Hoshizaki KM Series Ice Machine Diagnostics

แชร์
ฝัง
  • เผยแพร่เมื่อ 15 ต.ค. 2013
  • Diagnosing of the Hoshizaki KM Series Ice Machines. Video made by Hoshizaki America.
    Hoshizaki Ice Makers
    www.gofoodservice.com/brand/h...

ความคิดเห็น • 23

  • @tekman2000
    @tekman2000 ปีที่แล้ว +4

    Thank you for taking the time to make this FANTASTIC diagnostic video 😀👍

  • @wesleyreach1144
    @wesleyreach1144 3 หลายเดือนก่อน

    Thank you very much. Great video takes me straight back to high school ag class

  • @DaCrunkwizard
    @DaCrunkwizard 4 ปีที่แล้ว +5

    Love that 90s style intro

  • @tomascoronado9502
    @tomascoronado9502 7 ปีที่แล้ว +4

    great video!

  • @AndresCura-ys5vb
    @AndresCura-ys5vb ปีที่แล้ว

    Exelente ayuda para nuestras dudas y problemas técnicos grasias

  • @briangiven7399
    @briangiven7399 2 ปีที่แล้ว +1

    I have a KM-1900saj that dumps a lot of water into the drain. Is this normal for this style ice maker? I know it can rinse water though the system but heard that some units are water cooler compressors and may dump water for this reason.

  • @kleberluismoura7313
    @kleberluismoura7313 5 ปีที่แล้ว +4

    Poderia ter um video traduzido para portugues, tem muitas maquinas hoshizaki no Brasil...

  • @wellingtoncamargo8133
    @wellingtoncamargo8133 3 ปีที่แล้ว +1

    Great explication !!!!1

  • @marcdorizar5742
    @marcdorizar5742 ปีที่แล้ว +2

    where should i purchase the tech spec's book please?

  • @rosskious7084
    @rosskious7084 3 ปีที่แล้ว +2

    Most thermistors fail open or shorted. I have seen a few with the values off. However this is not common.

  • @user-gm4xx1zm3g
    @user-gm4xx1zm3g 7 หลายเดือนก่อน

    i have a KM-520maj and dumps a lot of water into the drain. what is the cause

  • @whitebear1903
    @whitebear1903 3 หลายเดือนก่อน

    Awesome

  • @raviyadav8743
    @raviyadav8743 3 หลายเดือนก่อน

    What is possible reason of 3 beeps

  • @GaunttFarms
    @GaunttFarms 4 ปีที่แล้ว

    HOW DO YOU CHECK THE CIRCULATION PUMP ?

    • @GoFoodservice
      @GoFoodservice  3 ปีที่แล้ว +1

      Information taken from Hoshizaki's Troubleshooting Guide:
      The water pump itself can be easily tested by putting the unit in wash mode via the 3 position toggle switch found at the top of the ice maker. You must however also confirm the operation of the water pump in conjunction with the control board. When the unit begins the freeze cycle, the water pump and condenser fan motor should energize on self-contained units (with remote units, the condenser fan starts with the compressor). If the water pump fails to run, check voltage from the control board K1 connector (red wire) and you should see it running at 110 volts. If not, it is a good idea to verify that the board is actually in the “freeze” cycle. If you find there is power running to the red connector of the pump and it's still not functioning properly, next check the toggle switch.
      For more information, please contact Hoshizaki Tech Support at 800-438-6087

  • @dodok961
    @dodok961 ปีที่แล้ว

    Every night when I close the door . The machine start 1 times beep, i think hot water went in

  • @bubbasmith3219
    @bubbasmith3219 6 ปีที่แล้ว +2

    Is the fan supposed to run the whole time

    • @Pious-Inquisitor
      @Pious-Inquisitor 5 ปีที่แล้ว +4

      Fan should only run when compressor is running

    • @alexandercanto7587
      @alexandercanto7587 2 ปีที่แล้ว

      The compressor should be always running, the fan should stop on the Harvest cycle

  • @eriksyhre8030
    @eriksyhre8030 3 ปีที่แล้ว +1

    What is the difference of e board and g board? Please help

    • @GoFoodservice
      @GoFoodservice  3 ปีที่แล้ว +2

      The E Board (Green) was the main control board used for Hoshizaki ice machines starting in the late 1990s. It was full of features the previous board did not have. Including lights and audible safeties and alarms.
      The G Board (Tan/Brown) was created several years ago as a water saver control board to go with California water conservation laws. This changed water valves and bin controls to keep the unit from wasting as much water on pump-out cycles. It too has many of the same features of the E board just slightly improved.
      For more information, please contact Hoshizaki Tech Support at 800-438-6087