thanks for the reply.i have another one question if theres no power to control board does it mean the 24 volts (transformer ) is bad or the control board itself id bad .
are all the hoshizaki ice machine models have the same sequence of operations? can I pls get some troubleshooting guide of different problem on these hoshizaki commercial ice machines? if where can I get this guides ?
I have a hoshizaki ice machine after the water drips the evaporator and the water pump starts pumping water to eavaporator I noticed the compressor tries to come on but instead of starting it just give a "click" then gone .was it beacause of a very dirty condenser that makes the compressor be on the overload state??
which comes on first? the conderser fan or the compressor? in my case I heard the compressor treis to come on first but the fan is not doing anything pls help
My compressor floods back, freeze time of 45 min to make ice, running pressures at 45/220, I'm not sure of what my superheat is. Could I have a bad TXV ? Model KM-1601SWH.
thanks for the reply.i have another one question if theres no power to control board does it mean the 24 volts (transformer ) is bad or the control board itself id bad .
are all the hoshizaki ice machine models have the same sequence of operations? can I pls get some troubleshooting guide of different problem on these hoshizaki commercial ice machines? if where can I get this guides ?
I have a hoshizaki ice machine after the water drips the evaporator and the water pump starts pumping water to eavaporator I noticed the compressor tries to come on but instead of starting it just give a "click" then gone .was it beacause of a very dirty condenser that makes the compressor be on the overload state??
Very informative!
A brown Alpine circuit board?
Are there any left?
which comes on first? the conderser fan or the compressor? in my case I heard the compressor treis to come on first but the fan is not doing anything pls help
Could be. Dirty condenser wreaks all kinds of havoc because it makes head pressure skyrocket.
thanks
My compressor floods back, freeze time of 45 min to make ice, running pressures at 45/220, I'm not sure of what my superheat is. Could I have a bad TXV ?
Model KM-1601SWH.
as long the freeze time not over 60 min. its should be ok. it depend on the ambient too.
machine makes ice but dont drop it what could cause this
Harvest valve stuck shut/ no voltage or low gas.
I have one machine goes to harvest every 5 minutes ..what could be??
5 minute freeze cycles are caused by a loss of water usually through the check valve
Will cleaning the machine help