DC soft starting the SUN1000/2000GTIL inverter

แชร์
ฝัง
  • เผยแพร่เมื่อ 23 ก.ค. 2024
  • Hi, in this video, I want to tell you about the problem you might run into when using the SUN1000/2000GTIL inverter from a battery, while activating it with a timer for Peak Shaving or Arbitrage.
    Attention: In the video I am saying that the Standby-power AC draw of the Inverter is pretty high (70W), but luckily, that is not true, as the current flowing through the AC wire is mostly capacitive, and the Power Factor of that draw is only 0.03. So, this is resulting in a Real Power of only 2W in Standby, which makes it perfectly fine to leave the Inverter connected while not generating power.
    On our property, all energy systems (PV, Powerwalls, etc.) are DIY. Please check my Playlists for other content. Thanks
    Please consider donating to the channel if my videos helped you out in any way. We are in especially tough times and it takes a lot effort to create the content. Thank you for your kindness!
    PayPal address: office@thehillside.net
  • วิทยาศาสตร์และเทคโนโลยี

ความคิดเห็น • 31

  • @gerdholzhauer
    @gerdholzhauer ปีที่แล้ว

    Danke für das schöne Video, genau das hab ich gebraucht !

  • @kostaschatzi6391
    @kostaschatzi6391 5 หลายเดือนก่อน

    Hallo Roland , seit einem Jahr gehe ich deinem Rat nach aber halt Manuel mit zwei on-off Schalter . Alles OK ! Jetzt ging es diesen Vorgang mit zwei shellys zu verwirklichen damit ich das Ganze auch von der Ferne starten kann . Habe den Sun 1000 24V Bat. und benutze 4x 25W 6.8Ω Aluminium Widerstände in Reihe . ( Widererstaende die ich für Motorrad-Blinker gekauft habe aber nie zum Einsatz gekommen sind ) . "Normale " manuelle Umschaltzeit liegt bei ca. 3-4 Sek. . Jetzt wollte ich mal den Strom messen der durch diese Brücke fliest sobald der Sun anfängt Leistung zu produzieren und habe die Brücke drin gelassen aber nicht das Hauptschutz eingeschaltet und gewartet aber der Sun fing nicht an Leistung zu produzieren . Die Spannung ( im Sun zeigte mal 22.5V und mal 25V an ) bei kontinuierliche Bat.- Spannung von 26V . (Eingestellte Leistung des Sun 550W) . Erst nach dem einschalten des "Haupt-Schütz" und ausschalten der Widerstands-brücke fing der Sun wieder an zu produzieren .
    Die Frage ist , wenn die Umschaltung aus irgend einem Grund nicht stattfindet ob das den Sun beschädigen kann ?

    • @RolandW_DIYEnergyandMore
      @RolandW_DIYEnergyandMore  5 หลายเดือนก่อน +1

      Hallo Kostas. Der DC Eingang des SUN ist in Wahrheit ja kein Batterie-Eingang sondern ein MPPT-PV Eingang. Sprich, anstatt einer Batterie können dort auch Solar-Paneele hängen.
      Diese würden in der Nacht auch keine Spannung produzieren, am Morgen und Abend dann nur Spannung, jedoch keinen Strom, etc.
      Was Du siehst, wenn die Spannung schwankt, ist nur der MPP-Tracker, welcher den DC testet, ob dort auch Leistung rauszuholen ist.
      Es ist also ein ganz normaler Zustand für den SUN, wenn DC noch nicht vollständig aufliegt.
      In meinem Setup schalte ich die Starter-Brücke nach ein paar Sekunden wieder weg, damit es nicht dazu kommt, dass eben eine unbelastbare DC für lange Zeit anliegt falls der Schuetz aus irgendeinem Grund nicht funktioniert.

    • @kostaschatzi6391
      @kostaschatzi6391 5 หลายเดือนก่อน

      @@RolandW_DIYEnergyandMore Vielen Dank für die Antwort.

  • @fkdeazevedo
    @fkdeazevedo ปีที่แล้ว +1

    What contactor and timer relay controller do you recommend?

  • @dralusion
    @dralusion ปีที่แล้ว +1

    thanks for this. would it be possible to list which products you used. amazon affiliate links would work. thanks

  • @esuohdica
    @esuohdica ปีที่แล้ว

    This is very good idea! Would the same idea work, but using a permanently connected resistor of higher value (say 1k ohm) to keep the inverter capacitors charged, but only allow low current to be drawn? (50mA at 50V)? The contactor would then just "bridge" the resistor when batterys are fully connected? I have a second question regarding your setup - Do you recommend charging while the batteries are also connected to inverter? Thanks

    • @RolandW_DIYEnergyandMore
      @RolandW_DIYEnergyandMore  ปีที่แล้ว

      Well, the inverter will always try to use as much power as it can as long as it sees voltage on the DC In. It will act like a solar MPPT controller and try to chase the 50mA. That might not work very well.
      You can charge the battery while inverting. that shouldn't be a problem.

  • @offgridwanabe
    @offgridwanabe 3 ปีที่แล้ว

    I never shut mine down but I understand what you have designed. I wonder how does the inverter shut down when it reaches a predetermined voltage to save the battery? I thought I could see some ramping down but not sure. The only thing that sometimes happens is the video freezes, buttons still work but it doesn't show on screen.

    • @RolandW_DIYEnergyandMore
      @RolandW_DIYEnergyandMore  3 ปีที่แล้ว

      People who are using this inverter as a solar grid tie inverter are fine, it is only an issue when used as a purpose controlled pure battery inverter.

    • @offgridwanabe
      @offgridwanabe 3 ปีที่แล้ว

      @@RolandW_DIYEnergyandMore yes I use the battery only but have a low voltage cutoff so inverter shuts down on it's own just wondering how it does that.

    • @RolandW_DIYEnergyandMore
      @RolandW_DIYEnergyandMore  3 ปีที่แล้ว

      @@offgridwanabe It will use internal relays or transistors. But definitly isolating the DC site. Probably similar concept as we do on the outside

  • @uweheckmann5111
    @uweheckmann5111 3 ปีที่แล้ว

    Hallo Roland,
    Ein Bekannter von mir wollte mal seinen SMA Sunny Island direkt "starten"
    dann ist ihm der Schütz verklebt. Habe im dann auch so eine Vorladeschaltung gebaut ähnlich deiner...
    Wie immer tolles Video.
    Gruß Uwe

    • @RolandW_DIYEnergyandMore
      @RolandW_DIYEnergyandMore  3 ปีที่แล้ว

      Ja, je nach Groesse der Kondensatoren, kann schon etwas Strom zusammen kommen :)

  • @benkanobe7500
    @benkanobe7500 ปีที่แล้ว

    It would be great if you supplied links to the components of your DC disconnect/reconnect circuit as some of us are not technical. I have been using AC switching for my batteries on/off at night. No failure yet, but DC does seem to make the most sense.

    • @RolandW_DIYEnergyandMore
      @RolandW_DIYEnergyandMore  ปีที่แล้ว

      As I do not live in a western country where Amazon and Ebay are the first option to get stuff, it is very hard for me to provide useful links.
      I can link the contactor from AliExpress for example which I am using: www.aliexpress.com/item/1005004614039976.html?spm=a2g0o.detail.1000014.14.3c3b17f91sPmng&gps-id=pcDetailBottomMoreOtherSeller&scm=1007.40050.281175.0&scm_id=1007.40050.281175.0&scm-url=1007.40050.281175.0&pvid=7e7ff2da-bd11-4a64-9d1f-acbd239de52c&_t=gps-id:pcDetailBottomMoreOtherSeller,scm-url:1007.40050.281175.0,pvid:7e7ff2da-bd11-4a64-9d1f-acbd239de52c,tpp_buckets:668%232846%238116%232002&pdp_npi=3%40dis%21THB%21820.93%21689.58%21%21%21%21%21%402103011716830651916416982ecb33%2112000029836355617%21rec%21TH%21185638773
      But I am sure you are much mor interested in a circuitry which is timing the pre-charge resistor. I know there are delay timers on the market which might be used for something like this, for example: www.aliexpress.com/item/1005004063991674.html?spm=a2g0o.order_list.order_list_main.53.54811802NXRqsl
      It is everyone's part to find his solution by doing some homework ;)

  • @benkanobe7500
    @benkanobe7500 ปีที่แล้ว

    But, because it is designed with anti-islanding to no provide power to the grid in the event of a grid down/failure, it would seem that it is designed specifically to handle the loss of AC while being supplied DC power and then switching back on when AC power is restored. Is this not true?

    • @RolandW_DIYEnergyandMore
      @RolandW_DIYEnergyandMore  ปีที่แล้ว +1

      In a way it would seem that AC faults shouldn't matter, but still how frequently does the grid go down? In my case I have grid interruptions probably every 3 days. They are just short but are bringing many devices down.
      My SUN1000 had a blown component in its AC power supply circuit after less than a year which I can only explain to happen because of those grid interruptions.
      I see more AC side problem repair videos for such SUN inverters recently. It's not invulnerable.

    • @benkanobe7500
      @benkanobe7500 ปีที่แล้ว

      @@RolandW_DIYEnergyandMore Thank you. I am not really technical and so am going to need to do lots of research to figure out where and what components to purchase and build a DC disconnect as you have shown. Mine have not failed using AC timers to turn on the ones I have for battery power at night (two for day powered by solar and two for night powered by battery banks. Mine are 1000Watt 120VAC with one on each Leg of 120VAC to give a total of 240VAC)

  • @kostaschatzi6391
    @kostaschatzi6391 ปีที่แล้ว

    Hallo Roland , gutes Video ! Wie waehren die Werte der Bauteile bei einer 24V Anlage und mit einem Sun 1000 und hast Du vieleicht Links dazu ? Einen schoenen Tag noch .

    • @RolandW_DIYEnergyandMore
      @RolandW_DIYEnergyandMore  ปีที่แล้ว +1

      Ein Widerstand so um die 20-30 Ohm bei 30W wären optimal. Es soll sich ein Vorladestrom von ca 1A ergeben um diese kleinen Relays nicht zu beschädigen. Der hohe Leistungswert der Widerstände ist wichtig, damit diese nicht abbrennen sollte ein Relay einmal händenbleiben. Für den Sun 1000 reichen ca 3 Sekunden Vorladezeit bei 1A. Auch Dir einen schönen Tag noch!

    • @kostaschatzi6391
      @kostaschatzi6391 ปีที่แล้ว

      @@RolandW_DIYEnergyandMore Vielen lieben Dank fuer dein schnelles Antworten .

    • @kostaschatzi6391
      @kostaschatzi6391 ปีที่แล้ว

      @@RolandW_DIYEnergyandMore Eine Frage zu den Widerstaenden . Wo liegt der Unterschied zwischen deinem gruenen Widerstand , einem Zement Widerstand und einem mit Aluminium Koerper wenn doch alle drei die gleiche Watt und Ohm haben ?

    • @RolandW_DIYEnergyandMore
      @RolandW_DIYEnergyandMore  ปีที่แล้ว +1

      @@kostaschatzi6391 Da wird es nicht viel Unterschied geben. Aus Erfahrung weiß ich nur, dass die weißen Keramik Widerstände sehr heiß werden. Die grünen sind gross und haben viel Oberfläche um die Wärme wieder abzugeben. Im Normalfall ist das aber ohnehin alles Nebensache, weil der Vorlauf ja nur sehr kurz eingeschaltet ist. Du kannst verwenden was immer Du am besten bei Dir bekommst...

    • @kostaschatzi6391
      @kostaschatzi6391 ปีที่แล้ว

      @@RolandW_DIYEnergyandMore Ok , verstanden ! Ich haette auch lieber einen Grossen 30 Ohm / 30 Watt aber den finde ich nur aus China und nach dem Zoll ist der dann zu teuer . Hier werde ich wohl auf einen weißen Keramik Widerstand den es aber nur mit 25 Ohm / 25 Watt gibt ausweichen muessen . Bei 3 Sek. duerfte das kein Problem sein , oder ?

  • @afsallais9825
    @afsallais9825 3 ปีที่แล้ว

    dont buy this thing its very bad. you cant change the settings on it. the production is lower than other converters too. i bought solis inverter after this and it has much better output in lower sun light and has better build quality. dont compromise your budget on converters. the mppt tracking on this is just shit.

    • @RolandW_DIYEnergyandMore
      @RolandW_DIYEnergyandMore  3 ปีที่แล้ว +2

      I am only using it as battery inverter. Don't have a solar system connected. I am sure that every passive cooled Grid-tie String inverter has a better performance and MPPT circuit then this. But for battery this is OK, and there is not much other choice. Thanks

    • @benkanobe7500
      @benkanobe7500 ปีที่แล้ว

      Can you provide links to what you recommend? I have four of these (1KWatt each). Two are just solar with one on each leg of 240VAC Split phase (North America) and two that run the house each night from battery with AC timmers. This plug and play system has been on line for nearly 3 years and we have almost no power bill and no contract with our Utility here in San Diego. We couldn't be happier. So please tell show me how to have a better system as you have recommended. Thank you.