You are the best of the best of the best, thank you so much for sharing all of your knoledge. In the other hand I have a big issue with adding a router, I have disabled all of the firewalls, the smartscreen, both PC see each other, I can share files between them, I am using Remote Desktop, but every time I try to add a new router the error 1796 "reading/writing not permitted" I have done evrything but still can not make the connection, Can you please, plase help me. Both PC are connected by a ethernet cable through a router, static IPs. Best regards.
Thanks my friend!, Regarding your question about "error 1796 "reading/writing not permitted" , it may come from three issues 1. The user name and password is not correct for loggin the remote TwinCAT PC. (But if you could do remote desktop, this should not a problem) 2. Your TwinCAT revision of programming PC is not the same as the remote Runtime TwinCAT PLC. 3. Make sure using 'Run as administrator' to install your engineering TwinCAT.
@@electricalautomationThank you so much for your quickly respond, user name is ok, I'm using the same as you, TwinCAT revision is the same in both PC, I have installed with the same file and for the open as administrator I am running both as administrator. I don't really know what else I can do, I'm thinking that may be it is a Ethernet adapter not compatibility issue, because I have done everything, and as soon as I try to add the router, the error pops up. Once again thank you so much for everything.
Hi, When ı tried to connect beckhoff opc ua server with TwinCAT everything is fine. Data exchanged but when ı tried to setup TwinCAT OPC UA Gateway then tried to connect server TwinCat warning pop up and show it is not a beckoff server. System can not establish server . How can ı fix that. Can you explain on next video ? is it about certificates ? Thank you btw
Regarding the TwinCAT OPC UA, you could review COM08b. OPC UA Beckhoff - TwinCAT 3 TF6100 (OPC UA Server) Beckhoff IPC Controller (C6030), th-cam.com/video/ShfRMd6-eIY/w-d-xo.html. I will also release a video SCADA05. the other way to configure the OPC UA Server next Monday.
@Electrical Automation Hands-On i reviewed your COM08b and COM8a videos. You used TcOpcUaServer right ? i just wanna use beckhoff OPC UA Server via TcOpcUaGateway on port 48050 . It is not allowed or I did some configuration wrong anyway. I'm looking forward to the SCADA05 video. Thanks for your answers
Thank you for these Bechoff tutorials mate, love it!
Glad you like them!
You are the best of the best of the best, thank you so much for sharing all of your knoledge. In the other hand I have a big issue with adding a router, I have disabled all of the firewalls, the smartscreen, both PC see each other, I can share files between them, I am using Remote Desktop, but every time I try to add a new router the error 1796 "reading/writing not permitted" I have done evrything but still can not make the connection, Can you please, plase help me. Both PC are connected by a ethernet cable through a router, static IPs. Best regards.
Thanks my friend!, Regarding your question about "error 1796 "reading/writing not permitted" , it may come from three issues
1. The user name and password is not correct for loggin the remote TwinCAT PC. (But if you could do remote desktop, this should not a problem)
2. Your TwinCAT revision of programming PC is not the same as the remote Runtime TwinCAT PLC.
3. Make sure using 'Run as administrator' to install your engineering TwinCAT.
@@electricalautomationThank you so much for your quickly respond, user name is ok, I'm using the same as you, TwinCAT revision is the same in both PC, I have installed with the same file and for the open as administrator I am running both as administrator.
I don't really know what else I can do, I'm thinking that may be it is a Ethernet adapter not compatibility issue, because I have done everything, and as soon as I try to add the router, the error pops up.
Once again thank you so much for everything.
can engineering laptop and plc+hmi controller computer be same device
Yes, In this video series, I am using one computer for PLC and HMI
Hi, When ı tried to connect beckhoff opc ua server with TwinCAT everything is fine. Data exchanged but when ı tried to setup TwinCAT OPC UA Gateway then tried to connect server TwinCat warning pop up and show it is not a beckoff server. System can not establish server . How can ı fix that. Can you explain on next video ? is it about certificates ? Thank you btw
Regarding the TwinCAT OPC UA, you could review COM08b. OPC UA Beckhoff - TwinCAT 3 TF6100 (OPC UA Server) Beckhoff IPC Controller (C6030), th-cam.com/video/ShfRMd6-eIY/w-d-xo.html. I will also release a video SCADA05. the other way to configure the OPC UA Server next Monday.
@Electrical Automation Hands-On i reviewed your COM08b and COM8a videos. You used TcOpcUaServer right ? i just wanna use beckhoff OPC UA Server via TcOpcUaGateway on port 48050 . It is not allowed or I did some configuration wrong anyway. I'm looking forward to the SCADA05 video. Thanks for your answers