Simple Earth pit resistance test (how to test it) | Earth Tester | Earth resistance Tester

แชร์
ฝัง
  • เผยแพร่เมื่อ 4 เม.ย. 2019
  • #earthingtest #earthpittest #earthtester #SustainableEveryDay
    If you are targeting Solar Industry jobs in Dubai , then this might be "SUPER helpful"
    Important Video: • Crack All Engineering ...
    Learn all About Solar Plant DATA analytics & advance report creation:
    www.udemy.com/course/learn-so...
    Digital CV creation for Dubai JOBS on Solar PV Industry:
    www.udemy.com/course/crack-al...
    For Questions/Technical support connect with me.
    Subscribe:bit.ly/2XoCPH8
    Linkdln:bit.ly/3xG9tQX
    Instagram:bit.ly/3jLSV5e
    Facebook:cutt.ly/JQDl7Ba
    Quora:bit.ly/3iFvM4X
    Telegram Solar Group:bit.ly/3iFC2d9
    Twitter:bit.ly/3iEYdQw
    SOLAR DC cable MEGGER TEST - • SOLAR DC cable Insulat...
    Solar DC Cable management - • Solar DC cable Managem...
    1500VDC Solar Plant - • 3MW Solar Central Inve...
    Solar Plant Thermography - • solar plant thermography
    Wrong PR%😭 What to do?? - • Solar PR% issue | Sens...
    Solar Plant SECRET - • Solar Plant SECRET , ...
    Tilt 📐/ Orientation📈 without PvSyst - • Tilt / Orientation wit...
    Solar☀️ Plant 🔺 Thermography❗ - • solar plant thermography
    Solar 100kw Plant , perfect installation - • 100KW Solar Plant | in...
    Solar Plant power Factor🚫- • Solar Plant | Power Fa...
    Solar Plant Specific Yield ?? - • Solar Specific Yield ?...
    Solar Plant AC/DC earthing ? Why - • Solar Plant Earthing |...
    Solar 🌞Net Meter Fault Solution - • Net metering Import v...
    Solar 🌞 PID LOSS 📉♻️- • PID loss in SOLAR Pane...
    Solar Plant Measurements - • Solar Plant Measuremen...
    Solar Plant 🌞Ground Fault - • Solar Plant Ground Fau...
    Solar Inverter Derating 🔥- • Solar inverter Deratin...
    Solar Plant Overheating Issue🔥- • Solar Plant Over heati...
    Solar Eclipse 🌞🌜Genration Analysis - • Solar Eclipse Genratio...
    Free Pvsyst software Book ♻️- • Free PvSyst Documents ...
    Solar Plant money Payback Calculation 💵- • Solar Plant Money Retu...
    Solar🌞 plant LA earthing Calculation in हिंदी में♻️- • Solar Plant LA selecti...
    Types of Solar🌞 cell Fault👨🏻‍🔧 हिंदी में - • Types of Defects in So...
    Solar🌞 inverter Selection calculation👨🏻‍🔧 हिंदी में - • Solar Inverter Selecti...
    Solar 👨🏻‍🔧Parking 🚕Installation 👨🏻‍🔧 हिंदी में - • Solar Parking | Cost |...
    Solar tilt angle & Azimuth experiment🔅- • Video
    Middle East Energy expo🔅♻️- • Middle East Energy exp...
    How to use PVSYST software🖥️- • Video
    Solar AC cable sizing Calculation👨🏻‍🔧- • Solar AC cable sizing ...
    Solar DC CABLE sizing Calculation👨🏻‍🔧- • Solar DC cable calcula...
    Solar DC earthing systems Calculation👨🏻‍🔧- • Solar DC earthing calc...
    Calculate Solar Plant PR%🌞- • Calculate Solar plant ...
    SOLAR PV modules comparison🔅- • Calculate How to Selec...
    Solar Earth pit resistance Test 👨🏻‍🔧- • Simple Earth pit resis...
    Best Solar panel 🌞cleaning method part 1 - • Best Solar Panel clean...
    Best Solar panel 🌞cleaning method part 2 - • Best Solar Panel clean...
    Renewable energy India Expo♻️- • REI Renewable energy I...
    Solar DC👩‍🔧 string Fault Rectification method - • Solar DC string curren...
    How does solar panels catch fire🔥- • Solar Cell Hotspot, कै...
    Solar cell working in Hindi🌞- • Solar Cell Working in ...
    Rooftop Solar plant visit🌞- • Understand solar plant...
    How to check Solar Delta Inverters👩‍🔧- • Delta Solar string inv...
    Solar Plant thermography test 🔅- • Thermography test of s...
    Earthing test
    Earth pit
    Earthing
    How to test earthing
    How to test earth resistance
    earth pit testing,
    earth pit testing in tamil,
    earth pit testing in hindi,
    earth pit testing with megger,
    earth pit testing in telugu,
    earth pit testing with megger in tamil,
    earth pit testing methods,
    earth pit testing meter,
    earth pit test procedure,
    earth pit test value,
    how to test earth pit resistance,
    earth pit megger test,
    how to earth pit test
    Connect with me on Linkdln / himanshu-tewari-58994413a
    How to use clamp meter • MECO AC/DC CLAMP METER...
    Voltage testing with clamp meter • Solar plant How to che...
    Solar string inverter how to check • Delta Solar string inv...
    Earthing test • Simple Earth pit resis...

ความคิดเห็น • 170

  • @syedmohammadsaif8344
    @syedmohammadsaif8344 3 ปีที่แล้ว

    Spikes jo E2 aur P2 ki through he kya earth pit k series or line me lena he ya kahi bhi lagaskte he bas 10m or 20m from tester ??

  • @avin5472
    @avin5472 4 ปีที่แล้ว +1

    Hi sir, You have taken the distance from E1(P1) to P2 as 10m and then P2 to E2 as 10m again. But in the connection diagram of the earth tester it's 0.62 D and 0.38D, which means they shouldn't be equal.

  • @ramanactive6412
    @ramanactive6412 3 ปีที่แล้ว +2

    3 wires connected together and 1.25 ohms substract... is it right procedure?
    Is it as per IS?

  • @abdulnafayawan8683
    @abdulnafayawan8683 3 ปีที่แล้ว

    Nice information. Also tell about the value of voltage between Vm3 Inverter solar input points to ground value .

  • @venkatesanvijaya5104
    @venkatesanvijaya5104 4 ปีที่แล้ว

    Sir what is output voltage range of DET 2000 used . AC or DC volts

  • @SachinKumar-yg1tq
    @SachinKumar-yg1tq 4 ปีที่แล้ว +1

    awesome video thanks for this great content.

  • @jameszosangliana8113
    @jameszosangliana8113 ปีที่แล้ว

    Kafi informative lag raha tha, mahar mujhe to yeh samaj mai nahi aya khi yellow wire kaha se shuru hoti aur kah stop..Pls😮

  • @tpgaderiya
    @tpgaderiya 5 ปีที่แล้ว +1

    Sir ek baat bataiye pls meri earthing ki reading 0.2 aa rahi h to kya galat h

  • @suryaprakasheng
    @suryaprakasheng 3 ปีที่แล้ว

    Thanks

  • @oroknowledge2232
    @oroknowledge2232 2 ปีที่แล้ว

    10qu is it possible to use earth tester for installation of diesel generator

  • @satishgajini9086
    @satishgajini9086 4 ปีที่แล้ว +5

    Sir ,if I want to measure the resistance between 2 wires (BSNL for ex 1km ) will this meter support. If it support at which I have to connect Plz reply me

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว

      This is earth tester , the test you want to do , you will require a megger device it will give you better result

  • @Manavsain00
    @Manavsain00 3 ปีที่แล้ว

    Sir oms ya mega oms hona chahiye.wese kam se kam 1megaoms hona chahiye kya bis k anusar.

  • @technicalthinks5981
    @technicalthinks5981 2 ปีที่แล้ว +1

    Sir you said that resistance should be less then 5 ohm but here is 12.6 ohm?

  • @vgksatya1969
    @vgksatya1969 2 ปีที่แล้ว +1

    nice video jeethe raho..

  • @jayantaostad6426
    @jayantaostad6426 4 ปีที่แล้ว

    Sir how will be check the 100 ton weighbridge earth resistance ?

  • @otimalfred8390
    @otimalfred8390 2 ปีที่แล้ว

    hello sir how are you please can you share with me the prices for those earth tester meter

  • @MHBDUBAI
    @MHBDUBAI 3 ปีที่แล้ว

    What will be depth of each electrodes P2 and E2?

  • @manusharma9837
    @manusharma9837 4 ปีที่แล้ว +4

    Earth Pit 1 = for ACDB & Inverter.
    Earth Pit 2 = for DCDB, Panals & structure.
    Earth Pit 3 = for Lightning Arrester.
    Is it proper way to do earthing for 3kw solar plant?

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว +5

      EP - 1 no. DCDB + INVERTER body dc section+ panels + structure
      EP - 2 Nno. ACDB + INVERTER AC section
      EP - 3 For LA

    • @manusharma9837
      @manusharma9837 4 ปีที่แล้ว

      @@SustainableEveryDay Thanks a Lot G

  • @AbhishekKumar-eu4ne
    @AbhishekKumar-eu4ne 4 ปีที่แล้ว +1

    thanks for video

  • @tabasumali7682
    @tabasumali7682 2 ปีที่แล้ว

    Sir please hamen yah bataen ki hamare solar plate dhone se platon ko hath lagane se current padta hai

  • @OmarAlvi
    @OmarAlvi 3 ปีที่แล้ว

    Brilliant and Detailed demonstration
    Only thing I want to ask,
    This one reading is suffice or we have to taken multiple readings on different distances and average out them all?
    Thanks in advance, Very informative video.

  • @prajapatiroy5393
    @prajapatiroy5393 3 ปีที่แล้ว

    Nice

  • @anaspatel7970
    @anaspatel7970 3 ปีที่แล้ว +1

    Hi
    Can. We use this instrument to check underground water for bore well

  • @vishnuprakash3187
    @vishnuprakash3187 3 ปีที่แล้ว

    How did ypu get to the yellow wire from the blue wire. Not explained properly.

  • @maruthupandi8213
    @maruthupandi8213 4 ปีที่แล้ว +2

    my doubt is , it is necessary to fix both p2 & e2 in a same direction, then your answer is yes means, what will happen if we fix that auxiliary electrodes in a oposite opposite direction .can you please clear me

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว +1

      No you can fix it in different directions , I did it because the land was cemented , so I had no option

  • @gourangasasmal8815
    @gourangasasmal8815 4 ปีที่แล้ว +2

    Thank you sir for your video,
    Why you subtract 1.25 from main value

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว +3

      Thanks for your support Gourang, the value 1.25 is the material resistance of the GI strip and earthing rod, so this value has to be subtracted from final value to get exat resistance of earthing pit.

    • @MohammadIrfan-xp7sr
      @MohammadIrfan-xp7sr 4 ปีที่แล้ว

      You again listen to the video.actually we want to find the earthing resistance of the earthing rod as well as the earthing resistance of the soil in which the earth rod is present that is rod+soil only.But since while measuring the resistance of those two things, you are using red and green and blue electric wires, the result on the meter will show a combination of three things( rod+soil+ colored wires).so in the video he measures the resistance of the colored wires separately which is 1.25 ohm.So to find only resistance of rod+soil,you have to subtract 1.25 ohm from the reading given on the meter( which was about 13).

  • @trimafs
    @trimafs 4 ปีที่แล้ว +1

    Thanks for your video sharing its very informative, i want to ask one question in this case we get resistance of 12.16 ohm how we will bring it to 5 ohm ? awaiting for your valuable reply

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว

      In order to reduce the resistance of the earth pit , we will have to increase the conductivity of the earth pit , so for that we usually drain 10L water mix with salt in the earth pit

    • @trimafs
      @trimafs 4 ปีที่แล้ว

      as i know if we have current more than 200A we use minimum 2 earth pits than how we will measure earth resistance either we have to connect both earth pits and then measure or any other method plz reply

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว

      See usually in case of dual or tri vector earthing , we test the resistance of individual earth pit , not by connecting 2 together , as per the IEC standards an individual earth pit should offer a resistance of 5ohms or below it , which is a safe limit and ensures that if you have a heavy leakage current then at this resistance it will be smoothly absorbed by earth

    • @syedmohammadsaif8344
      @syedmohammadsaif8344 3 ปีที่แล้ว

      Put water & salt into earth pit

    • @mohanjha3302
      @mohanjha3302 ปีที่แล้ว

      ​@@SustainableEveryDay😊

  • @zalamahipatsinh4327
    @zalamahipatsinh4327 3 ปีที่แล้ว +5

    Bhai aapne 10 ohn pe range set kiya tha, to phir value 13 ohm kyu aaya, aur as pe standards 5ohm hona chahiye

    • @jitendrajhafitness
      @jitendrajhafitness 2 ปีที่แล้ว +1

      Bro 10 ka matalv 2 digit.vala 😊 Agar achha lage to subscribe kar dio Merko ko

    • @mohanji5530
      @mohanji5530 11 หลายเดือนก่อน

      ​@@jitendrajhafitnesssir ager hum es ku 1000ohm pye set kregye tu kya es ka value 00.13ohm hi ayyega pl tell us thanks u

  • @balabalaji4770
    @balabalaji4770 4 ปีที่แล้ว +1

    Hi sir the direction of E2 changes what will be happen?
    P2 after E2 is necessary or not?

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว +1

      Changing the direction can make the distance between earth electrode and test electrode E2 , close to the value of resistance which you will get will not be according to the standard test procedure of earth test

  • @manusharma9837
    @manusharma9837 4 ปีที่แล้ว

    Can we use 4mm thickness Aluminium wire to connect LA with earthing?
    If not then what is the alternate of GI strip?

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว +1

      4mm conducter is actually underated , and not at used for earthing , and lightning surge are heavy , as you know the charges only flow on the surface of the conductor so you need higher cross-section conducter , only use 25mmx3mm GI flat strip

  • @aashutoshkumar3966
    @aashutoshkumar3966 4 ปีที่แล้ว

    Why use 2 electrode for earthing value test

  • @truthbolo6114
    @truthbolo6114 9 หลายเดือนก่อน

    Kyy load connect ho tab resistance check hoga???

  • @sujitkumar6123
    @sujitkumar6123 3 ปีที่แล้ว

    Tin taar ke baare me kuchh information dijiye na

  • @user-pt2ln7fe3e
    @user-pt2ln7fe3e 3 ปีที่แล้ว +2

    I don't have an earth tester. Is there a way to test it with a multimeter.

  • @sjcreation6459
    @sjcreation6459 2 ปีที่แล้ว +1

    Sir which type of glouse are you using please tell

  • @engrakram3649
    @engrakram3649 4 ปีที่แล้ว +2

    Repeat the same with analog meter

  • @yaseenalimohammed4443
    @yaseenalimohammed4443 4 ปีที่แล้ว

    Hi sir , in indian we are using different earth pits for both AC( inverter & LA) & DC( stru & invr) is there any particular reason for this ?

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว

      Better protection

    • @123qatar7
      @123qatar7 4 ปีที่แล้ว

      @@SustainableEveryDay
      Solar Panel K moveable stand c LA ki hight kitni honi chaye?
      Top level of Pv Panel c above honi chaye ?

  • @thetravelend
    @thetravelend 4 หลายเดือนก่อน

    Electrode kitna metre Jamin mai gaadna hai

  • @niaziexplores
    @niaziexplores 3 ปีที่แล้ว +1

    👌

  • @devanandthakare2263
    @devanandthakare2263 4 ปีที่แล้ว +1

    Why earth resistance tester is not working in EHV transmission lines
    Please reply sir as early as possible . Thank you

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว +1

      EHV transmission line usually have end to end transformer earthing , so even it Earth test is conducted it is done at transformer end

  • @devanandthakare2263
    @devanandthakare2263 4 ปีที่แล้ว +1

    Can I use earth resistance tester for measurement of earthing of EHV 400 kV transmission lines

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว

      Yes definitely

    • @devanandthakare2263
      @devanandthakare2263 4 ปีที่แล้ว +1

      @@SustainableEveryDay thank you

    • @dvice2350
      @dvice2350 3 ปีที่แล้ว

      Bhai koi batiyga ki 115 kv ka kitna ohm hona chya or 13.8 kv ka kitna or 440 ka kitna hai standard

  • @Shaanutry
    @Shaanutry 4 ปีที่แล้ว +1

    Hi, What is the standard value for earth pit resistance??

  • @vinaykumarbl8654
    @vinaykumarbl8654 ปีที่แล้ว

    Why short E1 and P1..?

  • @engrazharsheikh4931
    @engrazharsheikh4931 3 ปีที่แล้ว

    I want to buy earth resistance tester.Please advise me good type and brand I should buy at reasonable price

  • @shuklanilabh8612
    @shuklanilabh8612 หลายเดือนก่อน

    link to second part please

  • @azharkhan7598
    @azharkhan7598 ปีที่แล้ว

    Why you are combining the yellow 🟡 and red 🔴

  • @Rahulmishra-xy5rx
    @Rahulmishra-xy5rx 4 ปีที่แล้ว

    Himanshu kya haal chal h kis company me ho abhi......

  • @praveensharma8768
    @praveensharma8768 5 ปีที่แล้ว +1

    What is the Reason behind 10 and 20 mtr electrode. Why it is necessary.

    • @SustainableEveryDay
      @SustainableEveryDay  5 ปีที่แล้ว

      The electrode E1, P1 passes current in soil which is detected by earth pit at a fixed voltage by device so by formula V=I/R the device calculate R i.e. Resistance of soil

  • @deepsinghthakur8268
    @deepsinghthakur8268 ปีที่แล้ว

    Why earthpit connection disconnected

  • @entertaintube335
    @entertaintube335 4 ปีที่แล้ว +1

    Pit resistance is 12.16 ohms..
    Is this good earthing ???
    I heard that earthing should be less than 5 ohms..
    Please share your views brother..
    You explained well but conclusion is not clear..please explain ..
    I would be thankful to you

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว +4

      The reason why we conducted this earth resistance test because we had a doubt on this earth pit , as we detected that AC voltage between the neutral and earth was coming about 20-22v which was beyond limit ,
      You are absolutely right the pit resistance should be below 5ohms , but ours was 12.16ohms , so what we did to improve it , we immersed 20liters mixture of water with rocksalt inside the earth pit to lower the resistance , and finally got value below 5ohms

    • @entertaintube335
      @entertaintube335 4 ปีที่แล้ว +1

      @@SustainableEveryDay thank you so much for your assistance....if you could have made a video of remaining part ..it would be a piece of cake...

  • @RakeshDas-zu1rq
    @RakeshDas-zu1rq 4 ปีที่แล้ว +1

    Sir value jyada nahi hai???
    Earth resistance value kitna honi chahiye sir??

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว +1

      Yes ,our value was high , is leye humne earth test conducted keya tha, kyuki humara solar inverter was facing overvoltage issue ,the standard value of proper Earth pit should be below 5ohms

  • @vickykumar6212
    @vickykumar6212 3 ปีที่แล้ว

    I have found 18 ohm in chemical earthing , how will come below of 5 ohm.

    • @endlessuniverse9312
      @endlessuniverse9312 ปีที่แล้ว

      Chemical earthing is cheap in cost .
      If you want power full earthing then go for GI PIPE MINIMUM 38MM TO 50MM(ISI) (TATA,JINDAL) OR go for COPPER PLATE earthing. in both types of earthing coal and salt are used. minimum 8 feet depth. For better result. please provide watering pipe for regularly maintain earth resistance below 5 ohms by adding saulty water every 3 to 6 months as per your requirements

  • @DurgeTech
    @DurgeTech 5 ปีที่แล้ว +3

    E1 p1 ko short kyun karte hai
    ..?

    • @SustainableEveryDay
      @SustainableEveryDay  5 ปีที่แล้ว

      It it a method to complete the circuit, by shorting E1, P1, iske alawa soil resistance test ke time all 4 points E1, P1, E2, P2 is used no point is shorted

  • @tpgaderiya
    @tpgaderiya 5 ปีที่แล้ว +1

    Sir mene 200 V~ pr check kiya h mere meter ka nam DT830D digital multimeter pls sir bata dijiye

  • @NAZIRAHMAD-ps6pw
    @NAZIRAHMAD-ps6pw 3 ปีที่แล้ว

    That means the value you are getting it shows the earth pit is not correct..?

  • @jayanandamohanty260
    @jayanandamohanty260 4 ปีที่แล้ว +1

    How many meter deep ground a electrod

  • @abhijayjain
    @abhijayjain 2 ปีที่แล้ว +2

    in vit students do not know hindi so please speak in english

  • @pavankumarbikkavolu9055
    @pavankumarbikkavolu9055 4 ปีที่แล้ว +1

    Y ethna distance se placed electrodes

  • @murshaddadarvesh7338
    @murshaddadarvesh7338 3 ปีที่แล้ว +1

    Bhai agar value zada ho to kaise thik kare Gaye earthing ko

  • @MZ-ri9dc
    @MZ-ri9dc 3 ปีที่แล้ว +1

    👍👍👍👍👍

    • @SustainableEveryDay
      @SustainableEveryDay  3 ปีที่แล้ว

      Thanks

    • @rajshriwastav2335
      @rajshriwastav2335 3 ปีที่แล้ว

      @@SustainableEveryDay sir apne E2, P2 wire ko distance me kyo le gye isko justify kr dijiye pls

  • @AsifAnsari-zh8ef
    @AsifAnsari-zh8ef 2 ปีที่แล้ว +1

    Sir Earth testing apne kaha ki iski veleu 5ohm se km honi chahiye to fir 13ohm kyu aari h

    • @SustainableEveryDay
      @SustainableEveryDay  2 ปีที่แล้ว

      Ye site mai overvoltage ka issue tha , that's why we were testing this Faulty earth pit

    • @JitendraKumar-zm2hg
      @JitendraKumar-zm2hg 6 วันที่ผ่านมา

      How earthing linked with overvoltage.

  • @kuldeeptiwari954
    @kuldeeptiwari954 6 หลายเดือนก่อน

    Clear nahi ho pa Raha hai
    Simple hai pr AAP ne critical bana diye

  • @sathyanathan5793
    @sathyanathan5793 ปีที่แล้ว +1

    Analog insulation tester best company name please

  • @arunborewellpoint
    @arunborewellpoint 2 ปีที่แล้ว

    price

  • @mangeshr979
    @mangeshr979 2 ปีที่แล้ว +1

    How to short 3 wire

  • @assonam4411
    @assonam4411 3 ปีที่แล้ว +1

    Sir earthing response stay n ho rha ho lgatar up down Ho rha ho to kya kiya jae ki sahi response mile chemical earthing me

    • @SustainableEveryDay
      @SustainableEveryDay  3 ปีที่แล้ว

      Put 25L of water mix with rocksalt in earth pit

    • @assonam4411
      @assonam4411 3 ปีที่แล้ว +1

      @@SustainableEveryDay Sir responce thik aa jaega fir sir

    • @assonam4411
      @assonam4411 3 ปีที่แล้ว

      20 feet deep tk chemical earthing huwa hai sir fir bhi response me up down Ho rha hai aisa kyu ho rha hai sir aur Kaise thik hoga

    • @SustainableEveryDay
      @SustainableEveryDay  3 ปีที่แล้ว

      Yes

    • @SustainableEveryDay
      @SustainableEveryDay  3 ปีที่แล้ว

      Contacts proper hai na aap check kar lo, especially Earth & all Neutral line contact joints

  • @djelectricals34
    @djelectricals34 4 ปีที่แล้ว +1

    nice

  • @shivaramdurgam4949
    @shivaramdurgam4949 5 ปีที่แล้ว

    Why should take 10m distance

    • @SustainableEveryDay
      @SustainableEveryDay  5 ปีที่แล้ว

      This is a standard set in the industry to measure the resistance, for earth test because for different distance you will get different values, which will confuse you

  • @MegaAjaydas
    @MegaAjaydas 10 หลายเดือนก่อน

    Need help

  • @cartoonhub1945
    @cartoonhub1945 4 ปีที่แล้ว +1

    but you said it should be less than 5ohm

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว

      Yes so this earth pit failed the test , its value is more than 5ohm

  • @mukeshbhardwaj1756
    @mukeshbhardwaj1756 4 ปีที่แล้ว +1

    But earth value is less then 1 ohm's honi cahiye na

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว

      Correct , isleye video mai jo earthing hai wo Earth test mai fail ho gaye

  • @s200029928
    @s200029928 4 ปีที่แล้ว +1

    What is the Optimal earth resistance

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว

      Below 5ohm is all accepted ,

    • @s200029928
      @s200029928 4 ปีที่แล้ว

      @@SustainableEveryDay thank you for your prompt reply, another question if you may 😅. What is the resistance of a human body if corrected directly to earth

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว +1

      So it will totally depends on how harsh or dry the skin will be , it starts between 100,000ohms for extremely dry to 1000ohms for wet skin

  • @MHBDUBAI
    @MHBDUBAI 3 ปีที่แล้ว

    What is differences between Multimeter and Earth resistance meter?
    Can I use multimeter?

    • @SustainableEveryDay
      @SustainableEveryDay  3 ปีที่แล้ว

      Both are different equipment , and work differently

    • @oroknowledge2232
      @oroknowledge2232 2 ปีที่แล้ว

      @@SustainableEveryDay Earth resistance meter should be done only with earthy tester,if you use multimeter it will only indicate continuity but not the actual healthy of the earth pit

    • @SustainableEveryDay
      @SustainableEveryDay  2 ปีที่แล้ว +1

      @@oroknowledge2232 only with Earth resistance tester

    • @oroknowledge2232
      @oroknowledge2232 2 ปีที่แล้ว

      @@SustainableEveryDay is it possible to use earth tester for installation of diesel generator

    • @mohanji5530
      @mohanji5530 11 หลายเดือนก่อน

      ​@@oroknowledge2232dear sir pl tell if we check voltage between earth and neutral wire it is 5volt
      It means our earth is ok pl pl

  • @kartikchauhan3209
    @kartikchauhan3209 5 ปีที่แล้ว +1

    What if the resistance is more than 5 ohm ?

    • @SustainableEveryDay
      @SustainableEveryDay  5 ปีที่แล้ว

      Hi kartik
      Then the inverter will experience Abnormal performance as leakage AC and DC CURRENT will find it hard to travel towards the earth pit

  • @gourangasasmal8815
    @gourangasasmal8815 4 ปีที่แล้ว

    Or sir how much value suitable for earth resistant,

    • @jashwanthrko8870
      @jashwanthrko8870 4 ปีที่แล้ว +1

      When grid is connected resistance should be less than 1ohm and when grid is not connected it should be less than 5ohm.

  • @asifdhawalgi
    @asifdhawalgi 3 ปีที่แล้ว

    Resistance to under 5ohm hona chahiye tha

  • @dansmith2863
    @dansmith2863 4 ปีที่แล้ว +1

    What language is he speaking?

  • @amolmahajan5465
    @amolmahajan5465 5 ปีที่แล้ว

    But iska to 5 ohm jada hai, is it ol

    • @amolmahajan5465
      @amolmahajan5465 5 ปีที่แล้ว

      Is it ok

    • @SustainableEveryDay
      @SustainableEveryDay  5 ปีที่แล้ว

      No it's not ok, that is why we were testing it, there was lot of Inverter tripping so we checked the earth pit resistance

    • @Syntaxnuddin
      @Syntaxnuddin 5 ปีที่แล้ว

      What is the solution... Have u poured water and salt in earth pit?

  • @brijeshsharma6073
    @brijeshsharma6073 4 ปีที่แล้ว +1

    My earthing resistance is coming 0.12 is it perfect

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว

      Hi Brijesh what is the condition of the soil near earth pit is it dry soil or moisture soil

    • @brijeshsharma6073
      @brijeshsharma6073 4 ปีที่แล้ว

      @@SustainableEveryDay its normal dry and little bit sandy soil

    • @brijeshsharma6073
      @brijeshsharma6073 4 ปีที่แล้ว

      @@SustainableEveryDay please tell me what how it could be resolve

    • @chandranarayana6670
      @chandranarayana6670 4 ปีที่แล้ว

      0.45,0.27.0.80

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว

      Take a bucket with water 10liters and mix rock salt half kg in the bucket and pour the water in earthing pit which you want to test it will increase the conductivity of ground electrode

  • @engrakram3649
    @engrakram3649 4 ปีที่แล้ว +1

    Your demo is not clear. It wont help the beginners . your need to elaborate what is E1, P1, E2, P2. Similarly you then need to narrate why u short the E1 and P1.. Explain the depth of electrode. Explain it more to be more beneficial. Its not valuable..

    • @SustainableEveryDay
      @SustainableEveryDay  4 ปีที่แล้ว

      Well Akram you are right , many people have pointed out this , surely I will upload a better version

  • @franciscj8211
    @franciscj8211 3 ปีที่แล้ว

    This is not Standerd Earth Testing

  • @raytech6049
    @raytech6049 ปีที่แล้ว

    Most fake device ,
    Don't use it.