Electrical Designing of High Rise Building G+10 | Electrical Design Course

แชร์
ฝัง
  • เผยแพร่เมื่อ 24 พ.ย. 2024

ความคิดเห็น • 150

  • @prasenjit_hazra
    @prasenjit_hazra 3 ปีที่แล้ว +6

    A Big Thanks for your magnificent job of teaching us from scrach. It often helpful to make some quality negotiation with consultant & infra individual as a "Sales Specialist".

  • @SrujanRaghavendra-y9h
    @SrujanRaghavendra-y9h ปีที่แล้ว +2

    A very rare video on electrical design. Thank you so much for the clarity in explaining.

    • @ElectricalInfinity
      @ElectricalInfinity  ปีที่แล้ว

      You are welcome. Make sure you subscribe and share it with your friend's and colleagues.
      Thanks ❤️

  • @abdiit5129
    @abdiit5129 3 ปีที่แล้ว +5

    Great, thank you! Can we consider socket outlet power consumtion as a common connected load? And also please share us electrical design for residential house G+3 with all connected load like kitchen, lighting, washing machine, Iron, sockets, water pumps, oven , etc. Thanks bro.

  • @abdulkhadeer2351
    @abdulkhadeer2351 3 หลายเดือนก่อน

    Thanks a lot for making a video of full knowledge, easy explaination, simple method.. it helps us a lot to perform best in company and to face the interviews.
    Tons of thanks to you❤

  • @9852626796
    @9852626796 ปีที่แล้ว +1

    Just now I seen your video it's outstanding.
    Can I get this elaborated topic in pdf format please.

  • @salahuddinbangash4785
    @salahuddinbangash4785 2 ปีที่แล้ว +3

    Damn Nice bro, I thought it will be difficult but this is just basic electrical engineering 🔥🔥

    • @ElectricalInfinity
      @ElectricalInfinity  2 ปีที่แล้ว +2

      Yeah much easier than engineering theories. But on Job it is a challenge to deal with complexity of projects. This was just a basic sample to make it easier for audience to understand.

  • @mobilesandcomputers5931
    @mobilesandcomputers5931 2 ปีที่แล้ว +2

    I am working as a deputy messenger in a good housing society in Pakistan. I have seen your video on youtube. It is important to learn building. Tell me some main points

  • @salunkhesandeep
    @salunkhesandeep ปีที่แล้ว

    Very well explained... Thanks so much for sharing knowledge....

  • @sultanurrahman799
    @sultanurrahman799 ปีที่แล้ว

    It's helpful for technical support

  • @koala4599
    @koala4599 2 ปีที่แล้ว +1

    first of all thank you for the great video, But please can you explain how you decide to use 7.5 kw for 3BHK ?

  • @incredibleindia3572
    @incredibleindia3572 ปีที่แล้ว

    Wonderful Explanation ❤

  • @mdshadaabalam2612
    @mdshadaabalam2612 3 ปีที่แล้ว +2

    Awesome explained.....sir kindly make video on cable sizing, voltage drop, ssc, bus bar sizing, earthing and lighting arrester calculation for the same project.

    • @mdshadaabalam2612
      @mdshadaabalam2612 3 ปีที่แล้ว

      Request you to make video as soon as possible.

  • @_InzimamImtiazuddin
    @_InzimamImtiazuddin 7 หลายเดือนก่อน

    Thank you very much for this informative video. I had one question. 2BHK flats are provided with single phase supply. So when determining C.B size, for converting Watts to Amps, we should be multiplying with 8 and not 1.9 right? (Based on your G+5 electrical design video)

  • @saleembasha7924
    @saleembasha7924 9 หลายเดือนก่อน

    Thank you for the detailed video bro.,👌👌👌👍👍👍

  • @rajeevneela2861
    @rajeevneela2861 ปีที่แล้ว

    Thank you... good knowledge given

  • @yatinthakuryt3362
    @yatinthakuryt3362 7 หลายเดือนก่อน

    Thank you very much for giving such great information.

  • @saalimbaig4896
    @saalimbaig4896 ปีที่แล้ว

    Very useful information

  • @therealitypresenters8616
    @therealitypresenters8616 6 หลายเดือนก่อน

    Great, haven't found any video on any platform like this. Glad if add cable sizing calculation grounding and lightning protection system.

  • @engmohamedmuraase5119
    @engmohamedmuraase5119 2 ปีที่แล้ว

    thanks sir for your kind to explain us more I would like to ask you PART-4 for the C.B sizing for main meter panel and flats.at PANEL-1 How you got common load result in 60kw? thanks sir.

  • @gkd5421
    @gkd5421 3 ปีที่แล้ว

    Sir, all your vedios are very informative..I seen all your channel... waiting for next latest vedios... thank you very much...

  • @StephenAgutu-gt2xu
    @StephenAgutu-gt2xu 2 หลายเดือนก่อน

    Good work

  • @sefatullah441
    @sefatullah441 3 ปีที่แล้ว

    manny many thanks sir g....outstanding video.......please continue thils topic electrical designing. upload more videos related to electrical building design..l...cable selection farmula etc.etc please

  • @shahbaazalam1003
    @shahbaazalam1003 3 ปีที่แล้ว +2

    Can you please make a video on calculation of lightning arrestor and calculation of earthing rod, pits and wire?

  • @smnmj3320
    @smnmj3320 5 หลายเดือนก่อน

    Thanks brother..it's a very helpful video.❤

  • @sagarvv4699
    @sagarvv4699 3 ปีที่แล้ว +2

    Thank you so much for this. Could you please if you have time just explain the above 40-floors building details as per Indian standard.

  • @imrankhan-uf7ww
    @imrankhan-uf7ww 3 ปีที่แล้ว

    great work sir ❤️❤️❤️❤️

  • @rahulgaikwad8430
    @rahulgaikwad8430 2 ปีที่แล้ว

    very good Explanation

  • @spritor6463
    @spritor6463 3 ปีที่แล้ว

    Good to see you upload regularly again :)

  • @mithunmathew7965
    @mithunmathew7965 2 ปีที่แล้ว

    Sir, We need to consider hvac load
    for public area and corridor's,
    Firepump

  • @etelanarendra9873
    @etelanarendra9873 ปีที่แล้ว

    Excellent

  • @PraveenKumar-rh9bv
    @PraveenKumar-rh9bv 7 หลายเดือนก่อน

    Awesome very useful

  • @yograjsingh3604
    @yograjsingh3604 8 หลายเดือนก่อน

    wow very helpfull

  • @kobe8502
    @kobe8502 5 หลายเดือนก่อน

    At 11:00 how did you get those MCCB values? Why is it almost doubled when you already multiplied them by 2?

  • @ZubairAhmed-uc7tb
    @ZubairAhmed-uc7tb ปีที่แล้ว

    Thanks for the Video, Can your please explain how the Multipier Value (KW - A =x1.9 ) Comes. Where as I =P/(VxPF) for Single phase and I = P/(1.732xVXPF). Kindly Correct me if I am Doing any mistake understanding Data manipulation. Warm Regards

  • @Bandarofficial
    @Bandarofficial ปีที่แล้ว

    Thanks you so much.

  • @md.gufranansari9672
    @md.gufranansari9672 3 ปีที่แล้ว

    Please make a video overall design parts such as cable calculation, voltage drop, short circuit, power factor.

  • @davendertaneja3489
    @davendertaneja3489 3 ปีที่แล้ว

    Nice 👍

  • @roofi881
    @roofi881 3 ปีที่แล้ว +2

    HI Dear,
    I wanted to know that why did you assume DF as 70% while for the commercial buildings you mentioned earlier standar DF is 80-90% in India.
    please explain this point, Thanks

  • @sandeshdhungana2749
    @sandeshdhungana2749 3 ปีที่แล้ว

    Great video, thank you!! Would you make video on cable sizing considering voltage drop for high rise building.

    • @ElectricalInfinity
      @ElectricalInfinity  3 ปีที่แล้ว +1

      Thanks. Will make it soon.

    • @jahanzaibilyas2649
      @jahanzaibilyas2649 2 ปีที่แล้ว +1

      I think common load should be seperated and it should have Seperate SMDB

  • @AkashSingh-jz4zo
    @AkashSingh-jz4zo 2 ปีที่แล้ว

    In the video, df for residential is mentioned as 0.6, but you considered 0.75, why the difference? And what are the actual standards?

  • @Belive_trust_wait
    @Belive_trust_wait 4 หลายเดือนก่อน

    Sir give a link for , workout screen calculation...give a new video also sir

  • @franchettecariaga
    @franchettecariaga ปีที่แล้ว

    Hello! I just saw your channel and I am so thrilled. J would just like to ask.. Is this as per australian standard?

    • @ElectricalInfinity
      @ElectricalInfinity  ปีที่แล้ว

      Hi Franchette 👋,
      Thanks for watching. Yes, the design is as per Australian standards.

  • @Premkumark90
    @Premkumark90 2 ปีที่แล้ว

    Hello,
    Can I convert kw to amps by .
    First kw to kva
    Then kva to amps.
    If do like this different values coming ,what should I do?

  • @shahbaazalam1003
    @shahbaazalam1003 3 ปีที่แล้ว

    Can you make a video on the cable size selection from transformer to transformer's CB and from tx's CB to load' CB?

  • @sefatullah441
    @sefatullah441 3 ปีที่แล้ว

    waiting for your next video.. please upload soon

  • @emr207
    @emr207 10 หลายเดือนก่อน

    🎉super

  • @dineshmehta3688
    @dineshmehta3688 ปีที่แล้ว

    V good

  • @arunkumarthakur9679
    @arunkumarthakur9679 2 ปีที่แล้ว

    B+P+33 including club, stp, water supply, fire system. Provide electrical load calculation.

  • @kalingahistory
    @kalingahistory ปีที่แล้ว

    But the loads you clubbed together are single-phase loads. Where as the main power supply will in three phases.

  • @kv848
    @kv848 3 ปีที่แล้ว

    Great brother..Suppose you have 2 transfer pumps,1 is standby and other is on duty, means they will work interchangeable and both will not ON at Sam time and they are in same panel MCC,..So how will you calculate main cable to this panel, will you consider kW of both motor or only 1 ?

    • @ElectricalInfinity
      @ElectricalInfinity  3 ปีที่แล้ว

      Total of both.

    • @kv848
      @kv848 3 ปีที่แล้ว

      @@ElectricalInfinity but at any instant, both will not work together, then why we consider both load ? Is it general rule to consider both ?

    • @ElectricalInfinity
      @ElectricalInfinity  3 ปีที่แล้ว

      That's why we take 0.7 demand factor after calculating total load.

  • @rashidchibvuri2036
    @rashidchibvuri2036 10 หลายเดือนก่อน

    Thank you so much sir

  • @seng7333
    @seng7333 2 ปีที่แล้ว

    Nice explanation
    But
    The breaker size of 40A for 5kw load seems to be high
    Also 50A breaker is not standard size

  • @swapnilshiyaniya5306
    @swapnilshiyaniya5306 ปีที่แล้ว

    Time 11:04 When you are calculating MCB for 2BHK load, you multiplied 5kw by 1.9 ... but wo to 3 phase ke liye aayega na ... for 1 Phase 5.43 Amp aayega na as 5 kw load is Single Phase load. Please correct me if i am wrong.

  • @mujeebrehman7097
    @mujeebrehman7097 ปีที่แล้ว

    How you find the value of 1.4 when you convert kva to amp ?

  • @Concepttalks98
    @Concepttalks98 2 ปีที่แล้ว

    Brother you didn't count future expansion of 20-30% why?
    Also you considered only demand factor but not diversity factor ..
    And i designed further and calculated and i got secondary current more than 1200A ...so should I take 3 runs of 1core 300sq mm cable or 3 run of 3 core 300sqmm cable.?

  • @sabinaktar5135
    @sabinaktar5135 2 ปีที่แล้ว

    fab❤

  • @everythingforyouonly5694
    @everythingforyouonly5694 3 ปีที่แล้ว +1

    Why you take 2 time demand factor
    1) for TCL and
    2) for metering panel c.b selection

  • @shahidmasoodi4847
    @shahidmasoodi4847 หลายเดือนก่อน

    Is it according to Uae standard or indian standard

  • @Saichanti77
    @Saichanti77 ปีที่แล้ว

    Thanks ❤

  • @altamashsayed5264
    @altamashsayed5264 ปีที่แล้ว

    I have a doubt related cb sizizing
    For 1500kva transformer Secondary side.
    Once we convert kva to amp
    1500kva*1.4 =2100A
    Should be consider 1.5 safety factor or directly select breaker from 2100A

  • @copycatonlyoriginal6585
    @copycatonlyoriginal6585 ปีที่แล้ว

    Could you please provide links to reference guidelines?

  • @demonkiller2358
    @demonkiller2358 3 ปีที่แล้ว

    Can u make video on Important is and nec standards

  • @eaknadhwilson5931
    @eaknadhwilson5931 2 ปีที่แล้ว

    Bro it's better to share the image of those calculations thanks 👍🏻 very useful

  • @sachinlandge6401
    @sachinlandge6401 ปีที่แล้ว

    How to calculate electrical meter room and duct size

  • @tharserohit
    @tharserohit 2 ปีที่แล้ว

    Bhai single phase meter kitna load leta he

  • @AbidKhan-tj6en
    @AbidKhan-tj6en 2 ปีที่แล้ว

    Ipad kaun sa hai bhai btana lena hai mujhe

  • @altamashsayed5264
    @altamashsayed5264 2 ปีที่แล้ว

    I need urgent help.
    Actually I got bit confused.
    I have to select cable, which load I should consider while selecting cable size from transformer to MDB
    Should it be tcl amp or peak load amp or transformer amp or circuit breaker amp.
    Pls do reply as early as possible

    • @ElectricalInfinity
      @ElectricalInfinity  2 ปีที่แล้ว +1

      Usually a cable between transformer and supply connection facility is provided by supply authority and is sized depending on transformer secondary side ampere setting. Supply connection facility is used by supply authority to set the current to certain required amperes depending on supply application done by electrical consultant by calculating max demand. The cable from supply connection facility is sized depending on circuit breaker setting in supply connection facility.
      I hope this answers your question.

    • @altamashsayed5264
      @altamashsayed5264 2 ปีที่แล้ว

      @@ElectricalInfinity appreciate your reply..

    • @anwarullakhayoom7863
      @anwarullakhayoom7863 2 ปีที่แล้ว

      Always cable +breaker is sized as per continous current of the Transformer + consider the derating factors for grouping depth of laying and Thermal withstand capacity. and also the voltage drop . all calculated precisely.

  • @itz_tipzy5949
    @itz_tipzy5949 2 ปีที่แล้ว

    Where is the standard to be exact for 2bhk 5kw energy meter and 3bhk 7.5kw? I need to furnish it for a project of mine...

    • @ElectricalInfinity
      @ElectricalInfinity  2 ปีที่แล้ว +1

      IS 13010

    • @itz_tipzy5949
      @itz_tipzy5949 2 ปีที่แล้ว

      @@ElectricalInfinity thank you so much

    • @itz_tipzy5949
      @itz_tipzy5949 2 ปีที่แล้ว

      @@ElectricalInfinity can't find it in there... Is it mentioned explicitly that for a 2bhk this much capacity energy meter and so on... I have calculated loads of all flats individually but even after taking into diversity factor the load is quite large...

    • @itz_tipzy5949
      @itz_tipzy5949 2 ปีที่แล้ว

      @@ElectricalInfinity also if I could discuss it with you somwhere else..

    • @ElectricalInfinity
      @ElectricalInfinity  2 ปีที่แล้ว +1

      It's a general thumb rule contractor follows for considering total load. Usually it's 0-10 amps, 10-20amps and 20-30 amps energy meter rating.

  • @habibullah7853
    @habibullah7853 9 หลายเดือนก่อน

    This is very informative.
    I am here in UAE as a fresh electrical engineer and looking for job. Can anybody help me getting a job.
    Thank You

  • @kuldeepraghuwanshi60
    @kuldeepraghuwanshi60 หลายเดือนก่อน

    Sir cable size bhi bata dete

  • @tamaghnadutta1644
    @tamaghnadutta1644 2 ปีที่แล้ว

    From where I can get the Standerd chart of Transformer , Cb e.t.c

    • @ElectricalInfinity
      @ElectricalInfinity  2 ปีที่แล้ว

      You can get Transformer standard sizes from supply authority and cb sizes from manufacturer manuals or datasheets.

    • @anwarullakhayoom7863
      @anwarullakhayoom7863 2 ปีที่แล้ว

      Buy TNEB Hand book.

  • @muhammadwaqas4699
    @muhammadwaqas4699 ปีที่แล้ว

    Circuit breaker calculations?

  • @kobe8502
    @kobe8502 5 หลายเดือนก่อน

    It would be great to explain this slowly. Kind of confusing and some details were not explained properly. Why did you use 400A in 9:52?

  • @Aliajikar89
    @Aliajikar89 2 ปีที่แล้ว

    Raw power is done ...Sir plz added ups power....

  • @digantpatankar3758
    @digantpatankar3758 2 ปีที่แล้ว

    Sir please mention cable size.....in SLD...

  • @KhanContent
    @KhanContent 2 หลายเดือนก่อน

    Time 06:17 where this 1.4, 1.9 and 1.5 came from ?

  • @sherifgamal730
    @sherifgamal730 2 ปีที่แล้ว

    Can i have this Sheet you write in the video please?!

  • @electricalconcept32
    @electricalconcept32 3 ปีที่แล้ว

    Sir can you tell me if load is 868KW, power factor is.0.8 and voltage is 415v and the cable length is 138meter.
    Which size cable we should chose to have maximum voltage drop of 3 percent

    • @anwarullakhayoom7863
      @anwarullakhayoom7863 2 ปีที่แล้ว

      Calculate VD on actual current , Not on Derated Current. Derated Current is only for cable+Equipment selection.

  • @VijayKumar-qx1kr
    @VijayKumar-qx1kr 2 ปีที่แล้ว

    IN FOUR POINT HOW WILL YOU DESIGN THE PANEL?

  • @mudassariqbal8532
    @mudassariqbal8532 2 ปีที่แล้ว

    You should explain it according to any international standard,

  • @sefatullah441
    @sefatullah441 3 ปีที่แล้ว

    please make your next video at low speed

  • @mangeshdalvi842
    @mangeshdalvi842 3 ปีที่แล้ว

    Whay about shop, if considerd?

    • @ElectricalInfinity
      @ElectricalInfinity  3 ปีที่แล้ว +2

      Well we need add total load of the shop and consider demand factor as 0.8 to 0.9 for commercial places.

  • @sumanbepari609
    @sumanbepari609 2 ปีที่แล้ว

    How a flat will use 3 phase???

    • @ElectricalInfinity
      @ElectricalInfinity  2 ปีที่แล้ว

      All loads are distributed equally among each phase of 3 phase supply. Usually the loads are single phase for example lighting circuits and power loads. If it's 3 phase load then a 3 Phase supply is provided.

    • @sumanbepari609
      @sumanbepari609 2 ปีที่แล้ว

      @@ElectricalInfinity sir, then there are SPN inside the room which are not showing here???

    • @anwarullakhayoom7863
      @anwarullakhayoom7863 2 ปีที่แล้ว

      upto 3KW - 1PH /240V IS enough , >3kw opt for 3ph 415v.

  • @shaneefh926
    @shaneefh926 3 ปีที่แล้ว

    For 19 amp y we use 40 amp breaker+

  • @AK_Entertainment26
    @AK_Entertainment26 ปีที่แล้ว

    please upload video we are waiting for new video

  • @khan__123
    @khan__123 2 ปีที่แล้ว

    Bhai ye pen kaha se magbaye

  • @outofthebox6027
    @outofthebox6027 6 หลายเดือนก่อน

    Sir can you share the notes??

  • @mobilesandcomputers5931
    @mobilesandcomputers5931 2 ปีที่แล้ว +1

    ONLY I NEED YOUR ONLY FEW TIME IF POSSIBLE I WIST YOU GIVE ME POSITIVE RESPONSE

  • @prithivi5440
    @prithivi5440 ปีที่แล้ว

    Hloo bro can you share your linked in profile?

  • @mustafaidris6476
    @mustafaidris6476 7 หลายเดือนก่อน

    Thank u , but its very fast way so
    As you r trading from papers

  • @mohammedezaj1018
    @mohammedezaj1018 3 ปีที่แล้ว

    Where is cable sizing, voltage drop, sc calculation?

    • @ElectricalInfinity
      @ElectricalInfinity  3 ปีที่แล้ว +3

      Will make another video for that. The video would have become lengthier if added everything you asked for.

    • @mohammedezaj1018
      @mohammedezaj1018 3 ปีที่แล้ว

      @@ElectricalInfinity Thank you

  • @everything7790
    @everything7790 6 หลายเดือนก่อน

    1 KVA = 1.9 anybody explain please
    in my calculation its is 1.39 something

  • @farazuddin7160
    @farazuddin7160 ปีที่แล้ว

    they said three lift but write only two lifts

  • @peopleofkpk5558
    @peopleofkpk5558 ปีที่แล้ว

    Very interesting but your vedios is too much fast 🙈

    • @ElectricalInfinity
      @ElectricalInfinity  ปีที่แล้ว

      Thanks and sorry for that. You can use reduce the speed to 0.8x while watching

  • @md.gufranansari9672
    @md.gufranansari9672 3 ปีที่แล้ว

    This video already you had made

    • @ElectricalInfinity
      @ElectricalInfinity  3 ปีที่แล้ว +1

      Steps 4 and 5 are different. This one is for high rise building not g plus 5. Watch it full you will know the difference. 😊

  • @notfalcongaming7839
    @notfalcongaming7839 3 ปีที่แล้ว

    Hlo

  • @hark758
    @hark758 8 วันที่ผ่านมา

    very fast explanation 🙄

  • @kashmirengineeringvision
    @kashmirengineeringvision 3 หลายเดือนก่อน

    really helpful amir need a small help is it possible to get in touch with you that will be your most kindness