It's more of a peace of mind that the system is leak free before opening those valves. Have a great day!

  • @douglasthompson2740
    @douglasthompson2740 3 ปีที่แล้ว

    When you began the pressure check you never said or showed closing the valve? You said leave it for ten minutes and check it but with the tank still on and open it would just replace any leaked pressure?? I don't see the valving necessary to close off the system with a gauge included to actually test the pressure???

    • @stuzman52
      @stuzman52  3 ปีที่แล้ว

      Hi Douglas! It may appear that I didn't close any valve for the nitrogen. I probably should have mentioned it, but I show closing off the low pressure valve on the manifold set at timeline 4:00. Have a great day!

  • @135taz
    @135taz ปีที่แล้ว

    Personally, I would do a drop test for a few hours in addition to soap testing the fittings. My current mini split system says to test for several hours.
    Simple to do. Just shut off the nitrogen once you have your pressure (200# in this case). Crack a fitting to verify the gauge is not stuck. Visually observe the gauge drop a little. Tighten fitting and allow the pressure to sit for a few hours. Nitrogen will not expand /contract like "atmospheric air". So, ambient atmospheric temperature changes should not be observed in the gauge. Check on it after 15 minutes, 1 hour. If you have a pressure drop you have a leak. Pressure increase might mean the nitrogen valve is not completely off or sealed or ambient temperature increase causing increase in pressure (not likely with nitrogen). This will allow you to test all of the system. Areas that are sealed and lines that are insulated. Not just the fittings.

    • @stuzman52
      @stuzman52  ปีที่แล้ว

      Thank you for the comments and have a great day!

  • @mid-hudsontoolworks2022
    @mid-hudsontoolworks2022 5 ปีที่แล้ว +1

    Very informative, thanks for posting this. Any chance you could note part numbers for the equipment you used to pressure test this mini split?

  • @cansno100
    @cansno100 2 หลายเดือนก่อน

    Just wondering. A lot of installers say not to coil excess line set vertically due to possibility of oil pooling which I understand. So , what about when the inside unit is lower than the outside unit as with a basement install? Why doesn't the oil pool in the head?

    • @stuzman52
      @stuzman52  2 หลายเดือนก่อน

      I'm trying to think of an installation where the indoor unit would be lower than the outdoor unit. Even with a basement installation, I can't see how the indoor unit would be lower than the outside unit. Sure, there are installations where dirt is covered higher on three of the walls. But, that would be considered a crawl space. I can't think of the repercussions if the unit is lower than the outside unit. Maybe nothing will happen to the oil and the refrigerant pressure will push it through. I haven't run into an installation where the indoor unit is lower than the outside unit.

    • @CraigHiscock
      @CraigHiscock 2 หลายเดือนก่อน

      ​@stuzman52 Around here, a lot of full 8ft concrete basements are backfilled up to 6 and 7 ft. So the inside head has to be lower than the outside.

  • @hugosafar
    @hugosafar 4 ปีที่แล้ว +1

    The bubble test is fine. But as far as pressure drop, it seems to me that you kept the nitrogen tank ooen...so IF there was a leak nitrogen would keep coming from the tank, keeping pressure constant....at least for some time, depending of course of how bad the leak was...

    • @stuzman52
      @stuzman52  4 ปีที่แล้ว +1

      Although the nitrogen tank valve was left open, I had the valve closed off on the low side of the manifold gauge set. One can close the valve on the tank if it's desired.

    • @hugosafar
      @hugosafar 4 ปีที่แล้ว

      Understood, thanks Sir

  • @OldSchoolLFCGeezer
    @OldSchoolLFCGeezer 4 หลายเดือนก่อน

    Hi Terry ~ As with your vacuum test video, I really enjoy your down to earth, no BS, way of explaining what you're doing while you work. The main question that I came away with after watching this particular video, however, is the capacity of your N2 (Nitrogen) tank? Another thing that has me wondering is, for folks like us who live in very cold climates, is the minimum test pressure to apply for leak testing heating systems. To clarify, I've been told that a 410A mini split system can operate at pressures as high as 400 PSI during the winter, so I'm thinking that one may want to leak test a new mini split system at 400 PSI instead of 200 PSI? Do you have any thoughts about this, sir?

    • @stuzman52
      @stuzman52  4 หลายเดือนก่อน

      Most people think that you must pressurize the system to the maximum pressure that the system will operate. This implies that a leak can not be found unless it has this maximum pressure. 200 psi is more than enough to find a leak, even a small one. However, if one wants to increase the pressure then one can do it. Thanks for watching and sharing a comment. Have a great day!

  • @hafizhan8654
    @hafizhan8654 ปีที่แล้ว

    thank you for this precious gem !

    • @stuzman52
      @stuzman52  ปีที่แล้ว +1

      Thank you hafizhan for the comment and have a great day!

  • @justinrrizzo
    @justinrrizzo ปีที่แล้ว

    Is there a way to make this test on the unit BEFORE install? I have a store-return unit with damaged fins, and want to ensure it does not leak before purchasing further equipment.

    • @stuzman52
      @stuzman52  ปีที่แล้ว

      Yes, you should be able to still pressure test the unit.

  • @Froggability
    @Froggability 4 ปีที่แล้ว

    Im curious 1/ the need to remove the schrader?
    2/ was the LP shut off at 4:02.? Nothing was said. But it's a critical juncture meaning nitro doesn't top itself up.
    3/ how can you be satisfied using foamy bubble check? Micro sized bubbles will never been seen, get non foamed liquid.

    • @stuzman52
      @stuzman52  4 ปีที่แล้ว

      Removing the schrader valve was in preparation for the next step, (next video) to pull a vacuum. Removing the valve allows for a faster and deeper vacuum. Yes, the low pressure gauge was closed on the manifold gauge set. Using a gel to check for bubbles is a standard used in the field. Also, the low pressure gauge was monitored for a pressure drop. And the unit is still working well.

  • @haywardsautomotive6156
    @haywardsautomotive6156 6 ปีที่แล้ว

    Vacuum, service and you'll have a nice cool garage in the summer and cozy warm in the winter!! Looking good Terry!!

    • @stuzman52
      @stuzman52  6 ปีที่แล้ว

      I was working in the garage yesterday with the wife doing a little organizing, and it was very nice inside for sure. Thanks Bob!

  • @jayf9259
    @jayf9259 3 ปีที่แล้ว +1

    Great, informative video series on how to install a mini split. One question - where did you buy your nitrogen tank and gauges, and where would one get a nitrogen tank filled? Thanks

    • @stuzman52
      @stuzman52  3 ปีที่แล้ว +1

      The tank and nitrogen was purchased and AirGas Supply which is a national chain. You probably have one near you. The gauges and regulator for tank were purchased from Amazon.

  • @mosfet500
    @mosfet500 ปีที่แล้ว

    Hi Stuzman, thanks for this video.
    I watched it again and I noticed you didn't shut off the nitrogen tank when doing the pressure test. If there is a leak then wouldn't the nitrogen keep the pressure level up? Shouldn't you shut off the tank while doing the test?
    thanks

    • @stuzman52
      @stuzman52  ปีที่แล้ว

      I did close off the valve on the manifold gauge set. Take a look at the timeline at 4:00 and you'll see that. Have a great day!

    • @mosfet500
      @mosfet500 ปีที่แล้ว

      @@stuzman52 Okay, thanks! I had to watch it again to see you do it. Thanks again for your help.

  • @karlambrose261
    @karlambrose261 2 ปีที่แล้ว

    so doesn't the line set and indoor coil have a little air and moisture in it before you even add the nitrogen? If so , how is it purged before the nitro goes in ? Otherwise you have a mixture of nitro, air and moisture in the line and unit ?

    • @stuzman52
      @stuzman52  2 ปีที่แล้ว

      Yes, there is a small amount of air and moisture within in the system. In the field, the nitrogen is added to the line-set to check for leaks using the pressure. Afterwards, the nitrogen is released and then a vacuum pump is attached which removes the air and moisture.

  • @relaxingsounds3909
    @relaxingsounds3909 4 ปีที่แล้ว

    Many thanks for this I’ve shared this with som of my work colleagues in the Uk

    • @stuzman52
      @stuzman52  4 ปีที่แล้ว

      Glad to hear the video was helpful!

  • @electrake2063
    @electrake2063 2 ปีที่แล้ว

    @4:50... you never turned off the supply of nitrogen! It will not show a leak if you do not turn off the supply and cap off the flow from the tank. Maybe I missed it?

    • @stuzman52
      @stuzman52  2 ปีที่แล้ว

      You don't have to turn the supply off at the tank. I opted to turn it off at the manifold gauge set on the low pressure side at timeline 4:01. Thanks for dropping in and sharing a comment. Have a great day!

  • @Manavsain00
    @Manavsain00 5 ปีที่แล้ว +1

    Can we use nitrogen by low pressure gauge

  • @joeoehm4341
    @joeoehm4341 10 หลายเดือนก่อน

    Can I close the valve of the nitrogen bottle, as soon as the pressure for the system has been set? This should not affect the pressure test? Or is there something against it?

    • @stuzman52
      @stuzman52  10 หลายเดือนก่อน +1

      Yes sir, you can close the valve on the nitrogen tank and will not effect the test. I opted to use the valve on the manifold gauge set. Either method is fine to use. Have a great day!

  • @mikehawk825
    @mikehawk825 2 ปีที่แล้ว

    Don't you have to turn off the nitrogen tank to watch if the pressure will drop? If there is a small leak the tank will just keep filling the system and keep the pressure at 200PSI?

    • @stuzman52
      @stuzman52  2 ปีที่แล้ว +1

      Hi Mike, I didn't mention it in the video, but I did close the valve at the 4:00 mark. I could have closed the valve at the nitrogen tank or which is what I did is close the low pressure valve on the manifold gauge set. Have a great day!

    • @mikehawk825
      @mikehawk825 2 ปีที่แล้ว

      @@stuzman52 Thanks I saw the other reply and rewatched the video - Thanks!!

  • @lukecrawford9180
    @lukecrawford9180 หลายเดือนก่อน

    did you vacuum out all of the air from the line sets before pressure testing with nitrogen?

    • @stuzman52
      @stuzman52  หลายเดือนก่อน

      No, you pressure test with nitrogen first and then vacuum afterwards provided you don't find a leak.

  • @John.Paulis
    @John.Paulis ปีที่แล้ว

    So is it necessary to vacuum the lines after the nitrogen test? Seems like it might not be necessary

    • @stuzman52
      @stuzman52  ปีที่แล้ว +1

      Yes Jake, you MUST vacuum the system after doing the nitrogen test. Otherwise, you'll have air in the system. Have a great day!

  • @kirill_gusev
    @kirill_gusev ปีที่แล้ว

    Thank you for putting these very detailed videos for everyone! I'm about to attempt to replace the outdoor unit and already swapped those and connected lines and power. Have a couple questions as I want to be clear on couple things before continue:
    1. I assume this is new pre-charged system. So it's OK to test lines (and indoor unit) when both valves (under caps) are closed?
    2. I don't need to do vacuum procedure prior to pressure test, right? Just connect lines to unit and proceed following steps in video?
    Thanks!

    • @stuzman52
      @stuzman52  ปีที่แล้ว +1

      Yes, you will leave both valves closed when you're testing the line-set and indoor unit for leaks. It's always a good idea to pressurize the system with nitrogen because small leaks will be revealed when it's under the nitrogen pressure. If you ignore this step and proceed to vacuum the system, it may appear to hold vacuum for a period of time. But I can remember several times where I just vacuumed the system without pressurizing it with nitrogen. Pressure stayed around 30" Hg for several hours. Opened the valves and about a month later, I found out that I had a very small leak. And what if you just vacuumed the system and saw that the pressure didn't hold? How are you going to find a leak under vacuum? Not possible....So, pressurize the system with nitrogen to ensure there are no leaks and then proceed with the vacuum. Have a great day!

    • @kirill_gusev
      @kirill_gusev ปีที่แล้ว +1

      @@stuzman52 Thank you !!!

    • @stuzman52
      @stuzman52  ปีที่แล้ว

      @@kirill_gusev Glad to help!

  • @peaceinwartimeable
    @peaceinwartimeable 11 หลายเดือนก่อน

    I agree that the absolute test would include closing the nitrogen bottle. However the manifold trapped the nitrogen. If any case the manifold was faulty the tank being open could botch the test.

  • @pchmbrs7
    @pchmbrs7 11 หลายเดือนก่อน

    how frequently does a system test fine with pressure and vacuum and then later develop a leak at flare joint?
    if pressure testing good with a digital probe and holding under 500 microns with the micron gauge should one be confident in the flare joint longevity?

    • @stuzman52
      @stuzman52  11 หลายเดือนก่อน

      I would suppose there's always a chance that you could have a very small leak and have a leak later down the road, but it's not likely. If you leave it pressurize say for an hour and especially if you're using digital gauges, it will show up. Now, looking at it from the other end where you only vacuum the system with a micron gauge and it holds steady under 500 microns, then you most likely don't have a leak as the micron gauge is very sensitive to any pressure changes. But, if you do have a leak while under this scenario, you're back to pressurizing the system to find the leak. So, to save time, pressurize the system to check for leaks and if that looks good, vacuum the system. And Merry Christmas and Happy New Year to you and your family!

  • @DmaxH.Country
    @DmaxH.Country 3 หลายเดือนก่อน

    Where do you get the fancy adapter rig on low press side or nitrogen entrance?

    • @stuzman52
      @stuzman52  3 หลายเดือนก่อน

      I assume that you're talking about the adapter which connects to the low pressure side. This is a 5/16" adapter instead of the typical 1/4" adapter that connects hoses. You should be able to find them on Amazon.

  • @larryhalleck2432
    @larryhalleck2432 ปีที่แล้ว

    I was always told to pressure test to 400-500 PSI when using flare fittings

    • @stuzman52
      @stuzman52  ปีที่แล้ว

      Hi Larry! The manufacturer has already tested the indoor and outdoor coil at these high pressures. The only thing that we're testing is the flared fittings which do not need these high pressures. 200-300 psi is more than enough for testing for very small leaks. Of course, if you want to test at the higher pressures, then make sure the pressures do not exceed the test pressures which are on the indoor and outdoor units.

  • @msaeed8031
    @msaeed8031 5 ปีที่แล้ว +1

    In this test both service valve LKEY WILL BE CLOSE OR OPEN? OR CLOSE ONLY SUCTION LINE LKEY CLOSE?

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว +3

      If I understand your question, both valves on the condenser are closed when you do a pressure test. They will be closed from the factory when the unit arrives. Then when the pressure test is okay and a vacuum has been pulled on the system, then you open both valves on the condenser.

    • @msaeed8031
      @msaeed8031 5 ปีที่แล้ว

      @@stuzman52 Good work.... Thanks sir.

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว +1

      m saeed Thank you!

  • @klanda1095
    @klanda1095 4 ปีที่แล้ว +1

    Hi , do you have a video on pressure testing and vacuum of a 36000 BTU ( 4 } four zone mini split ( four 9000 BTU indoor unit ) Not sure if all 4 line sets need to be vacuumed individually or is there way to do all one shot ?
    Thanks Jay

    • @stuzman52
      @stuzman52  4 ปีที่แล้ว

      Sorry I don't have a video for multi-zone systems. I've never done one of these systems, but would think that the manual would offer some information about it. My guess it that since each system is isolated, each would have to be tested individually. If the manual doesn't offer any help, you could call the manufacturer and I'm sure they could point you in the right direction.

  • @msaeed8031
    @msaeed8031 5 ปีที่แล้ว

    Can we use nitrogen gass pressure test in compressor and condenser coil(outdoor unit) also, I mean Nitrogen Gass will be dangerous for compressor winding or pump?

  • @Tarnimo
    @Tarnimo 5 ปีที่แล้ว

    this was a great video put together very well I need to do this exact procedure on Sunday thank you very much for posting this

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว

      Thank you and good luck on getting your unit installed!

    • @Tarnimo
      @Tarnimo 5 ปีที่แล้ว

      @@stuzman52 thank you everything went great

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว

      k adel Glad to hear all went well!

  • @philsmesrud7182
    @philsmesrud7182 5 ปีที่แล้ว

    Why do you need the manifold gauges? Can't you connect the nitrogen tank with its gauge and hose directly to the service port?

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว +2

      Sorry for the delay Phil as TH-cam did not contact me. The manifold gauges have a higher resolution than the gauges on the tank which makes it a little easier to see small leaks. :)

  • @bukownl
    @bukownl 3 ปีที่แล้ว

    No wonder it was holding the pressure, you did not shut off the valve between pressure regulator and manifold. In that case even with a leak, pressure stays as set.

    • @stuzman52
      @stuzman52  3 ปีที่แล้ว

      Maciej, it may appear that I didn't shut off the nitrogen, but that is not the case. I didn't mention it in the video, but the low-pressure valve on the manifold was closed at the timeline of 4:05 in the video. Thank you for the comment!

  • @scottmorales3341
    @scottmorales3341 3 ปีที่แล้ว

    Why are you using the red, blue and yellow guages rather than just using the pressure guage that's attached to your nitrogen tank?

    • @stuzman52
      @stuzman52  3 ปีที่แล้ว +1

      I'm actually more focused on the compound gauge on the side connected to the blue line. The reason is that the gauge on the nitrogen tank doesn't have the resolution to see small pressure drops as it goes to 4000 psi.

    • @scottmorales3341
      @scottmorales3341 3 ปีที่แล้ว

      @@stuzman52 thanks!

  • @briekhnaa
    @briekhnaa ปีที่แล้ว

    Were valves towards compressor and condenser closed during this test?

    • @stuzman52
      @stuzman52  ปีที่แล้ว +1

      Yes, that is correct, the valves are closed during this test and they remain closed when you're doing an evacuation of the system, (in other words when you pull a vacuum on the system).

    • @briekhnaa
      @briekhnaa ปีที่แล้ว

      @@stuzman52 thank you.

    • @stuzman52
      @stuzman52  ปีที่แล้ว

      @@briekhnaa You are welcome!

  • @nandorhadhazy4345
    @nandorhadhazy4345 4 ปีที่แล้ว

    Dear stuzman! Why are you using only 200 psi? Could you Tell me the refrigenerant gas inside the ac? Thanks

    • @stuzman52
      @stuzman52  4 ปีที่แล้ว

      You could use a higher pressure if you like, but stay under the lowest test pressure of the outdoor or indoor unit. This was a R410a unit.

  • @worldline7147
    @worldline7147 3 หลายเดือนก่อน

    Can you make that red hose connection with a hose that does not have a ball valve?

    • @stuzman52
      @stuzman52  3 หลายเดือนก่อน

      Yes, you can use the red hose instead of the blue for the test if you like.

    • @worldline7147
      @worldline7147 3 หลายเดือนก่อน

      @@stuzman52 I meant the connection that you made entirely on the High Side of the gauge set - connecting it to itself in a loop - with the red hose. So, my questions would be: (1) could I use a hose for this connection that did NOT have its own ball valve?, and (2) Do I even need to connect a hose at all on the High Side of the gauge set ? (Obviously, in any case, the High Side valve on that (right hand) side of the gauge set is closed.)

    • @stuzman52
      @stuzman52  3 หลายเดือนก่อน

      @@worldline7147 As seen in the video, I'm not using the high-side gauge. And of course, you don't need to have a shut-off valve on the hose as the gauge on the manifold will isolate any pressure coming through the hose. No, it's not necessary to have a hose on the high pressure side. Just make sure that the gauge on the high side of the manifold is closed. Sounds like you got it! Have a good one!

    • @worldline7147
      @worldline7147 3 หลายเดือนก่อน

      @@stuzman52 Thank-you.

    • @stuzman52
      @stuzman52  2 หลายเดือนก่อน

      @@worldline7147 You are welcome!

  • @Badgertronix
    @Badgertronix 6 ปีที่แล้ว +1

    Nice work Terry, looks good to go.

    • @stuzman52
      @stuzman52  6 ปีที่แล้ว

      Thank you Jonathan!

  • @johannesvangalen2300
    @johannesvangalen2300 3 ปีที่แล้ว

    Are you using Dry nitrogen?
    If so, where can you purchase?
    Thanks

  • @liotcik
    @liotcik 2 ปีที่แล้ว

    Pressure test is not needed for home users and factory build units when professional tooling is used for pipes. The test came from engineered and build cooling systems where piping is soldered all around.

    • @stuzman52
      @stuzman52  2 ปีที่แล้ว

      There would be some service technicians out there who would disagree with you. I would much rather test a system for leaks rather than just dump the refrigerant into the line-set and then find out later there is a leak. And one could look at brazed joints that if they were done professionally correct, then you wouldn't need to test those joints for leaks. Of course, whether to pressure test the system or not is up to the individual.

  • @tulio3571
    @tulio3571 5 ปีที่แล้ว

    Hi sir ,would want to hear your opinion on my issue ,here we go . I have a two story home with two central ac systems .one for first floor , one for second floor ,my second floor condenser just failed ,not worth fixing it uses the r22 gas.I can replace with a 4 ton rheem for about $4000 , or just replace it with 3 zone mini split ,one for each bedroom ,i feel i will have better control as far as i dont have to have the whole second floor cool when only one person is in the bedroom.The mini splits would cost about the same .But i heard that since i already have the duct work ,a central would be better . thanks again

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว

      That's a toss up for sure! I would go for what your needs are. Since you want better control, maybe the mini-splits could give you better control. But you might want to look into zone dampers which can go on your existing duct for the Rheem that would do the same thing. You may want to take advantage of your existing duct work since you have it.

  • @brandonbass1457
    @brandonbass1457 ปีที่แล้ว

    Thank you for your video I was successful at testing my line thanks forYour time and making your video it was brilliant. Keep up the good work.

    • @stuzman52
      @stuzman52  ปีที่แล้ว

      Glad to hear that it all worked out for you Brandon! Have a great day!

  • @guychapman4037
    @guychapman4037 5 หลายเดือนก่อน

    Just wondering about the 200 psi charge. Is it sufficient for extreme temps and pressures ? Ive been testing systems a 300 psi for minimum of 1 hour in a leak test fir reoairs and installs. If I could save time and some nitrogen...everything counts when working for yourself.

    • @stuzman52
      @stuzman52  5 หลายเดือนก่อน

      200 psi should be enough pressure to find the smallest leaks. Of course, some people may disagree but I've found that this pressure was sufficient. Have a great day!

  • @ozzstars_cars
    @ozzstars_cars 6 ปีที่แล้ว +1

    Now it's time to evacuate, charge and enjoy the cool fruit of your labor!

    • @stuzman52
      @stuzman52  6 ปีที่แล้ว +1

      You are correct Glen; almost there now :)

  • @volvot5turbo
    @volvot5turbo ปีที่แล้ว

    do you have to remove the schrader valve when pressure testing or vacuum testing? Also my iQool9 (electriq) has no info on what pressures to test to so I have no idea whether 200psi or 300psi or even maybe 150psi?

    • @stuzman52
      @stuzman52  ปีที่แล้ว +1

      No, it's not a requirement that you remove the schrader valve. The reason for removing it is to allow a faster evacuation of the air in the line-set to minimize the restriction. If you want to go a little higher pressure than me, you could use 300psi, but the other pressures are fine too. Have a great day!

  • @SamuelBachorik-Mrtapo8-ApeX
    @SamuelBachorik-Mrtapo8-ApeX 2 ปีที่แล้ว

    Hi, why some of guys don't do pressure test ? They just do vacuum test. What is the difference ? Isn't vacuum test enough ? thank you

    • @stuzman52
      @stuzman52  2 ปีที่แล้ว

      Well, if you eliminate one of the tests such as a pressure test, that's one less thing to do. And you can move on to the next job. You always want to do a pressure test before you vacuum. Having a system under a vacuum will not detect small leaks. And if you did see a leak under a vacuum, what will you do now to find a leak while under a vacuum? The only way is to pressurize the system. Thanks for the comment and have a great day!

    • @SamuelBachorik-Mrtapo8-ApeX
      @SamuelBachorik-Mrtapo8-ApeX 2 ปีที่แล้ว

      @@stuzman52 Hi, thanks for reply, one more question, why did you do it with nitrogen? Is it not enough to pump air with a compressor?

    • @stuzman52
      @stuzman52  2 ปีที่แล้ว +1

      @@SamuelBachorik-Mrtapo8-ApeX Some people do use compressed air, but there is always water vapor inside the compressed air which is being introduced into the system. Even though you may not see it, it's there. Although, the system has air inside it, why throw more into it. Another reason is that you want at least 200 psi or even more psi depending on the system to pressure check for small leaks that the system may have. Most air compressors will not get to these higher pressures. Also, nitrogen is an inert gas which is very dry, (no water vapor) and will not react with any metals in the system. Some people will use argon or CO2 which is fine because they are inert and are very dry. Have a great day Samuel!

  • @loudsubz
    @loudsubz 2 หลายเดือนก่อน

    Is 200 psi standard or should you go higher or lower depending on what your units nameplate says?

    • @stuzman52
      @stuzman52  2 หลายเดือนก่อน

      200 psi is not a standard. You can higher or lower, but never exceed the maximum working pressure of the unit(s) being tested.

  • @UnkyjoesPlayhouse
    @UnkyjoesPlayhouse 5 ปีที่แล้ว

    I don't understand why you would only test up to 200psi, in heat mode the pressures are closer to 450-500psi on the high side, I know it is a common procedure for a leak test but in my way of thinking you should at least get the test pressures up to operating pressures, your thoughts?

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว

      You could set the pressure higher as you mention and should be fine. I believe most people look at it if there's a leak, at 200psi you should be able to see it. Of course, with the higher pressure, you probably can find it quicker because of bigger bubbles. :) Seems like a lot of techs use 200psi for a leak test as shown here hvac-talk.com/vbb/showthread.php?1273751-Pressure-test-and-vacuum-on-split-systems

    • @Froggability
      @Froggability 4 ปีที่แล้ว +1

      The molecule size of nitrogen is far smaller than that of the hfc molecule and the leak will show up at 200 psi

  • @mohaalgha3397
    @mohaalgha3397 4 ปีที่แล้ว +1

    Waleed7rrag RRAG
    I do thank you very much for your excellent instructions and great detailed explanations. You are during your video answering all the what, why, how and what not to do with great details and explanations. I must say the video recording very sharp and pleasant. Having said that, if you would please answer a few questions:
    1. As you know the mini split AC of all brands and kind has no high side shredder valve and I do not know why, so is it good idea to install one out side the system near the low side shredder valve?
    2. I have a mini split AC under full maintenance including a leak repair on the condenser, as you know the metering device is just at the end of the condenser going to the evaporator, in this case is it OK to feed nitrogen gas from the low side all the way to the condenser to test the condenser leak repair? will nitrogen pass through metering device? and if so will it affect the metering device and or the high side of the compressor?
    3. After doing system and line set vacuuming, is their a need to add 2 ounces or may be less of a compressor oil? I can not find any sold information on this issue?
    Last but not least, thank you very much for teaching and helping so many people !!!

    • @stuzman52
      @stuzman52  4 ปีที่แล้ว +1

      For question 1, I'll refer you to an article by Craig who is a HVACR technician about why there isn't a high side service valve, and I would not install a valve on this side as it's not needed and you're not going to gain anything from it. Here is the link to his article along with many others. You'll find the information about the valve further down in the article www.acservicetech.com/post/checking-the-charge-of-a-mini-split-unit Also, you can get more useful information from his TH-cam channel located here. th-cam.com/channels/OZR-1IqsAer9wzlvFgb4mA.html?disable_polymer=1
      Question 2: When you're checking the condenser for leaks, I would use an ultrasonic leak detector or you could use a sniffer while the unit is running. Although a bubble test may work, you will have to cover a larger area covering both sides of the outdoor coil. This would be the best method to check for a leak while the unit is running. And you may not have a leak. The procedure you're describing with nitrogen will require you to recover all the refrigerant, fill the system with nitrogen, check for leaks using ultrasonics or with bubbles, pull a vacuum and finally recharge the system with refrigerant by weighing it. That would be a lot of wasted time if you find that you don't have a leak. If you did have a leak, you would have to do all of the above of course. But just use the first method and you only do the second method if you find that you have a leak. Putting the nitrogen in the system would pass through the metering device so no problem there.
      Question 3: When you have a leak, I would not worry about adding oil, because you don't know how much leaked out. During recovery of the refrigerant, the recovery unit may pull some oil out, and it's permissible to add back in the amount taken out. In other words, you know how much to put back in the system.
      Hope that answers your questions and thank you for watching the videos!

    • @mohaalgha3397
      @mohaalgha3397 4 ปีที่แล้ว +1

      @@stuzman52 I thank you very much for taking the time to answer my questions. Your answer was very sound and clear. Thank you again!!!

    • @stuzman52
      @stuzman52  4 ปีที่แล้ว

      Waleed7rrag RRAG Glad to help and you’re welcome!

  • @sabrinac665
    @sabrinac665 ปีที่แล้ว

    hello ..i purchased a della 36 btu 3 zone unit that i'm currently installing
    and noticed when i was attempting tonever install the line sets to the condenser units that they are filled and capped off (plastic caps) with nitrogen from the factory.
    i've never seen this before, is there a procedure that i should be using since the condensers are filled with nitrogen, or do i just release it and hook up line sets and vacuum???

    • @stuzman52
      @stuzman52  ปีที่แล้ว

      Hi Sabrina... I looked over the installation procedure for your unit. There is only one set of lines which goes to the indoor cooling unit that will have nitrogen in them and these lines are capped to prevent the nitrogen from coming out. When you remove the plastic caps, you will hear the nitrogen being released. This is normal. The refrigerant is stored in the outdoor cooling unit which is prevented from coming out by the two service valves located on this unit. As for the line-set itself, there is no nitrogen inside of them. You would make all of your line-set connections, pressurize the system with nitrogen to check for leaks and if that looks good, then you would vacuum the system and release the refrigerant into the line-set.

  • @fly4fun24
    @fly4fun24 3 ปีที่แล้ว

    If I pulled the vaccuum ;and left the micron meter there showing 240 micron For 6 h with no de gradation, Why should I do pessue test with nitrogen ?

    • @stuzman52
      @stuzman52  3 ปีที่แล้ว +1

      The reason for the pressure test is to find small leaks under a higher pressure than what would be under a vacuum. Since you kept the gauge on there for 6 hours, more than likely you don't have a leak.

  • @harryvalsak
    @harryvalsak 5 ปีที่แล้ว

    I do not know if it has been pointed out in the comments but I would had cracked open the liquid line at the coupling to bleed or displaced ambient air from the lines. You just pressurized the system with a Nitrogen tank with air still in it. My 2 cents. Besides that, good video.

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว +1

      I appreciate your comment Giovanni, but that wouldn't be a recommended procedure. When you crack open the liquid line, you would be letting refrigerant into the atmosphere which is a EPA violation. And let's say that you did that. How much refrigerant would you let out to know when all the air has been released? At that point, why use nitrogen; couldn't we just leak test with an electronic leak detector or use soap bubbles. And now you'll be low on refrigerant. How would we recharge the system with the refrigerant that's lost? You can't just add an amount and use the subcool or superheat method of checking the refrigerant charge because mini splits have an electronic thermostatic expansion valve and the compressor runs at a variable speed based on the heat load. You'll have to recover the entire contents of refrigerant and then weight the refrigerant back into the system based on the manufacturer's nameplate of refrigerant charge. And if we were able to get all the air out through purging, would we need to pull a vacuum on the system? And here's what section 608 of the EPA study guide for certification says about high pressure systems, under Type II, C-2 for leak detection. "The first thing to do when a new system has been assembled (built up), and is ready for testing, is to pressurize with an inert gas and leak check. After installation of a field piped split system the unit should first be pressurized with nitrogen and leak checked." It says nothing about purging the line of refrigerant to remove the air before you put nitrogen in the system. If you look anywhere on TH-cam and follow the pros such as acservicetech, you'll see that no one cracks the liquid line to purge the system of air and then put nitrogen into the system. Have a great day!

    • @harryvalsak
      @harryvalsak 5 ปีที่แล้ว

      @@stuzman52 not the service port on the condenser, the lineset you just installed. There isn't any refrigerant in it. Just to clear out any air. Sorry if you misunderstood.

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว +1

      @Giovanni Ciuro Okay, I misunderstood you. Yes, in that case, that would be fine.

    • @Froggability
      @Froggability 4 ปีที่แล้ว

      Giovanni Ciuro , I got what you mean, but there’s no need to flush the air out per se . It is diluted during pressure test and comes out on release and during vacuum

  • @csavage1947
    @csavage1947 5 ปีที่แล้ว +1

    Extremely well done.

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว

      Thank you very much Craig!

  • @kevinkevin9448
    @kevinkevin9448 4 ปีที่แล้ว

    Thanks for the video I have a lg mini split 2 zone but I can't pressure test all the lines can't figure out why ?? Any suggestions

    • @stuzman52
      @stuzman52  4 ปีที่แล้ว

      I believe Kevin that you'll have to pressure test each one separately.

  • @paulntx
    @paulntx 5 ปีที่แล้ว

    So does procuring nitrogen require any special certifications? Can you rent a tank of nitrogen?

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว +1

      No Paul, it doesn't require any certification to get nitrogen. You can buy nitrogen for about $25-30 a tank. If you don't have a tank, then the company will allow you to buy one. I believe the price for the tank and fill it is around $110. When you empty the tank, bring it back and they'll give you another tank already filled. Give them the empty, pay the refill fee and you don't pay for the tank again. I did this through airgas which is in my city. I'm sure that you have one or a similar company if you want to get a tank of nitrogen.

  • @floatybyboaty
    @floatybyboaty 3 ปีที่แล้ว

    Can i ask, Why the Low side and not the High?

    • @stuzman52
      @stuzman52  3 ปีที่แล้ว +2

      The low side gauge has a higher resolution than the other gauge. Makes it a little easier to read for pressure drops of the nitrogen.

  • @SteveRobReviews
    @SteveRobReviews 6 ปีที่แล้ว +1

    Nice to see it held pressure. If you seen a leak it would have been go time eh:) I have to try that bubble fluid. Nicely done Terry. 👍

    • @stuzman52
      @stuzman52  6 ปีที่แล้ว +2

      STEVE ROB REVIEWS Yes, you are correct that if there was a leak, the pressure would have dropped off fast, even for a small leak. I’ve used all kind of stuff for bubbles over the years and this stuff is amazing. You won’t be disappointed! 😀👍

  • @Manavsain00
    @Manavsain00 5 ปีที่แล้ว

    Sir how much nitrogan pressure can filling in 1ton air-condition

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว

      I don't know the quantity of nitrogen that's used, but around 200psi should be good enough.

  • @msaeed8031
    @msaeed8031 5 ปีที่แล้ว +1

    Can I nitrogen test with valve core?

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว +1

      Sure, no problem!

  • @kevinkevin9448
    @kevinkevin9448 5 ปีที่แล้ว +1

    What size nitrogen tank ???

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว +1

      Kevin, it's a 40 cu ft cylinder which is about 7" in diameter, 18" high.

    • @kevinkevin9448
      @kevinkevin9448 5 ปีที่แล้ว

      @@stuzman52 thanks u the man

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว

      Kevin kevin You’re quite welcomed! 😀

  • @JSROOKS
    @JSROOKS 5 ปีที่แล้ว +1

    Nice video, but you never isolated the pressure from the nitrogen tank, so there was no way for the pressure to drop below 200psi.

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว

      Read one of the comments where another viewer thought the same thing. The valves on the manifold gauge set isolates the lines from the tank. If you want to turn the valve off on the nitrogen tank, you can do that, but it's not necessary.

  • @ignatiousreddykolukula2585
    @ignatiousreddykolukula2585 5 ปีที่แล้ว

    Is the nitrogen cylinder regulator two stage

    • @stuzman52
      @stuzman52  5 ปีที่แล้ว

      Not sure about that, but you can click on the link in the description and there may be more information about it.

  • @diysolaradventures7894
    @diysolaradventures7894 ปีที่แล้ว

    My mini split has no pressure at all the outside compressor barely wants to run there are no leaks I made a mistake and let all the air out how do I fix this I thought the compressor actually build up the pressure in the lines I'm trying to figure out why mine's haven't built up any pressure

    • @stuzman52
      @stuzman52  ปีที่แล้ว

      Is this a new install or has it been running for awhile and now you have this issue? When the system is installed, there is air in the lineset and the refrigerant is inside the outside coil. The refrigerant is held inside the outside coil by the two service valves. The inside coil will have two plugs on the lines which when taken off will release nitrogen which is from the factory. And what do you mean when you say, I let all the air out?

    • @diysolaradventures7894
      @diysolaradventures7894 ปีที่แล้ว

      @stuzman OK so my mini-split was running just fine till Friday when my new mini split stand came I pumped down the unit sending all the refrigerant back into the outside compressor right installed the stand hooked everything back up nice and tight my mistake came when I opened up the high pressure line allowing the refrigerant in then opening the low pressure side I called my self bleeding the air out by pressing the valve stem until I saw a lil refrigerant it's worked for me perfect the first time but this time I must of did something wrong

    • @stuzman52
      @stuzman52  ปีที่แล้ว +1

      @@diysolaradventures7894 Ok, good luck on what you find and hope you get your system running.

    • @diysolaradventures7894
      @diysolaradventures7894 ปีที่แล้ว

      @@stuzman52 I'm waiting on a vacuum pump and gauges and hopefully I can create the pressure it needs by pulling a vacuum

    • @stuzman52
      @stuzman52  ปีที่แล้ว +1

      @@diysolaradventures7894 Just keep in mind that if there is no refrigerant, no amount of vacuum is not going to raise the pressure. You mentioned that you don’t have any gauges. Just crack one of the fittings at a service valve to see if you have any pressure. I looked back at one of your previous posts and you mentioned that you let all the air out. Maybe, you let all the refrigerant out. The compressor will move the refrigerant throughout the system and the pressure it creates is based on the refrigerant being in the system. Thus, if you have no refrigerant, very little pressure in the system when compressor is running.

  • @user-bj4lp3fr1o
    @user-bj4lp3fr1o 3 ปีที่แล้ว

    How long will that tank of nitrogen last? Or how many units can you test with one tank?

    • @stuzman52
      @stuzman52  3 ปีที่แล้ว

      Don't know but I still have 2000psi on the tank and I've check several systems.

  • @syazwihalip2873
    @syazwihalip2873 4 ปีที่แล้ว

    hey sir great video! but how do u nitro test a multi split? do you nitro individually on each service valve or just 1?

    • @stuzman52
      @stuzman52  4 ปีที่แล้ว

      I've never done a multi-split unit, but from what I understand, you'll pressure test each unit separately, especially if you have a separate service valve for each zone.

  • @mark.r8900
    @mark.r8900 3 ปีที่แล้ว

    hi, some of these units come with a mini condensate pump. when would i need to use that? thanks

    • @stuzman52
      @stuzman52  3 ปีที่แล้ว

      The only scenario that I can think of is if the indoor unit is located in a basement which is below grade level. The pump would then pump the condensate upward to get above the grade level to be deposited on the ground. In most cases, the indoor unit is located above grade level where the condensate will move by gravity to be deposited on the ground.

  • @Upliftyourbrothers
    @Upliftyourbrothers 4 ปีที่แล้ว

    Would inert welding gas work instead?
    Great video!

    • @stuzman52
      @stuzman52  4 ปีที่แล้ว +1

      Yes, it should be fine.

  • @johnmcculloch6961
    @johnmcculloch6961 4 ปีที่แล้ว +1

    Excellent video series that gave me confidence to purchase and install my own mini split system. Really enjoyed the classroom lesson in the first video. Quick question, how much nitrogen would you estimate you used for your 12k system. Many thanks. John

    • @stuzman52
      @stuzman52  4 ปีที่แล้ว

      Thank you very much John and glad to hear that you liked the videos. I couldn't say about how much nitrogen was used, but it was very little. I've used the same tank to test other systems and the tank is still pretty much full.

    • @TalkwithTobby
      @TalkwithTobby 3 ปีที่แล้ว

      Very good video

  • @stevengao8345
    @stevengao8345 4 ปีที่แล้ว

    thanks for this video, after you are done with pressure test with nitrogen, how you gona release or get rid of the nitrogen in the system ? did you mentioned it , sorry if this question is very noob. i have noticed at 9:55, are you releasing all the NItrogen there ? but i am not sure

    • @stuzman52
      @stuzman52  4 ปีที่แล้ว +1

      Yes, you are correct Steven. After the pressure test is completed, the nitrogen in the system is released to the atmosphere.

    • @stevengao8345
      @stevengao8345 4 ปีที่แล้ว

      @@stuzman52 thanks