FM 200 FIRE SUPRESSION SYSTEM HOCHIKI,VES,FIREPRO,AVENGER CONTROL PANEL

แชร์
ฝัง
  • เผยแพร่เมื่อ 10 ก.ย. 2024
  • THIS PANEL CAN BE USED FOR VARIOUS TYPES OF FIRE SUPRESSION INCLUDING FM 200,NOVEC,ECO,FOAM SYSTEM,DELUGE WATER,PRE ACTION SYSTEMS PART 1

ความคิดเห็น • 67

  • @edwaynemago2633
    @edwaynemago2633 11 หลายเดือนก่อน +1

    end of line resistor (EOL) must be installed in the last devices for supervisory if someone removes the devices no trouble or supervisory in the control panel

  • @IkihiroCostillas
    @IkihiroCostillas 5 วันที่ผ่านมา

    Thank you so much

  • @EngrJrmt
    @EngrJrmt 7 หลายเดือนก่อน

    If someone press the manual extinguishant release will the horn and strobe lights activated then within 10 seconds it will release the aerosol? And in the disablement/supervisory will the manual release led light will turn on?

  • @engineersguide4249
    @engineersguide4249  3 ปีที่แล้ว

    ALL QUESTIONS AND SUGESTIONS WILL BE ANSWERED AND TAKING INTO ACCOUNT RESSPECTIVELY WHEN THE CONCERNS ARE RAISED HERE..THANK YOU

    • @safeyourself4755
      @safeyourself4755 3 ปีที่แล้ว

      We are using these panel but most of the panel key problem when we turned the key panel not working

    • @powerfulsermons5465
      @powerfulsermons5465 3 ปีที่แล้ว

      Could you send me photos of the panel and what u want to do I will be glad to help

    • @engineersguide4249
      @engineersguide4249  3 ปีที่แล้ว

      Mainly the key access needs to be turned to access the functioning of the buttons. There is one key switch called enable access turn it to the right side and access it, if it's another issue too pls let me know tnx 😊

    • @ericazure7569
      @ericazure7569 3 ปีที่แล้ว

      Please after installing the panel all the zone light is on please what's that place

    • @ericazure7569
      @ericazure7569 3 ปีที่แล้ว

      Please can i get ur contact ?

  • @user-sy6js4lg4o
    @user-sy6js4lg4o 27 วันที่ผ่านมา

    Can this board that you are explaining on be replaced with a shppro control board (fike) while keeping the same devices?

    • @engineersguide4249
      @engineersguide4249  7 วันที่ผ่านมา

      @@user-sy6js4lg4o yes you can but few modifications has to be done

  • @safaakadhim5040
    @safaakadhim5040 หลายเดือนก่อน

    Hello, how are you
    Mr , I have a simple question
    Why does a signal appear?
    Release trouble
    When connecting the selenoid to the cylinder
    As soon as I turn off the selenoid, the signal disappears. I hope you can find a solution for me

    • @engineersguide4249
      @engineersguide4249  หลายเดือนก่อน

      @@safaakadhim5040 share with me the type of solenoid you using

  • @syedaslam2856
    @syedaslam2856 2 ปีที่แล้ว +1

    What is the use of resistors connected on top side of the controller and what is their value

    • @engineersguide4249
      @engineersguide4249  2 ปีที่แล้ว +1

      It's called end of line resistor to keep system normal and monitor each line ..6.8k and 10k

  • @user-qu2yw3qy6m
    @user-qu2yw3qy6m ปีที่แล้ว +1

    Pleas clarify the connection of shield A-xT fm 200 panel to detctor ,manual releas and soundr,electric bell

    • @engineersguide4249
      @engineersguide4249  ปีที่แล้ว

      It's same as connecting conventional detectors,the mps needs 470ohms resistor to trigger it

  • @losta7008
    @losta7008 2 ปีที่แล้ว

    Thanks for clarification. My question is for stage 1, stage 2 & trouble relay there are resistance, why that?

    • @engineersguide4249
      @engineersguide4249  2 ปีที่แล้ว

      it is for the fire alarm module and since the panel is the end of line,so we connect incase it gets open or removed it will notify fire alarm

    • @losta7008
      @losta7008 2 ปีที่แล้ว

      @@engineersguide4249 thanks. But as you clarified. The resisiter will isolate the signal in the panel. And if there any cut in wire it will not appears in a board of the panel!

    • @engineersguide4249
      @engineersguide4249  2 ปีที่แล้ว

      @@losta7008 it wont but it will appear on the fire alarm panel

    • @bmmarufniloy3024
      @bmmarufniloy3024 2 หลายเดือนก่อน

      It would be helpful to know the value of the register

  • @NasirUddin-sk2sz
    @NasirUddin-sk2sz ปีที่แล้ว

    Our general trouble then I check silence/sounds alarm after fire light coming

  • @zenaidarios5204
    @zenaidarios5204 2 ปีที่แล้ว

    I have one question why they use 2.5mm cable for horn strobe and bell instead 1.5mm because the supply is 24vdc only

    • @engineersguide4249
      @engineersguide4249  2 ปีที่แล้ว +2

      1.5MM ARE USED FOR INPUT DEVICES AND 2.5MM FOR OUTPUT DEVICES BECAUSE WHENTHERE IS AN ALARM THE AMPS INCREASES WHEN ITS AT WORK.SO TO ESCAPE FAULTS LIKE GROUND FAULT DURING ALARM ACTIVATION AND OTHER RELATED TROUBLES ITS RECOMMENDED TO USE 2.5MM

  • @frilwan6522
    @frilwan6522 2 ปีที่แล้ว

    Dear brother nice video...
    Can you pls explain me about the additional relay for AC shutdown.
    From where you provide power to the relay and from where you will provide input signal to the relay , if we want to shutdown the AC in first stage...
    Thanks

    • @engineersguide4249
      @engineersguide4249  2 ปีที่แล้ว

      you can directly loop the neutral cable of the AC using the fire relay in normally closed condition...it will go off on 1st stage alarm

  • @hameedvp3490
    @hameedvp3490 10 หลายเดือนก่อน

    Sir how to solve and reset cpu foult pleas help...
    Showing cpu foult led and general foult led

    • @engineersguide4249
      @engineersguide4249  10 หลายเดือนก่อน

      you can only solve that by removing the power supply and battery to make the panel off for 30 secs and fix back problem is solved

  • @nithyakumarwhatsappstatus1034
    @nithyakumarwhatsappstatus1034 ปีที่แล้ว

    Please help me sir . Earth fault comming always i found it Earth. detector cable not possible cahange cable. iwant stop Earth trouble .

    • @engineersguide4249
      @engineersguide4249  ปีที่แล้ว

      first and foremost you have detect where the earth fault is coming from by removing the device cables one after the other till u see the earth fault gone so u can find the root cause of it .there is a code to disable earth fault trouble but the earth fault light will still be on ..check and update me and will advice you on what to do

    • @nithyakumarwhatsappstatus1034
      @nithyakumarwhatsappstatus1034 ปีที่แล้ว

      Thank you very much sir. I found it ,zone 1 detector cable when remove Earth fault going . Spare pair cable was there i connect it now normal. Thanks for ur advice . If i have any doubt i message u sir

    • @JafarKhan-pf3eu
      @JafarKhan-pf3eu ปีที่แล้ว

      How to disable earth fault

  • @Ariyan98060
    @Ariyan98060 ปีที่แล้ว +1

    Sir How solve Exiting trbl ?

    • @engineersguide4249
      @engineersguide4249  ปีที่แล้ว

      check your diode at the extiguishant area and replace it if possible

  • @jommelvictoria9693
    @jommelvictoria9693 2 ปีที่แล้ว

    Sir can you help me i have also a same panel that you have my problem was i already put two zone and my alarm bell was put on nac1 but when i was try to activate the detectors it shows panel only trouble not fire can you help me about this please thanks alot

    • @engineersguide4249
      @engineersguide4249  2 ปีที่แล้ว

      which way do you trigger the alarm, is it through the smoke detector or mcp lemme know

  • @mikemakokha8931
    @mikemakokha8931 2 ปีที่แล้ว

    How do I connect Ac shutdown, GSM, and the 2nd stage sounder can not silence when I press the button

    • @engineersguide4249
      @engineersguide4249  2 ปีที่แล้ว

      get an external relay rather than connecting direct

  • @falcond214
    @falcond214 2 ปีที่แล้ว

    I have fire zone and whenever I connect the power the alarm sounds will start. How can I stop and clear this

  • @MostafaMohamed-op3ch
    @MostafaMohamed-op3ch ปีที่แล้ว

    Nice video .. could you support me with any book in programming or in this field in general .. please

    • @engineersguide4249
      @engineersguide4249  ปีที่แล้ว

      All the programmings are pasted at the door of the panel when you open it ..will do a video on that to help out

  • @sekarjeya474
    @sekarjeya474 11 หลายเดือนก่อน

    What abt Nac3 what is the use of Nac3

    • @abdulraheem670
      @abdulraheem670 7 หลายเดือนก่อน

      NAC-01 USED FOR INDOOR BELL ( INSIDE THE ROOM) AND NAC-3 WILL USED OUT DOOR SOUNDER WITH FLASHER (OUT SIDE THE ROOM)

  • @saifrohad6297
    @saifrohad6297 ปีที่แล้ว

    I want to stop / disbale the panel sound which is contionusly beeping

  • @saifrohad6297
    @saifrohad6297 ปีที่แล้ว

    How can i disable or stop the beep beep continous sound..

  • @al_up61
    @al_up61 ปีที่แล้ว

    How to solve power troubles problems?

    • @engineersguide4249
      @engineersguide4249  11 หลายเดือนก่อน

      check on your ac supply it suppose to be 220v and battery 24v

  • @Itself686
    @Itself686 2 ปีที่แล้ว

    In this panel how to remove releasing trouble

  • @JafarKhan-pf3eu
    @JafarKhan-pf3eu ปีที่แล้ว

    How we can remove earth fault from panel

    • @engineersguide4249
      @engineersguide4249  ปีที่แล้ว

      Try removing the cables one after the other while checking which one will let the fault go then if u get the particular cable inspect to find out where the short is and correct it

  • @aleemfoodview9632
    @aleemfoodview9632 2 ปีที่แล้ว

    Can you pressure switch connect send pictures

    • @abdulraheem670
      @abdulraheem670 7 หลายเดือนก่อน

      Low pressure switch two wiring same colour will be connected From the Panel Red Colour Cable added 470k Resistance with other side 6.8k resistor another side of 6.8k resister will connect with black wire coming from the panel

  • @kotadevendar4299
    @kotadevendar4299 2 ปีที่แล้ว

    General trouble and power trouble how to close

    • @engineersguide4249
      @engineersguide4249  2 ปีที่แล้ว

      check the small indication light below it will give you the exact trouble,but the main is AC power loss or Battery low or battery failure