Very well explained. I have one doubt , in small buildings where we don't get 20 mtr straight length to insert earth test rods what is the solution. Pls suggest.
Yes you can check any time, in rainy season if the earth pit is wet then it will show good value. In summer it will show little less if earthing made properly.
No shock you will get. The test conducted by this device with very low voltage. But if you are checking a neutral earthing point of a live / Charged Transformer. You will be definitely electrocuted by heavy shock. Only in this case you have to Off Power Transformer when checking it's neutral ground earthing or ngr earthing. Very good question you asked and it is very important.
Agar hame Earthing ka Value check karna hai to ham log two wires se alag alag earth me dal ke voltage denge to us dono ka average Resistance pata chalega, jisse earthing resistance kahte hain. Resistance jitna kam utna acha mana jayega. Isliye mitti me ghusaya jata hai earthing rod ko.
Dono probe me ek hi voltage pass karega isliye dono ko short karke dono me ek voltage pass hota hai aur usme kitna current draw hua usi hisab se resistance calculation hota hai. Dono ka same voltage hoga to average sahi niklega.
To send same outgoing voltage in both terminal E1 and P1 have to short. Then Voltage will flow from E1 to E2 and from P1 to P2 for measuring resistance.
Distance hm reference set karne ke liye late hai.. jise hm sabhi earthing pit ki value same standard se le skate hai. Value vary nhi hoga. Dono probe me Distance voltage aur current probe ke karn rkhna hota hai
I will request to learn 1st before making this video. IEEE 81 will teach You can’t connect E2 and P2 anywhere. There is a rule of it. Request to all to go Is3043 or IEEE 81
I searched in internet about IEEE and found there is nothing about to test earthing resistance by Digital Earth Tester . If you found then send me the link or reference. By the way Everybody (including OEM Experts) are using this method to measure in industrial area.
Distance hm reference set karne ke liye late hai.. jise hm sabhi earthing pit ki value same standard se le skate hai. Value vary nhi hoga. Dono probe me Distance voltage aur current probe ke karn rkhna hota hai
Sir very good explanation. Ek doubt clear karein, ager ek building 🏢 me total 5 earthing he to uska resistance kese calculate karein? Please answer. I am waiting for your positive response.
@@BEE_CLASS Thank you very much sir. I appreciate your knowledge in the field of electrical engineering. Sir ek aur important doubt clear karein Jo aaj tak Mera e doubt clear Nahi ho paya, sir kese pata chalega ki ek bade 10 floor ke building me kitne earthing pit Lagenge? Aur wo sab earthing pit apas me interconnected honge ya fir separate earthings honge?
@@BEE_CLASS Thank you Sir. I am a engineering student. I study in electrical engineering. Sir humesa earthing ke upar mere Bahat doubt rehte the jo ki app ki explanation ke bad clear Hua he. Thanks again. Sir please T-T, TN-S, TNC-S earthing ke bare me ek practical vedio banaiye.
Individual value of Earthing pit approx 5 ohm and mesh or grid value approx depending on substation voltage level like less than 1 ohm in 132 kv grids. 33 kv grid value 1 ohm .
Individual value of Earthing pit approx 5 ohm and mesh or grid value approx depending on substation voltage level like less than 1 ohm in 132 kv grids. 33 kv grid value 1 ohm
Ek earth pit ko do alag alag jagah pe laga ke test karna hai, Jo bhi reading ayega agar 0.5 ohm ke niche hai to wo bilkul perfect hai. Agar use jyada hai tab apko earthing ke quality improve karna padega, nahi to Naya earthing karna padega.
Need more videos on live termination of feeder pillar,service turret, different testing of HV cable, DC Hipot test for HV cable in detail, videos on transformer testing etc
Is there is any precautions to check earthing in substation or Building???? Or we can check the earthing in Live substation or Building without disconnecting earthing..?????
Individual value of Earthing pit approx 5 ohm and mesh or grid value approx depending on substation voltage level like less than 1 ohm in 132 kv grids. 33 kv grid value 1 ohm
🎉being a railway employ...need it.,thanks for ur clarily...and explanation...😊
Thank you so much 🙏
Thank you bhai. I have clearly understand earthing test. Your explanation is very well. 🙏 Heartly thank you 🙏
Thankyou so much
Very well explained. THANKS.
Welcome bro
Thank you buddy for giving such a valuable information.👍
Thankyou so much sir for your support ❤️
Well explained
Thank you so much
Excellent curiosity thanks
Welcome Bro
Very nice
Thanks
Nice.....information sir
So nice of you
Very well explained.
I have one doubt , in small buildings where we don't get 20 mtr straight length to insert earth test rods what is the solution. Pls suggest.
Thank you
Hey, this is based on principle of potentiometer, pls read how it works.
Nicely deserved
Thank you so much
Awesome 👍
Thanks 🤗
Troubleshooting of VCB k uper ek vedio bnaaye
Aur VFD k wiring k uper video bnaaye
Thank you bro
Bhai tama ghara kouthi mu tamara new subscribers
Mera ghar UP me
Can we check earth resistance when surrounding ground is wet during rainy season?
Yes you can check any time, in rainy season if the earth pit is wet then it will show good value. In summer it will show little less if earthing made properly.
@@BEE_CLASS while i m checking it is showing overvalue '1' on meter. What can i do?
10 ohm valve grid value hai ya pit value hai
Pit value
Acha erthingkeley kithna homs chahih
Normal earthing - below 5 ohms
Grid earthing(looping earth) - below 1 ohms.
0.5 ohm below
During test if we touch the rod we get electric shock or not
No shock you will get. The test conducted by this device with very low voltage. But if you are checking a neutral earthing point of a live / Charged Transformer. You will be definitely electrocuted by heavy shock. Only in this case you have to Off Power Transformer when checking it's neutral ground earthing or ngr earthing. Very good question you asked and it is very important.
Thank you,🙏
very well understood
You're most welcome
Earthing registance value kam karne ke liye namak washing powder Pani ka ghol dal sakte hain?
Yes
Odisha se ho app kya
Carry on bro
UP
Sir muje ye instrument purchase karna hai
Koi bhi electrical instruments dukan se apko miljayega
Explain Grid valve and pit value kitna aana chahiye
Pit value and grid value always less than 1 ohm is the best. But you can use upto 3 ohm
Sir earthing resistance digital meter kitne Rs me milta hai
Rs 2000 se leke 50000 Tak ata hai
Acchi reading kitne se kitne Tak hoti hain sir
0.5 Ohm se kam ayaa to best earthing mana jata hai
@@BEE_CLASS Is 0.5 to less than 5 Ohm value best for house earthing connection?
Good
thank u so much
Price of this earth resistance measuring tool
5000 - 200000
👍👍👍👍tnx bro
Welcome
How much depth mesure?
1 feet to 1.5 feet dip
Sir rod ko jameen pe kyon ?? Gaadnaa hai . Why should we dig the rods on earth at different places ..??
Agar hame Earthing ka Value check karna hai to ham log two wires se alag alag earth me dal ke voltage denge to us dono ka average Resistance pata chalega, jisse earthing resistance kahte hain. Resistance jitna kam utna acha mana jayega. Isliye mitti me ghusaya jata hai earthing rod ko.
Arthik digital metre Milta Hai Kahan Se
Online mil jayega nahi to apke city area me koi hoga, net pe search karne se bhi dealer mil jayega
Very nice but mitter ka kay price hai
7000
E1and P1 ko short q katre hai wo bathao
Dono probe me ek hi voltage pass karega isliye dono ko short karke dono me ek voltage pass hota hai aur usme kitna current draw hua usi hisab se resistance calculation hota hai. Dono ka same voltage hoga to average sahi niklega.
Super
Thank you
Is machine se electrical resistivity v cheak hota h na
thank u so much for comment
Why E1 & P1 sort??
To send same outgoing voltage in both terminal E1 and P1 have to short. Then Voltage will flow from E1 to E2 and from P1 to P2 for measuring resistance.
Sir,Nameste how to check grid earth pit resistance.plz reply
@@BEE_CLASS Thank u sir for giving reply.
See this full video
Normal location ke liye under 8 ohm is sufficient, for substation and plants under 1 ohm is required.
Ye theory galat hai , Har jagah below 1 ohm is best. Hamare ghar pe bhi ham 1 ohm ke aas paas maintain karte hain
@BEE_CLASS railway station ke earth pits pr kahi 4ohm ya 3.5 ohm aisa likha dekha hai Maine.
@@gauravpatil2174 Less than 5 ohm value is best for house earthing connection
Sir with out meter earthing kaisa check kare
@@BEE_CLASS tq sir.but a tu house ke liye check karte hy magar industry my check karsakte hy kya
Ok
Ok
10 mtr aur 20 mtr ki duri me kyu rkkhe dono electrode.same distance me kyu nhi.
Please reply
Distance hm reference set karne ke liye late hai.. jise hm sabhi earthing pit ki value same standard se le skate hai. Value vary nhi hoga.
Dono probe me Distance voltage aur current probe ke karn rkhna hota hai
@@dhruv7409 , agar e2 and p2 dono ko 10 mtr ki hi duri pr rkhe to kya shi reading nhi milega.
ok
Sir give me purchase link this megger
You can simply search on google
Connections to be explained clearly...no short cut...
Ok 👌
Thank you bro.
thank u so much
please explain how flucke megger for earth resistance work step by step in a very clear english
Ok
Please conduct transformer megger test
Ok
Sir agar agar neutral or earth ke beech voltage jyada a raha hae to uska kya reason hae? Kya earth resistence jyada hone ke kaarn aisa hota hae?
@@BEE_CLASS sir earth or neutral ke beech 38 volts aa rha har. Ab earthing me kya problem ho skta hae?
earthing sahi hani hai nahito connect neutral with earthing
earthing ku lagaya jata h aur kaha use hota h
Sabhi electrical sector me use hota hai
accha hain
thank u so much
I will request to learn 1st before making this video. IEEE 81 will teach You can’t connect E2 and P2 anywhere. There is a rule of it. Request to all to go Is3043 or IEEE 81
I searched in internet about IEEE and found there is nothing about to test earthing resistance by Digital Earth Tester . If you found then send me the link or reference. By the way Everybody (including OEM Experts) are using this method to measure in industrial area.
Sir E1 or P1 ko short kyu krte h ???
@@BEE_CLASS thanks sir 🙏🙏👍👍
thank u so much for comment
Sir, why we using two spike for testing earth resistance? please answer me in English
for average result
Please price
Price depends upon kva size, manufacturer details available in this video name plate
0.00 aa raha h to kya sahi h sir
Itna kam to nahi ana chahiye . Dusra Meter se ek baar check karo
My side one comment how much distance measured
10-20 mtrs
Kitna voltage rehta h earth pit testor me
Bahut kam lets say maximum 5-9 volt dc
Metar ki kya price
15 rs
bhai mm30 relay ra use kana hue plz explain kara
Ok
Testing price kitna charge karte hai
one earthing 1000
Jaga ta kouthi hoo
cuttack
Distance hm reference set karne ke liye late hai.. jise hm sabhi earthing pit ki value same standard se le skate hai. Value vary nhi hoga.
Dono probe me Distance voltage aur current probe ke karn rkhna hota hai
ek probe 10 mtr dusra 20 mtr
Ghar ka voltage Kaise badhane Ka upaye bataee
@@BEE_CLASS earthing personal earthing se Thik nhi hoga lagane ke?
Stabilizer lagao
Sir ji
Playlist banvo.
Download kenemai aasani ho jayegi
Plz
thank u so much
Cost of testing machine .
starting from 7000
Sir kaam ksa hoga
Muja 1 0hm chaya .....ka kru plz help me...
Naa
Apply salt water weekly and normal water daily atleast one bucket
What is tolerance values (OHMS) of the earthing pit.
below 0.5 ohm
Press bell icon or subscribe wala video ke bich m aata h use aap starting m ya ending m keejiye ,it’s disturbing
Thank you so much
Sir very good explanation. Ek doubt clear karein, ager ek building 🏢 me total 5 earthing he to uska resistance kese calculate karein? Please answer. I am waiting for your positive response.
@@BEE_CLASS Thank you very much sir. I appreciate your knowledge in the field of electrical engineering. Sir ek aur important doubt clear karein Jo aaj tak Mera e doubt clear Nahi ho paya, sir kese pata chalega ki ek bade 10 floor ke building me kitne earthing pit Lagenge? Aur wo sab earthing pit apas me interconnected honge ya fir separate earthings honge?
@@BEE_CLASS Thank you Sir. I am a engineering student. I study in electrical engineering. Sir humesa earthing ke upar mere Bahat doubt rehte the jo ki app ki explanation ke bad clear Hua he. Thanks again. Sir please T-T, TN-S, TNC-S earthing ke bare me ek practical vedio banaiye.
@@BEE_CLASS sir 5 earthing ka average batayega ya total batayega
Thanks for your comments
Salt water use kya tha but kaam nahi hova
Hoga sare chiz dekhna padega
What is good resistance value of earth pit?? Kitna hona chahiye resistance
Individual value of Earthing pit approx 5 ohm and mesh or grid value approx depending on substation voltage level like less than 1 ohm in 132 kv grids. 33 kv grid value 1 ohm .
Individual value of Earthing pit approx 5 ohm and mesh or grid value approx depending on substation voltage level like less than 1 ohm in 132 kv grids. 33 kv grid value 1 ohm
below than 0.5 ohm is best
Sahi aur galat reading check Karke hamen hamen confirm Karke bataiye kaise hoga
Ek earth pit ko do alag alag jagah pe laga ke test karna hai, Jo bhi reading ayega agar 0.5 ohm ke niche hai to wo bilkul perfect hai. Agar use jyada hai tab apko earthing ke quality improve karna padega, nahi to Naya earthing karna padega.
Hi sir
Hi
Need more videos on live termination of feeder pillar,service turret, different testing of HV cable, DC Hipot test for HV cable in detail, videos on transformer testing etc
ok
what is the proper Reading , How much it should be there ?
below 0.5 ohm is the best
E1 E2 P1 P2 kya hota h
Ye sab us earth tester me cable lagane ka pionts hota hai
How much degree want to distance between 10 or 20 mtr rods
Kitna earth value rahega to sahi mana jaayeg
0.5 ohm se kam
Is there is any precautions to check earthing in substation or Building????
Or we can check the earthing in Live substation or Building without disconnecting earthing..?????
No
Odia
@@BEE_CLASS mu bi Jane odia electrician
No
ଭାଈ କଉ ଦିଷ୍ଟ୍ରିକ
Bhadrak
Odia re kahidia bhei
Ok
it is earth electrode resistance ,not earth -pit resistance
both are equal
Individual value of Earthing pit approx 5 ohm and mesh or grid value approx depending on substation voltage level like less than 1 ohm in 132 kv grids. 33 kv grid value 1 ohm
jitna kam utna acha erthing
Mujhe newtel aur earth se 1volt chahie to mein kitne earthing Karun sir
Yese nahi bata sakte
Bhai tame odia bodhe 😂
No Brother but odia janichi au Google translator achi na. I am from UP my brother staying on odisha so i know odia little bit.
Thats not 20m.
10-20
Sir mujay no send karoo
ko
Odia log thik se hindi nahi bol sakte kabhi bhi.Inka hindi bolne se pata chal jata he
@@BEE_CLASS 🤣🤣🤣
@@BEE_CLASS love from odisha
thank u so much for comment
Vat bpck
vat bpck
Well explained
Thank you so much
Kit price ₹ ?
Market me apko 5000 se leke 100000 tak miljayega , koi bhi hoga chalega bas warranty bala hona chahiye aur calibration ho sake aisa bala lena hai .