Zurn Wilkins 720A Pressure Vacuum Breaker Repair, Winterization
I talk about the Zurn Wilkins 720A PVB how to take it apart, repair it, the repair kits available, how to put it together, how to winterize it and advice in general about it and a little about trouble shooting it.
Repair Kit links to buy from our webstore:
1/2" - 1" Kits
Complete Kit RK1-720a backflow-supply.com/products/1-2-1-720a-repair-kit?_pos=1&_sid=c5106e35a&_ss=r
Bonnet kit backflow-supply.com/products/720a-1-2-1-bonnet-repair-kit?_pos=1&_sid=2dd9f3cdd&_ss=r
Poppet kit backflow-supply.com/products/1-2-1-720a-poppet-o-ring-kit?_pos=2&_sid=2dd9f3cdd&_ss=r
1 1/4" - 2" Kits
Complete kit
RK2-720A backflow-supply.com/products/wilkins-720a-1-1-4-2-kit?_pos=1&_sid=54b35a7e6&_ss=r
Ball Valve Handle Tools:
Small one WV100 backflow-supply.com/products/small-bv-handle-wrench?_pos=1&_sid=70b97fbc5&_ss=r
Larger one WV101 backflow-supply.com/products/ball-valve-wrench-large?_pos=2&_sid=70b97fbc5&_ss=r
Wider one for wider handles backflow-supply.com/products/large-small-valve-handle-wrench?_pos=5&_sid=70b97fbc5&_ss=r
มุมมอง: 8 460

วีดีโอ

Preventing Over Inflation of Temporary Sewer Plug
มุมมอง 1182 ปีที่แล้ว
Answer to customer questions about the sewer plug.
Backflow Supply Temporary Backflow Stop Installation Video
มุมมอง 1282 ปีที่แล้ว
Video demonstration of installing the temporary sewer backflow.
Can I use the temporary backflow device?
มุมมอง 1092 ปีที่แล้ว
Can this be used in an indoor sewer clean out pipe?
How long is the hose on the temporary backflow prevention device
มุมมอง 452 ปีที่แล้ว
Will the length of the hose work for your sewer clean out?
How many days can I keep the temporary backflow device in place
มุมมอง 932 ปีที่แล้ว
How long is it suggested to keep the device in place?
What if I have two sewer cleanout pipes
มุมมอง 1.8K2 ปีที่แล้ว
Where do I place the temporary sewer backflow device
Mid West Test Kits
มุมมอง 1.6K2 ปีที่แล้ว
I go over the Mid-West Backflow Test Kit line and show what comes with the gauges, explain how the hoses should be connected and cleaning the hose filters, why the bleed valves feel "loose," and explain the serial number and how you can tell how old your gauge is. Also talk about calibration, and link is below for authorized calibration service centers for Mid-West Instruments, of which we are ...
Insulating Your Backflow Assembly
มุมมอง 9052 ปีที่แล้ว
Talk about if you need to insulate your backflow assembly and provide options as well as talk about how not to insulate the backflow assembly. Here are some links for products talked about in the video. I am going to link some to my web page and some to the manufacturer because I don't have all of what they offer on my store, but can get it and sell it. AquaShield on my website: backflow-supply...
Wilkins 375 and 375XL Vessel Removal and Blow Out Fitting Installation and Usage
มุมมอง 3.4K2 ปีที่แล้ว
375 1" and smaller vessel removal and the installation of the blow out fitting and reinstalling of the vessel. 1/2" and 3/4" Blow Out Fitting backflow-supply.com/products/3-4-375-blow-out-fitting?_pos=1&_sid=319b92121&_ss=r 1" Blow Out Fitting backflow-supply.com/products/1-375-blow-out-fitting?_pos=1&_sid=bf6bdd5eb&_ss=r There are also blow out fittings for the 350 and 350XL models. 3/4" 350 a...
How to Identify your Backflow Model and Size
มุมมอง 6K2 ปีที่แล้ว
In this video I talk about where to find the model and size of your backflow assembly so you can order the right repair kit/parts. Look for a tag first that should have that information. If the tag is missing or unreadable look for the model and brand raised in the brass on the side of the assembly. Size is always raised in the brass on both ball valves/shut off valves. As a last resort I talk ...
RP4A/RPLF4A Breakdown and Explanation
มุมมอง 7K3 ปีที่แล้ว
I take the RP4A (same as the RPLF4A) apart and explain the different components and some things to look for if you suspect that it may have frozen. This would be the procedure for 2" and smaller sizes. Below are links to the major repair kits available on my webstore. Other kits can be found on our webstore. Complete assemblies can also be found on the webstore. For clarification repair kits ar...
Ames Colt and Maxim and Watts 757 and 957 Sleeve O ring Replacement
มุมมอง 3893 ปีที่แล้ว
This video is of the assembly of the o-rings being put on the sleeve of the Ames Colt/Maxim and Watts 757/957 models. I downloaded the video from Ghazwan Alqaraghuli Channel th-cam.com/video/4gkOnUeSPsI/w-d-xo.html Repair and Maintenance Sheet can be found here www.watts.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb521/34875-source/7018381/7018381 The body o-rings are found in the check rubber kit...
Temporary Emergency Backflow Device for Sewers
มุมมอง 3.2K3 ปีที่แล้ว
This is a new product just developed. It is designed for preventing sewage pushing into a home or building during an issue with the sewer system caused by flooding from natural disasters. It is designed to be put into place as you need it and removed when the event has ended. This will protect your home or building from a messy clean up and bill. To purchase this go to my online store. backflow...
Inspecting and Taking Apart the Watts 800M4 PVB Assembly
มุมมอง 28K4 ปีที่แล้ว
I briefly explain the components of the Watts 800M4 PVB assembly. I show how to take it apart and put it back together. I have linked to an old Watts video that shows water pouring out of it and it is a only a couple minutes long. Watts Video th-cam.com/video/BrvEbEEDewE/w-d-xo.html Link to Watts Installation and Repair and Maintenance Sheet: www.watts.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb...
How to Order Wilkins Repair Kits
มุมมอง 5084 ปีที่แล้ว
How to Order Wilkins Repair Kits
Ordering Repair Kits, Part 1, Ames, Febco and Watts
มุมมอง 4594 ปีที่แล้ว
Ordering Repair Kits, Part 1, Ames, Febco and Watts
RP4A and RP40 Winterization
มุมมอง 4K4 ปีที่แล้ว
RP4A and RP40 Winterization
Opening a Test Cock
มุมมอง 2.1K4 ปีที่แล้ว
Opening a Test Cock
How To Repair a Watts 909 Backflow Assembly
มุมมอง 23K4 ปีที่แล้ว
How To Repair a Watts 909 Backflow Assembly
Febco 825Y Backflow Repair Failure
มุมมอง 5K5 ปีที่แล้ว
Febco 825Y Backflow Repair Failure
Ames Check Removal Tool
มุมมอง 2.9K5 ปีที่แล้ว
Ames Check Removal Tool
How to Repair an Apollo RP40 Backflow Assembly
มุมมอง 7K5 ปีที่แล้ว
How to Repair an Apollo RP40 Backflow Assembly
How to Winterize Your Backflow Assembly
มุมมอง 3.2K5 ปีที่แล้ว
How to Winterize Your Backflow Assembly
This Thingy on My Backflow Assembly is Called a Test Cock
มุมมอง 14K5 ปีที่แล้ว
This Thingy on My Backflow Assembly is Called a Test Cock
Backflow Seat Removal Tools and More
มุมมอง 6K5 ปีที่แล้ว
Backflow Seat Removal Tools and More
How to Trouble Shoot a Leaking Backflow Assembly
มุมมอง 113K5 ปีที่แล้ว
How to Trouble Shoot a Leaking Backflow Assembly
How to identify Freeze Damage in Backflow Assemblies
มุมมอง 8K6 ปีที่แล้ว
How to identify Freeze Damage in Backflow Assemblies
Take Care Not to Freeze Your Test Kit
มุมมอง 1326 ปีที่แล้ว
Take Care Not to Freeze Your Test Kit
How to remove Febco 850/860/870/880 Seats
มุมมอง 3.8K6 ปีที่แล้ว
How to remove Febco 850/860/870/880 Seats

ความคิดเห็น

  • @CaraLake-d4v
    @CaraLake-d4v 2 ชั่วโมงที่ผ่านมา

    Thank you! This was super helpful

  • @clinteastwood6986
    @clinteastwood6986 2 วันที่ผ่านมา

    Awesome tutorial. Thank you.

  • @dskrpncs
    @dskrpncs 3 วันที่ผ่านมา

    Homeowner here. Curious what you think might be wrong here. When I turn on the water too the system the Wilkins 720 PVB seals and the mainline fills. When I activate zone 1 the PVB leaks and nothing comes out of any of the heads. What might you recommend? Thank you!

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 วันที่ผ่านมา

      I am guessing when you activate zone 1 and the PVB leaks, it means it is dumping all the water that would be going to the zone. Is that correct? Does this do it on any other zone? It sounds like you are losing too much pressure after the PVB. Either there are too many heads on the zone or there is a break between the valve and the heads. For some reason too much water going out and not enough pressure to sustain the float of the PVB to keep it sealed. Call me if you need to and we can talk. Sean, 801-355-6736

  • @stevecarvalho6937
    @stevecarvalho6937 19 วันที่ผ่านมา

    What an educational video. Thorough and succinct explanation. Thank you

  • @squebler
    @squebler หลายเดือนก่อน

    Thank you. Now I know how to open and close my test cock valves.

  • @rhinotown76
    @rhinotown76 หลายเดือนก่อน

    You should do all youtube videos. Great explanation.

  • @joelsander8289
    @joelsander8289 หลายเดือนก่อน

    Excellent information! This is the fourth video on this regulator that I watched and is the only one to explain what I was doing wrong. Problem solved.

  • @robertkoellisch470
    @robertkoellisch470 หลายเดือนก่อน

    Just noticed a small drip coming out of the horizontal test cock. Is there a remedy for this or is this normal? Thank you!

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 หลายเดือนก่อน

      No. It is not normal. Make sure the screw slot is turned straight across the valve. Every quarter turn is open /close. If it is then it might be time to change the test cock or you can go buy a 1/4" brass plug, teflon it and put in if it is a female ended test cock. If it has a male end then buy a cap. Or you can replace the test cock. I am guessing your assembly is a 1" or smaller line size so that means you need a 1/8" male fitting (that goes into the body of the assembly) by a 1/4" female, or by a new one. Here is the link to the test cocks on our site. backflow-supply.com/search?q=test+cocks&options%5Bprefix%5D=last

    • @robertkoellisch470
      @robertkoellisch470 หลายเดือนก่อน

      @@backflowsupplyslcut9394 I thought I had it stopped but now it's not just dripping but more like spraying out where the plastic plug fits. I tried to teflon tape the plug until I can order something but that didn't work either. How do I know which size plug to order and does it need to be lead free? Thank you!

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 หลายเดือนก่อน

      @@robertkoellisch470 Is the screw slot going in the direction of the flow or across the test cock. It should be going across the test cock. If you need a plug in it for now and it is a female test cock you need a 1/4" male plug. If it is a male flare fitting you need a 1/4" flare fitting (cap)with an o-ring on it to stop it.

  • @CassandraZachary
    @CassandraZachary หลายเดือนก่อน

    I have the one on the left but when I remove the bonnet it’s a black piece with only 1 long piece it’s so hard to even remove I can’t get it to budge. Any advice ?

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 หลายเดือนก่อน

      I wonder if you have a different model. Both of these are the Wilkins 720A. I wonder if you have the Wattts 800M4 PVB? th-cam.com/video/sqYsxJJk8m4/w-d-xo.html Watch this and see if it helps. You are welcome to send me pictures to sean@backflow-supply.com or call at 801-355-6736

  • @petersonfamily6223
    @petersonfamily6223 หลายเดือนก่อน

    Thanks, I had reduced pressure on all zones and my 800M4 was squealing when running. I took everything apart and cleaned it and ensured there were no cracks and or any damage. The difference is my float has a center tube with an internal spring the fits up into the bonnet center spring area. The pressure has returned minus the squeal but I now have a small leak and was going to replace everything inside our 20-year-old Watt 800M4 R regulator but I am not able to find a kit with the same float. Help and thanks again.

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 หลายเดือนก่อน

      I am not sure which size you have. 1" is most common, but here is a link to the parts for the 3/4" backflow-supply.com/collections/all?filter.p.m.custom.watts_models=800M4&filter.p.m.custom.sizes=3%2F4%22 and the 1" backflow-supply.com/collections/all?filter.p.m.custom.watts_models=800M4&filter.p.m.custom.sizes=3%2F4%22 just depends on if you want just that part or a complete kit. Call me if you have questions Sean 801-355-6736

  • @lindastretch2522
    @lindastretch2522 หลายเดือนก่อน

    i good looking

  • @shanew7361
    @shanew7361 หลายเดือนก่อน

    What if it's not leaking water but the pressure test failed to submit to tne County?

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 หลายเดือนก่อน

      I am not sure I am following your question. You had the assembly tested and it failed? That is a possibility. The air inlet could have opened below the required 1.0 or the check valve in the bottom could have leaked or not held at 1.0 or above. This would require perhaps a simple cleaning or rubber parts or complete parts. Hard to determine without seeing the components and knowing what the issue was in the first place. You are welcome to call me at 801-355-6736 and ask for Sean or email me at sean@backflow-supply.com

    • @shanew7361
      @shanew7361 หลายเดือนก่อน

      @@backflowsupplyslcut9394 Yes I had the pressure tested and it failed. Otherwise, its functioning fine zero issues.

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 หลายเดือนก่อน

      @@shanew7361 Maybe I need to clarify. Did someone come out to do a specific backflow test, using a gauge and they hooked a hose up to it? Did they leave a copy of the report?

    • @shanew7361
      @shanew7361 หลายเดือนก่อน

      @backflowsupplyslcut9394 Correct, and no report was given. I'm having a different plumbing company retest it.

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 หลายเดือนก่อน

      @@shanew7361 Make sure you ask them to explain why and how it failed so you know what you need to fix it.

  • @lindastretch2522
    @lindastretch2522 หลายเดือนก่อน

    i good looking

  • @lindastretch2522
    @lindastretch2522 หลายเดือนก่อน

    and a good looking one +

  • @lindastretch2522
    @lindastretch2522 หลายเดือนก่อน

    a nice looking too

  • @lindastretch2522
    @lindastretch2522 หลายเดือนก่อน

    i got it

  • @kev7017
    @kev7017 หลายเดือนก่อน

    I’ve learned a lot from this video. And now I know that the guy who installed mine didn’t know what he was doing. So now I will have to have it re-installed. I wish there was a way I could show you a picture of mine.

  • @tonyleopard6610
    @tonyleopard6610 2 หลายเดือนก่อน

    Any thoughts?

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 2 หลายเดือนก่อน

      it is not uncommon for a new install to leak. There could have been debris, such as rocks, sand or rust in your pipes that when turned on got stuck in the #1 check. I am assuming this is on a lawn sprinkler system. If so turn a zone on that will get more flow going through the heads than what is coming out of the relief valve. If it stops leaking out of the relief valve when the zones are running the problem is in the #1 check assembly. If it doesn't it is in the relief valve. Almost always it is in the #1 check assembly. If you determine it is in the #1 check take it apart and look for rocks, rust, even teflon tape or pipe dope. Clean it out, flush the line for a minute or so with the part out and the cover off then reassemble and try again. If you still need assistance you are welcome to call me at 801-355-6736.

  • @tonyleopard6610
    @tonyleopard6610 2 หลายเดือนก่อน

    I have a brand new backflow just out of the box that’s leaking just like that

  • @mikeheilman3368
    @mikeheilman3368 2 หลายเดือนก่อน

    I installed a new RP4A, bled the input and I'm sure its installed in the right direction but as soon as I turn the water on it starts gushing out the bottom. The unit is brand new so what might be the problem.

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 2 หลายเดือนก่อน

      Maybe you have resolved this already. But the first thing to do is to get a flow going through the backflow assembly greater than what is coming out the relief valve. I am assuming this is going to a lawn sprinkler system. Even though it is dumping water turn a zone on that will get the required flow of water and observe if it stops dumping. If it does you know there is an issue in the first check valve. If it doesn't it is an issue with the relief valve. It is not uncommon on a new install for debris in the line, rocks, rust or other debris gets flushed into the first check. Take it apart and see if that is your issue, inspect the rubber and the seat to make sure they didn't get damaged and put it back together and turn it on again. Hopefully it doesn't dump again. But sometimes it will and it could still be more debris in the line. I have seen a few issues with the relief valve in the last year in brand new units. So far I have not been able to determine the cause but have provided those that brought the unit from me with a new relief valve and it has solved the issue. This is rare. You are welcome to call me at 801-355-6736 if needed. Ask for Sean.

  • @riverraisin1
    @riverraisin1 2 หลายเดือนก่อน

    I wish you hosted all how to videos on TH-cam. Outstanding job!

  • @zeero62
    @zeero62 2 หลายเดือนก่อน

    Is it an optical illusion or does the apparatus on the right look bigger than the one on the left? I don't see any size specification on the 720-A that I'm looking at here at home.

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 2 หลายเดือนก่อน

      If you are referring to the two assemblies in front of me in the video, the old one is a 1" and the new one (the left) is 3/4". But the bodies are the same for 1/2", 3/4" and 1". You will be able to find the size raised in the brass on each of the ball valves. It will be marked as a 3/4" or 1" most likely.

    • @zeero62
      @zeero62 2 หลายเดือนก่อน

      @@backflowsupplyslcut9394 Thank you, I will take a 2nd look.

  • @bulletchicken
    @bulletchicken 2 หลายเดือนก่อน

    Great video. Very informative. Thank you!

  • @diverutah
    @diverutah 2 หลายเดือนก่อน

    Excellent video, very informative! Thank you

  • @riverraisin1
    @riverraisin1 2 หลายเดือนก่อน

    Correction. Yes you are a videographer. You just don't realize it. This instruction video is as good as it gets on TH-cam.

  • @LindaHeck-rs3jq
    @LindaHeck-rs3jq 2 หลายเดือนก่อน

    I have a Wilkins Zurn Model # 975XL It is leaking out of the diaphragm in the center hole. What is causing this?

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 2 หลายเดือนก่อน

      The leak out of the hole on the RV cover is one of three reasons or a combination. When you take that cover off the nipple end of the RV assembly may still be stuck in it. The part that fits into the cover has a plastic piece with an o-ring on it. Either the plastic could be cracked or broken or the o-ring is damaged. Lastly, it could be the cover plate inside where the o-ring seals is corroded or pitted. If the corrosion can be cleaned out and it has not pitted the brass you may be good or you may need a new o-ring. But regardless it is one of those reasons or a combination of them. Call me if you need to 801-355-6736

  • @wittmf
    @wittmf 2 หลายเดือนก่อน

    GREAT instructional video!!! My exact unit and NOW I understand it well, Thank You!

  • @GaryUllmer-dk2tk
    @GaryUllmer-dk2tk 2 หลายเดือนก่อน

    How do you drain the supply line? do you need too?

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 2 หลายเดือนก่อน

      IF you are referring to winterizing, I guess it would depend on your system. For example, I have a stop and waste and it should all run out of that. If your valve is in your home there should be a way to drain it as well.

  • @neilwoller
    @neilwoller 3 หลายเดือนก่อน

    Thank you for this. I now understand why it's only 1/4 turn.

  • @uptoolate2793
    @uptoolate2793 3 หลายเดือนก่อน

    Thank you. My valve, which I installed myself to please the water district, is 16 years old. This leak happened only once before today. That was 10 years ago. I forgot what what I did to fix it last time. I watched a more technical video earlier today that gave me the confidence to tackle the leak. It amazing what I remembered. But your video confirmed for me I made the repair correctly. No stones or debris. Nothing I could see but a depression of wear in the washer so I flipped it over. Repaired for zero cost. Again, thank you.

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 3 หลายเดือนก่อน

      You are welcome. Just know flipping the disc won't last as long as before you flipped it as it is hitting in the same spot as the side you just flipped. It now doesn't have any support or strength on the other side. It is intended to be a temporary fix.

  • @andyrowe1424
    @andyrowe1424 3 หลายเดือนก่อน

    Great ...now you have homeowners repairing backflows...they arent trained and qualified to repair and test any testable backflow device !!! Thats why plumbers have licenses to protect our public water utility

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 3 หลายเดือนก่อน

      I understand your concern. However, they are going to do it anyway and in many places codes allow them to do it. These videos are also not just for them but those that are licensed to do it. Many of them do not understand how to do it either and know very little about installation requirements for them.

    • @uptoolate2793
      @uptoolate2793 3 หลายเดือนก่อน

      Union plumber much?

  • @johnmccracken8023
    @johnmccracken8023 3 หลายเดือนก่อน

    Thank you for this very important video repair guide.

  • @chrisroberts8739
    @chrisroberts8739 3 หลายเดือนก่อน

    You mentioned that the washer has a "beveled edge" that goes under the head of the screw. The washer just looked flat to me. Do you mean it is slightly concave? In either case, could you be more specific on what way that the metal washer should go? What are we looking for? Thanks, Crzzy1

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 3 หลายเดือนก่อน

      The washer shouldn't be concaved. It should be flat. But one side should extend a fraction wider than the other side. The side that should go against the washer is the longer side. And the edge of this side feels a little more sharp. The other side that is away from the rubber disc is more rounded. I have found out since that according to Wilkins it doesn't matter, but I have had an experienced technician of several decades tell me it does matter. I think over time the washer might not be as easy to distinguish the edges as I think they wear away. You should be able to tell by the staining on the washer from the water what side was not against the rubber disc. Not sure if this helped, but I really think putting it on will not be noticeable.

    • @chrisroberts8739
      @chrisroberts8739 3 หลายเดือนก่อน

      @@backflowsupplyslcut9394 Thank you for the prompt reply! 🙂

  • @qing7
    @qing7 3 หลายเดือนก่อน

    Thank you for your sharing. I have the same pressure breaker and I am having hard time to take the bonnet off, it is so tight and maybe rusty. I have tried oil on it but it doesn’t help. Do you have any suggestions? Thank you!

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 3 หลายเดือนก่อน

      Take a hammer and gently tap around the outside of the housing at the top where the threads of the bonnet go down into the body. See if that will help loosen it up. if you are not using a long bar of some sort to put in between the three "legs" that the screws go into that the canopy attaches to I am not sure how else to get it out.

    • @qing7
      @qing7 3 หลายเดือนก่อน

      @@backflowsupplyslcut9394 It works!!! THANK YOU SO MUCH!!

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 3 หลายเดือนก่อน

      @@qing7 Glad it worked, but what worked specifically? The tapping with the hammer, the long bar to turn it with or both?

  • @k24accord1993
    @k24accord1993 3 หลายเดือนก่อน

    Did he just use a tool for a shut off valve....video skipping in 3,2,1

  • @partyhotline
    @partyhotline 3 หลายเดือนก่อน

    Shut off SOV#2 is all you forgot.

  • @user-qy5nt4jj5n
    @user-qy5nt4jj5n 4 หลายเดือนก่อน

    What does the number 4 test cock have to do with the number 1 check valve? You failed to explain how the number 4 test cock stopping the relief valve from leaking means that. Your number one check is bad?

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 4 หลายเดือนก่อน

      Opening the #4 test cock or if necessary opening a valve down stream that gets a greater flow through the assembly than what is coming out of the relief valve is a means of trouble shooting if the issue is the #1 check or the relief valve. It in effect allows the relief valve to fully close if it is a number one check issue. But if it is a relief valve issue it doesn't matter if water is flowing or not and you will know where to focus your efforts in your repair or cleaning.

  • @josefernandez8504
    @josefernandez8504 4 หลายเดือนก่อน

    This works in black pipes

  • @jayasanala
    @jayasanala 4 หลายเดือนก่อน

    i have the same Backflow assembly but when i turn it on today after winter, water gushing out from releaf valve and wont stop. actually when i first turn it on it was leaking from the releaf valve so i removed and put it back from then onwords water just gushes out from releaf valve. how can i fix it , please help.

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 4 หลายเดือนก่อน

      Did you come in today and get parts for this?

    • @jayasanala
      @jayasanala 3 หลายเดือนก่อน

      @@backflowsupplyslcut9394 no i m in Franklin TN

    • @jayasanala
      @jayasanala 3 หลายเดือนก่อน

      @@backflowsupplyslcut9394 i was able to stop gushing out of Relief valve but not able to completely stop leaking. now its still leaking even after changing all the parts.

  • @dzmitryrazalyeu
    @dzmitryrazalyeu 4 หลายเดือนก่อน

    Thank you very much for this video. This is so helpful. May I ask you a question? I have to replace a 3/4 valve with a bleeder in my system. I'd like to understand why one valve has a bleeder and the other doesn't? Does it matter which one has a bleeder from the other two? Thank you.

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 4 หลายเดือนก่อน

      i do not know what you mean by you need to replace a 3/4" bleeder in your system. When you say system are you referring to just the backflow assembly? Do you have the Wilkins 975XL or 975XL2 model? When you say bleeder are you referring to the test cock, the valve with the screw driver slot in it? Is it the one on the inlet ball valve? The inlet is supposed to have a test cock on it. So if you want to replace the test cock only you can. If you have to replace the ball valve with the test cock in it you can get that ball valve, but most models just come tapped and threaded and you can usually just take the old test cock out and reuse it. If you need to replace the ball valve on the outlet side of the assembly it doesn't have a test cock. If you need to send me pictures you can email me at sean@backflow-supply.com or call at 801-355-6736 on Monday. I will be out in the morning, but will respond to your email or call as soon as I can. Sean

  • @RotaryChannel
    @RotaryChannel 4 หลายเดือนก่อน

    thank you! Very helpful video!

  • @joniyee1467
    @joniyee1467 4 หลายเดือนก่อน

    I got a notice that the test of my backflow prevention assembly failed. The notice said "Assembly Untestable: Test Cocks #1-4" Could you help me know what that means?

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 4 หลายเดือนก่อน

      Sorry for the delay in responding. I can only assume that the tester is indicating that there is an issue with the test cocks. Have you tried taking a screwdriver out and turning the screw to see if they turn or not? Every quarter turn is open close. It does not tighten. Just open and closes a small ball inside. Please check that and get back to me. It might be best to email me at sean@backflow-supply.com or call me at 801-355-6736. I check these comments on TH-cam about once a day.

  • @glencaldwell3493
    @glencaldwell3493 5 หลายเดือนก่อน

    Thank you for the very clear instructions. You helped me understand the repair and assembly process.

  • @thelovefamilymilitarypod
    @thelovefamilymilitarypod 5 หลายเดือนก่อน

    How long can you use a kit after the calibration date has expired? Wondering if it’s a grace period

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 5 หลายเดือนก่อน

      it depends on the jurisdiction. It is only recommended it is calibrated annually. But some jurisdictions see the date as a hard date. You would need to see what they would allow.

  • @erikbradley3050
    @erikbradley3050 5 หลายเดือนก่อน

    Can I buy that socket adapter to shut off the water?

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 5 หลายเดือนก่อน

      If you are referring to that tool used at 2:22 in the video, yes you can buy those to shut off the ball valves on backflow assemblies. There are three different sizes. Part numbers WV100, WV101, WV106. backflow-supply.com/collections/backflow-test-kit-accessories

  • @erikbradley3050
    @erikbradley3050 5 หลายเดือนก่อน

    Where did you get that socket adapter tool to shut off the water?

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 5 หลายเดือนก่อน

      There are different sizes. part numbers WV100, WV101, WV106 backflow-supply.com/collections/backflow-test-kit-accessories

  • @paulfox521
    @paulfox521 5 หลายเดือนก่อน

    🎉😅thank you

  • @jamminr7533
    @jamminr7533 5 หลายเดือนก่อน

    So on that relief valve stem, does that "piston" with the red oring supposed to slide on that stem to compress the spring? Im rebuilding an 1½" 909 at the moment but it keeps blowing out the relief. Ive taken it apart 3 times now and this last time i checked, the "piston" wont move. Is that a problem??

    • @backflowsupplyslcut9394
      @backflowsupplyslcut9394 5 หลายเดือนก่อน

      No. That part where the red-ring sits does not move independently. The water pressure will push on the diaphragm and push the whole stem in compressing the spring. If you notice on the spring end of the stem is a nut and washer. That nut will sit in a recess further in the body and the washer will sit outside of the recess. When the pressure pushes the stem it compresses the spring and moves the stem to push the brass piece with the rubber molded into it onto the seat and the "piston" portion with the red o-ring to where it needs to sit against the body. If you need more help call me at 801-355-6736 or email sean@backflow-supply.com

    • @jamminr7533
      @jamminr7533 5 หลายเดือนก่อน

      @@backflowsupplyslcut9394 thank you sir!!!

  • @danmaltbie4507
    @danmaltbie4507 6 หลายเดือนก่อน

    Great explanation. Really helps a home owner do it them selves. Thanks.

  • @shauntampa
    @shauntampa 6 หลายเดือนก่อน

    For any irrigation backflow I would only install a Wilkins 375 or 975. So much easier to service.