  • generator under voltage problem fixed | DSE generator under & over voltage shutdown / warning alarm
    #generator #undervoltage #transientdelay
    About video: In this video i am explaining how to deal with generator under voltage problem | generator under & over voltage shutdown / warning alarm | DG alarm .
    Firstly, check all voltage-sensing fuses to ensure that none of them have blown. Secondly, take out each fuse, visually check for issues, clean and replace. Ensure firm fit. Check capacitors if you generator has any capacitors.
    If you watch this video completely you are able to troubleshoot all voltage related problems.
    generator under voltage problem fixed,DSE generator under & over voltage shutdown / warning alarm,generator under voltage problem,how to fix generator under voltage,dse controller under voltage,generator controller under voltage,generator under voltage shutdown,generator under voltage,generator controller wiring diagram,power learning channel,Muzammil Ismail,Dg over under voltage problem,under voltage over voltage protection,dse controller,dse generator controller

ความคิดเห็น • 129

  • @powerandmachines3517
    @powerandmachines3517 6 หลายเดือนก่อน +2

    This is educating and it help to solve my problem immediately. Thank you for enlightenment.

  • @BirukWolde-mn6hi
    @BirukWolde-mn6hi 10 หลายเดือนก่อน +1

    Thank you so much, Nice explanation

  • @EdmondNgologwana-nj2qv
    @EdmondNgologwana-nj2qv ปีที่แล้ว +2

    Thank you so much very educative, I need a video on how to do factory reset of a d500 control panel

  • @wassimsalloum2654
    @wassimsalloum2654 ปีที่แล้ว +1

    Thank u. In case of synchronizing 2 same size gensets, do we need to activate voltage and speed droop characteristics in the dse 8610

    • @DieselGeneratortraining
      @DieselGeneratortraining  ปีที่แล้ว +1

      Yes sure

    • @wassimsalloum2654
      @wassimsalloum2654 ปีที่แล้ว

      Even if the gensets r working off grid. In a remote area?

    • @acooper1037
      @acooper1037 7 วันที่ผ่านมา

      no, the DSE does not control droop, it is controlled by the AVR via the quad droop CT's and the electronic governour control the speed, ther DSE can control the reactive power.

  • @piusnasimolo1263
    @piusnasimolo1263 หลายเดือนก่อน +1

    My issue is the 20KV generator is meant to supply power to office, kitchen and laundry, however I have noticed that once we turn on the cooker it the generator shuts down,I want to know exactly how I can solve this problem,is it under voltage issue?

  • @tumuhimbisemike
    @tumuhimbisemike ปีที่แล้ว +1

    Thank you so much for the knowledge shared. My Diesel generator 52KVA shuts down citing low loading frequency. how do i solve that problem?

    • @DieselGeneratortraining
      @DieselGeneratortraining  ปีที่แล้ว

      What is engine model record a video n sent us on
      Info.powerlearning@gmail.com

  • @azharicenter5003
    @azharicenter5003 2 ปีที่แล้ว +2

    Bro i have problem under voltage shutdown phly engine 380 tha maine 220kia uske baad yahi horha hai under voltage shutdown iska kuch btao ?

  • @kummariravikumar9573
    @kummariravikumar9573 ปีที่แล้ว +1

    Nice explanation sir actually I had a small problem that was the dg was on but few seconds ofter then shutting down the display shows AGF V3 LOSE what I candoo now could you tell plzz sir

  • @yerooftolee5565
    @yerooftolee5565 ปีที่แล้ว +2

    Nice information? let you do detail wiring with explanation on deep sea electronics 7320 amf controller with all componemts like contactor, glass relay...

  • @renamaeandrade787
    @renamaeandrade787 ปีที่แล้ว +2

    What shoud i do when generator over voltage and it will automatically shutdown the genset

  • @ssemassem8838
    @ssemassem8838 ปีที่แล้ว +1

    can i get a video of confiheration of deepsea and sycronization of two or more DGS

    • @DieselGeneratortraining
      @DieselGeneratortraining  ปีที่แล้ว +1

      Dse 8610MKII synchronizing controller full training
      Part 1 video Link:
      th-cam.com/video/7SSpPzUazdA/w-d-xo.html
      Part 2 video link:
      th-cam.com/video/-NJ8BpXdrjs/w-d-xo.html
      Part 3 video Link:
      th-cam.com/video/ly_3RiZNg2w/w-d-xo.html
      DSE 8610 Part 4 VIDEO LINK configuration:
      th-cam.com/video/eNnEgmlzYuI/w-d-xo.html
      Practical training 8610 video Link:
      th-cam.com/video/zwLP5X9gGhc/w-d-xo.html

  • @ericbudoy4300
    @ericbudoy4300 ปีที่แล้ว +1

    Can you make a troubleshooting video of a generator which cannot be shutdown using the DSE6010 controller. Even the emergency stop button doesn't work anymore.

    • @acooper1037
      @acooper1037 7 วันที่ผ่านมา

      Air shutoff valve.

  • @richieuntaran8530
    @richieuntaran8530 2 ปีที่แล้ว +2

    Hello sir how are you, sir i have a genset kta 38 cummins 1000kva dse 7320 if the genset start line to neutral 230v line to line 400v, but the problems is frequency indicate 53hertz not stable to 60hertz how to fix this problems, thanks and take care sir

    • @DieselGeneratortraining
      @DieselGeneratortraining  2 ปีที่แล้ว +2

      Check ur speed sensor circuit

    • @richieuntaran8530
      @richieuntaran8530 2 ปีที่แล้ว +1

      The mpu sir ok 2 speed sensor is install i check, thanks sir

    • @shahariaakter4393
      @shahariaakter4393 2 ปีที่แล้ว +1

      what is the rpm?

    • @richieuntaran8530
      @richieuntaran8530 2 ปีที่แล้ว +1

      @@shahariaakter4393 1800rpm sir

    • @acooper1037
      @acooper1037 7 วันที่ผ่านมา

      throw the mag pickup in the bin and use frequecncy detection.

  • @azeresedov691
    @azeresedov691 ปีที่แล้ว +1

    Thank you so much for information

  • @baiticmixvlog863
    @baiticmixvlog863 ปีที่แล้ว +1

    When replacing contoller..
    I encounter under voltage alarm.. even the phasing and rated v was reconfigured..
    Any advise sir

  • @HamzaKhanKhanBhadur
    @HamzaKhanKhanBhadur 8 หลายเดือนก่อน +2

    Under speed alarm how can fix that

    • @acooper1037
      @acooper1037 7 วันที่ผ่านมา

      raise speed.

  • @EdmondNgologwana-nj2qv
    @EdmondNgologwana-nj2qv ปีที่แล้ว +1

    How do reset low voltage fault on kj power generator using a d500 control panel

  • @santhoshpaul382
    @santhoshpaul382 2 ปีที่แล้ว +1

    My Perkins generator is showing over voltage alarm and stopping. Phase to phase is 380 v and line to phase is 270 but actual is 220v so how can we adjust the line to phase voltage.

  • @alfredmat23
    @alfredmat23 7 หลายเดือนก่อน +1

    Need a video for smart gen controller for Automatic transfer switch setup in the settings of the controller and wirings.

  • @charliedelacruz8555
    @charliedelacruz8555 2 ปีที่แล้ว +1

    Sir Good day.about REVERSE POWER can You please make a lecture or content in your blog.
    Thank you...

  • @anthonychisala6792
    @anthonychisala6792 ปีที่แล้ว +1

    Make a video on trouble shooting a genset that shuts down after seconds or minutes after starting stating or explaining all possible reasons to what the cause can be

  • @EffiongBassey-yv1kj
    @EffiongBassey-yv1kj ปีที่แล้ว

    What could be the fault, I start a new dcec dongfeng Cummins model 4bta3 9-g13 but all the bulbs are blinking?

  • @lewisuruejomah8055
    @lewisuruejomah8055 ปีที่แล้ว +1

    Good morning pls help my Gen cat 450 kva couple of second it will sort down it showing high vote sort down pls what could that be the problem sir

  • @Mrquote30
    @Mrquote30 ปีที่แล้ว +1

    sir, if our generator shutdown on low voltage even load is not connected. whats the reason?? please answer

    • @acooper1037
      @acooper1037 7 วันที่ผ่านมา

      low voltage?

  • @ericgershon1496
    @ericgershon1496 2 ปีที่แล้ว +1

    Sir my 1000 kva cummins is showing high ac voltage after I increase one of the voltage phases, what should I do.

  • @kiafrank6903
    @kiafrank6903 ปีที่แล้ว +1

    Can you explain further why frequency increase and how to reset the frequency?

    • @acooper1037
      @acooper1037 7 วันที่ผ่านมา

      on the governour

  • @dennistejada2173
    @dennistejada2173 2 ปีที่แล้ว +1

    Bro! How to troubleshoot generator.gulf power 125kv.this senario.without load the voltage is ok.but if you put load the voltage flunctauting voltage.what is the problem.

  • @skos9618
    @skos9618 10 หลายเดือนก่อน +1

    why does the generator give an error low voltage of the generator? DTK controller

  • @Manoj_0341
    @Manoj_0341 2 ปีที่แล้ว +2

    Make video regarding CAT et and Volvo vodia

  • @hermantoofa1868
    @hermantoofa1868 9 หลายเดือนก่อน

    Hi sir
    Can you explain what is a transient delay?

  • @halalbuybd8497
    @halalbuybd8497 5 หลายเดือนก่อน +1

    3 phase Ship Generator sometime getting high voltage alarm (more then 106%) and on attempting paralleling with other generator Blackout occured. Voltage 480v instead if 440v.
    2. Same Generator in off load condition, sometime getting high voltage alarm
    Please advise for the root cause

  • @modisephohlo9980
    @modisephohlo9980 ปีที่แล้ว

    I have a Bundu 20kva Generator it's new but it's failing to take my four laundry machines, 2 speed Queen dryers and 2 commercial washers , it just shuts down when they are all running, what could be the problem

  • @mohammadsualeh8369
    @mohammadsualeh8369 8 หลายเดือนก่อน +2

    Thanks for sharing. Very useful for gen set operation.

  • @atkingapu7040
    @atkingapu7040 11 หลายเดือนก่อน

    i have a problem of over voltage and under voltage after 7sec from starting the cumins generator ,adjust avr but not respon to this issue..help pliz

  • @dark-mb1bs
    @dark-mb1bs ปีที่แล้ว +1

    I have a generator that works a little and then stops and gives a frequency alarm runaway What's the problem?

    • @dark-mb1bs
      @dark-mb1bs ปีที่แล้ว

      Please can you answer me I still can't figure out why

    • @rickywoods3101
      @rickywoods3101 5 หลายเดือนก่อน

      ​@@dark-mb1bsI'm having the same issue.

    • @acooper1037
      @acooper1037 7 วันที่ผ่านมา

      overspeed?

  • @santhoshr53
    @santhoshr53 ปีที่แล้ว

    Can explain how configure digital output based on speed. I want configure 3 output on different speed plz make video on it. thanks your video was so useful for new learners. God bless you sir.. Keep making more videos ... 🙏🙏🙏🙏

    • @DieselGeneratortraining
      @DieselGeneratortraining  ปีที่แล้ว

      Santosh thanks for liking 👍 I would like to inform you there is no option to select three outputs for 3 different speeds selection you can do it with different configuration selections

    • @santhoshr53
      @santhoshr53 ปีที่แล้ว

      @@DieselGeneratortrainingThanks for feedback, plz suggest how I can achieve from DSE 7320 for said above problem

    • @mogamatsalie2060
      @mogamatsalie2060 ปีที่แล้ว

      Asalaamu allykum why is a generator starting after few seconds it shut down

    • @acooper1037
      @acooper1037 7 วันที่ผ่านมา

      you can if the DSE has the PLC internal function

  • @juliantaer2425
    @juliantaer2425 ปีที่แล้ว +1

    What happened for my generator suddenly shutdown and it mention low voltage

  • @naushadmohammad2784
    @naushadmohammad2784 ปีที่แล้ว

    In synchronization generator 2 different KVA 800&500 under voltage tripping after running some times on load

  • @pp-pl2zg
    @pp-pl2zg ปีที่แล้ว +1

    Nice one!

  • @AltafKhan-zk5jh
    @AltafKhan-zk5jh หลายเดือนก่อน +1

    Sir Urdu language please Vedo information

  • @DieselGeneratortraining
    @DieselGeneratortraining  2 ปีที่แล้ว

    1. Dg operator practical training
    th-cam.com/video/T77bZHVUAXM/w-d-xo.html
    2.Plc industrial automation free video tutorial course
    th-cam.com/video/hk1WTmLujrA/w-d-xo.html
    3. Dse 7320 full course video tutorial
    th-cam.com/video/bsZ8875Xo58/w-d-xo.html
    4. How to read Electrical Drawings Video tutorial
    th-cam.com/video/IHHCT43sdYM/w-d-xo.html
    5.how to bypass generator AVR
    th-cam.com/video/JzuFHKMkKyA/w-d-xo.html

  • @davidbabatunde4275
    @davidbabatunde4275 ปีที่แล้ว

    The Gen. we have here shutdown after working for about 3 minutes and it is displaying uh with an alarm sound, what could be the problem?
    II. How can I solve the problem?

  • @LesterCortes-v1p
    @LesterCortes-v1p 3 หลายเดือนก่อน +1

    Our generator not giving load for the output..type diesel 800kVa

  • @aklilA
    @aklilA 2 ปีที่แล้ว +2

    Thank you so much as usual.

  • @bteshome2003
    @bteshome2003 ปีที่แล้ว +1

    what will be the possible causes of a generator that starts and run for 2 to 3 minutes and dies?

  • @oxford130
    @oxford130 2 หลายเดือนก่อน

    FAILED TO REACH LOADING VOLTAGE, If the engine fires but the generator fails to reach the loading voltage before the end of the Safety On timer a shutdown is initiated, how can fixed it?

    • @Anyssaherrera
      @Anyssaherrera หลายเดือนก่อน

      how did you fix it??

    • @acooper1037
      @acooper1037 7 วันที่ผ่านมา

      what is it set at ? have you tested the speed controler.

  • @ABDULRAHIM-ks2ym
    @ABDULRAHIM-ks2ym ปีที่แล้ว +1

    My caterpillar generator is running but frequency is stuck at 62hz and showing message on main panel NO COMMUNICATION WITH MAIN UNIT plz give some suggestions.

    • @DieselGeneratortraining
      @DieselGeneratortraining  ปีที่แล้ว +1

      Which controller and engine model u have try to adjust speed

    • @acooper1037
      @acooper1037 7 วันที่ผ่านมา

      if EMPC 2 bin it.

  • @Godman-ek9lv
    @Godman-ek9lv 5 หลายเดือนก่อน

    If the timing of c32 caterpillar generator 1000kva is in correct will it start

  • @sugumars8168
    @sugumars8168 2 ปีที่แล้ว +2

    Super bro

  • @ruwankumara6312
    @ruwankumara6312 2 ปีที่แล้ว +2

    Nice to herd

  • @siindian6517
    @siindian6517 ปีที่แล้ว +1

    كيف حال يا اخي فين شغل انت؟
    انا في موجود جازان.

  • @jefryrajagukguk2914
    @jefryrajagukguk2914 ปีที่แล้ว

    Hi sir,can you advise how to increase value of L1,L2 and L3?
    L1-L2.....374V
    L2-L3.....380V
    L3-L1.....366V
    How to fix this?
    Please help

  • @shonashona8332
    @shonashona8332 ปีที่แล้ว

    Generator locked out
    Stop mode
    Please explain this

  • @ihsanulhaq1687
    @ihsanulhaq1687 ปีที่แล้ว +1

    Want to under frequency stop problems

  • @koosdiedericks3035
    @koosdiedericks3035 2 ปีที่แล้ว

    i have a300kw generator 12 cylinder starts and runs for a couple of seconds then shuts off it is not a fuel problem mybe a voltage drop i dont no

  • @isaiahpax4933
    @isaiahpax4933 5 หลายเดือนก่อน +1

    Boss I want to be like u

  • @walusansadouglas5616
    @walusansadouglas5616 ปีที่แล้ว

    Thanx Engineer Muzamir,I request to demonstrate this practically on controller how to go about transient voltage setting, 10% high and low voltage allowance setting..

    • @acooper1037
      @acooper1037 7 วันที่ผ่านมา

      its in the manual

  • @michaelmane3907
    @michaelmane3907 ปีที่แล้ว

    When the oil sensor cable taken off engine continues with ac 265 vlts

  • @mohdashraf2486
    @mohdashraf2486 2 ปีที่แล้ว +1

    My generator give alarm charg failyer waht problem

  • @PatrickKitarepakei
    @PatrickKitarepakei หลายเดือนก่อน

    Voltage is running okay but rpm is over raping and stoping generator

  • @serutukanatukana2920
    @serutukanatukana2920 ปีที่แล้ว +1

    Thanks for advise

  • @azharicenter5003
    @azharicenter5003 2 ปีที่แล้ว +3

    Dse 7320

  • @pankajsharma-du2dl
    @pankajsharma-du2dl 4 หลายเดือนก่อน

    हिन्दी मै भी समझाना होगा

  • @tareqmamun2415
    @tareqmamun2415 ปีที่แล้ว +1

    Under ampere reason

  • @DfDf-v7u
    @DfDf-v7u 3 หลายเดือนก่อน

    Voltage problem full load

  • @DfDf-v7u
    @DfDf-v7u 3 หลายเดือนก่อน

    Voltage problem

  • @Babuganguly961
    @Babuganguly961 11 หลายเดือนก่อน +1

    My dg set not started alerms under voltage ans under frequency please solve the problem