Add Screens to a Panelview 800 HMI for BETTER Navigation

แชร์
ฝัง

ความคิดเห็น • 40

  • @onyitsme4740
    @onyitsme4740 ปีที่แล้ว +1

    Thanks for the videos there great. For those that don't know if your having a hard time dragging your box around you can move it with the arrow keys.

    • @TimWilborne
      @TimWilborne  ปีที่แล้ว +1

      Great tip. You can also right click an unused space on your screen and "Show Grid" to make it easier to line all the objects up.

  • @andremachadopereira8012
    @andremachadopereira8012 5 หลายเดือนก่อน +1

    Your tips are incredible, I learned a lot of things in this video, thank you very much.

    • @TimWilborne
      @TimWilborne  5 หลายเดือนก่อน +1

      Happy to hear that!

  • @flyfishing8849
    @flyfishing8849 3 ปีที่แล้ว +2

    Very well made, very well explained. I am delighted with the content and the clarity. Thanks a lot for this great video!

    • @TimWilborne
      @TimWilborne  3 ปีที่แล้ว +1

      You are welcome, thank you for watching!

    • @flyfishing8849
      @flyfishing8849 3 ปีที่แล้ว

      @@TimWilborne Would be interesting to see two Micro820 talking each other through Ethernet or DeviceNet using pluging modules.

  • @RudiduPlessis
    @RudiduPlessis ปีที่แล้ว +1

    Hi Tim! Thank you for posting these videos. They continue to be super useful.
    I was curious if you had anything on setting up graphs using the PanelView 800? I am trying to overlay real time data capture (Temperature vs time) against a calculated trend and don't know if the Panel view can display graphs with good resolution.
    I had planned on using a Scada system with my Mirco850 but I am running into problems that has me thinking it would be better to just buy the HMI and figure out a how to set up Scada control later.

    • @TimWilborne
      @TimWilborne  ปีที่แล้ว +1

      See if this helps.
      th-cam.com/video/2VFAiFfuIrQ/w-d-xo.html

    • @RudiduPlessis
      @RudiduPlessis ปีที่แล้ว

      Thank you Tim! Missed that video. As it happens my local allen bradely decided they would not be loaning out a HMI for my university presentation. I've spend the last 2 weeks desperately trying to find a scada system to use instead.
      I am hoping to get trail access to Rockwell's Scada system.

  • @adamhassell
    @adamhassell 2 ปีที่แล้ว +1

    Hi Tim, one final question on the Panelview 800 series. Is the screensaver necessary to prevent 'burn in' on these newer HMIs? I'd love to turn the screensaver off but want to know if I'll damage the panel first.

    • @TimWilborne
      @TimWilborne  2 ปีที่แล้ว +1

      No, it isn't necessary and I wish they would disable it by default.

  • @thebeansayshello5192
    @thebeansayshello5192 3 ปีที่แล้ว +1

    Have you done a video at all for adding users and password protected screens? There are settings I would like to access with the hmi that the operators shouldn't. Also just want to say you videos are great and extremely helpful thank you

    • @TimWilborne
      @TimWilborne  3 ปีที่แล้ว +3

      Hi Greg, no I haven't but it is on the list for the next set of Panelview videos.

    • @thebeansayshello5192
      @thebeansayshello5192 3 ปีที่แล้ว

      Awesome. Thanks for all your hard work on these and sharing your knowledge

  • @Practical_PLC_Tips
    @Practical_PLC_Tips 7 หลายเดือนก่อน +1

    Hey Tim,
    Quick question how can I get a tag on my plc for current screen that is displayed I want the plc to know what screen the hmi is on to control different sections of my program I know there is a global tag or system tag but I can’t quite figure out how to do it?
    Thanks and you’re awesome!!

    • @TimWilborne
      @TimWilborne  7 หลายเดือนก่อน +1

      Hi Dawson. As you have found, under global you have the Current Screen Number. And it has a source and destination tag. The source is your "commanded" screen number, the destination is the screen that it is currently on. If you notice, every screen starts with a number, that is the screen number. So if you enter a 5 into the source tag, then it will go to screen 5 then the destination will indicate 5. I haven't done it in a while, let me know if that works.

  • @AbdulWahab-iq3ej
    @AbdulWahab-iq3ej 2 ปีที่แล้ว +1

    Hi Tim,
    Great video.
    Do you have any video about studio 5000 view designer and view 5000 emulator?
    Please share if you have done any.
    Also I am confused about one thing. Can we export controller tags to panel view 800 HMI rather than putting tags one by one? Just need your point of view.

    • @TimWilborne
      @TimWilborne  2 ปีที่แล้ว +1

      Yes, you can select the file and pull the tags right out of Studio 5000 or CCW.
      I don't have anything in Emulate, not a fan.

  • @agnelocosta7934
    @agnelocosta7934 3 ปีที่แล้ว +1

    Hi TIM, thank you for your videos, it adds a lot! Is it possible to use two HMI PanelView 800 in a PLC of the Micro800 line? Like two different environments to connect different devices with an HMI in each environment with the same PLC?

  • @barrazo2
    @barrazo2 2 ปีที่แล้ว +1

    I didn't find the copy screen function, I did a template and I want preserve the same format to all my screens

  • @traviscoleman9520
    @traviscoleman9520 2 ปีที่แล้ว +1

    Hey Tim! Is it possible to create a HMI program in Factory Talk and upload to a different manufacturers screen? Or are each manufacturers HMI screens only compatible with their corresponding software?

    • @TimWilborne
      @TimWilborne  2 ปีที่แล้ว +1

      No, each manufacturer has their own software and many manufacturers, including AB, have different softwares for different HMI products.

  • @04sdpsd
    @04sdpsd 3 ปีที่แล้ว +1

    Is there any way to have an Micro 820 communicate with a Schneider Magelis HMI, utilizing either Modbus TCP or Modbus RTU

    • @TimWilborne
      @TimWilborne  3 ปีที่แล้ว +1

      Both should be possible, we have videos coming soon on Modbus with the Micro800 PLCs.

  • @anddrewb1367
    @anddrewb1367 3 ปีที่แล้ว +1

    Is there a way to make the alarm tab change colour when there is an active alarm?

    • @TimWilborne
      @TimWilborne  3 ปีที่แล้ว +2

      Yes, I'm going to do a video on it later where I change the alarm button to red when there is an active alarm.

  • @adamhassell
    @adamhassell 2 ปีที่แล้ว +1

    Hi all, I need the PLC to know which screen is currently displayed to do some logic on the PLC. (Read current screen only required, no need to set screen from PLC). I've added a global variable to the PLC called CURRENT_SCREEN as an int. I've added this variable on the Panelview global tags as a source for the system tag "Current Screen Number". In the PLC logic it is correctly reading the screen ID but when I try to change screens using the go to screen buttons on the HMI its alarming: "2053 Screen switching controlled by external source". Help! I'm not trying to switch the screen from the PLC, just read which screen is current.

    • @TimWilborne
      @TimWilborne  2 ปีที่แล้ว +1

      It sounds like you assigned it to both the source and destination tag, it only needs assigned to the destination tag if you are reading it.

    • @adamhassell
      @adamhassell 2 ปีที่แล้ว +1

      @@TimWilborne Thanks Tim, I did manage to solve this, quite a rabbit hole but I'll post the solution here in case anyone else has this problem. You have to create a rung that polls the destination tag variable (I did a check every 100ms). If the destination tag variable is > 0 then store the value to a local variable (this value is the ID of the current screen showing) then write a 0 back to the destination tag variable. Writing a zero gives screen selection control back to the HMI, if you don't return control after polling then you get the 2053 error when you try to switch screens via the HMI buttons. Seems like awkward behaviour. This might be worth a video on its own...

    • @TimWilborne
      @TimWilborne  2 ปีที่แล้ว +2

      @@adamhassell Thanks for the follow up. I'll have to experiment with that.

  • @kekdkxlhxnffkwrrk
    @kekdkxlhxnffkwrrk ปีที่แล้ว +1

    ingeniero,como puedo rotar una imagen o grafico a 0°,90°,180° etc?

    • @TimWilborne
      @TimWilborne  ปีที่แล้ว +2

      I don't think you can rotate an image on the Panelview 800, so you would need to make different views of it for the different angles before hand then use a multistate indicator to change between the different angles.

    • @kekdkxlhxnffkwrrk
      @kekdkxlhxnffkwrrk ปีที่แล้ว +2

      @@TimWilborne entonces,tengo que crear un grafico nuevo otro programa,ese mismo grafico que viene en la librería no puedo girarlo?,o hacerle un espejo para que cambie de dirección o vista.

    • @TimWilborne
      @TimWilborne  ปีที่แล้ว +2

      I don't believe so in the Panelview 800. Let me know if you find a way.

  • @JohnSmith-lv8xk
    @JohnSmith-lv8xk 3 ปีที่แล้ว +1

    How would you utilize the F keys on the 4" screen ?

    • @TimWilborne
      @TimWilborne  3 ปีที่แล้ว +1

      I don't recommend using the F keys at all! If you can't interface with the operator with the 4" screen, then get a bigger screen.

    • @JohnSmith-lv8xk
      @JohnSmith-lv8xk 3 ปีที่แล้ว +1

      @@TimWilborne Wow, alright then 😁

    • @TimWilborne
      @TimWilborne  3 ปีที่แล้ว

      @@JohnSmith-lv8xk Yes, it is one of the things I do have a strong opinion about :)