Relay setting calculation|IDMT relay|Protection|Electrical Technology and Industrial Practice

แชร์
ฝัง
  • เผยแพร่เมื่อ 17 ต.ค. 2024
  • In this video we have explained calculation for IDMT over current relay setting calculation. These calculations are required for successful implementation of protection of power system and protection co-ordination
    #ElectricalEngineering, #ElectricalTechnology,
    #RelaySettingCalculation, #IDMTRelaySetting, #OverCurrentRelaySetting, #RelayCoOrdination
    #ElectricalTechnologyAndIndustrialPractice
    The explanation given in the video is applicable for all the below mentioned topic.
    1. Relay setting
    2. IDMT relay setting
    3. Relay co-ordination
    4. Inverse time relay
    5. Protection
    6. Relay setting calculation.
    7. How to calculate settings for relays
    8. Relay setting in substation.
    9. Relay setting calculation example.
    please visit our website
    electricaltech...

ความคิดเห็น • 195

  • @bharatekmauj3245
    @bharatekmauj3245 4 ปีที่แล้ว +3

    There are hundreds of videos on this subject in youtube. But you are standing out of all because of your simplicity but precise way of explaining. It is very clear to me. Thanks for your good job.

  • @naveensm415
    @naveensm415 5 ปีที่แล้ว +7

    Hai sir, Really useful video. I have worked in SIEMENS and ABB as a electrical engineer but i have realized that i need to improve my technical skills. Your video gives good technical knowledge so keep it up!! And please add more video about relay coordination with upstream and downstream including discrimination time. Atleast add 11/0.433 kV incomer system and two LT motors of small kW rating then please give lecturer about relay setting calculation by considering EI,VI,NI curves. Thanks in Advance!!

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  5 ปีที่แล้ว +3

      Thank you for your comment. I will make video on the co ordination of relays. It may take some time, but I promise you that i will make video on those topic. Pleasr stay connected with my channel.

    • @kazirashel179
      @kazirashel179 2 ปีที่แล้ว

      @@electricaltechnologyandind5335
      Sir, everything was okay. you calculated everything but I don’t know where come from 60 m/sec? Pickup -5A, TSM-0.17, say time-0.5sec. But why you don’t use calculated value? 0.5+6=0.56 sec!!!

  • @jimuelvillaoz4238
    @jimuelvillaoz4238 4 ปีที่แล้ว +1

    I am from Philippines and i really appreciate this channel. This is very importamtivve

  • @MahMohamedBabou
    @MahMohamedBabou ปีที่แล้ว

    Thanks a lot for the clear explanation
    But i have a question how do we find the value of the required operation time which you have equal to 0.5 sec

  • @TOFFYHERO
    @TOFFYHERO 3 ปีที่แล้ว

    Thank you for teaching. I like these VDO.

  • @shanahmed9710
    @shanahmed9710 3 ปีที่แล้ว +1

    Can you please share the fault current formula you have used?
    We have MVA actual, Voltage actual, and per unit impedance.
    How do I derive this formula?

  • @milanmukherjee9425
    @milanmukherjee9425 4 ปีที่แล้ว +1

    Please give me an example about the NPS setting and required unbalance current of the transformer to operate the relay.and also describe the TMS setting.thanks

  • @VideozForFun
    @VideozForFun 4 ปีที่แล้ว +1

    Bro why did you add 60ms to 0.5s? What is the 60ms? What is the difference between the 0.5s and 60ms?

  • @sujaythakur6665
    @sujaythakur6665 3 ปีที่แล้ว +1

    At last you have added 60ms in the Breaker Operating time, Is that you converted 0.17Sec=60ms?

    • @Onlineelectrical123
      @Onlineelectrical123 ปีที่แล้ว

      th-cam.com/video/ISdnXvNDRvc/w-d-xo.html
      Psm.n tms calculation..easy trick

  • @dkverma67
    @dkverma67 2 ปีที่แล้ว +1

    What is the use of TMS value calculated in the video?

  • @ivinngunyule2108
    @ivinngunyule2108 3 ปีที่แล้ว

    Take me back to Electrical protection III, thank you sir for this information.

  • @gautamev7473
    @gautamev7473 2 หลายเดือนก่อน

    Sir in definition you are saying pick up current as 120% of full load current however in calculation you are dividing it by CT ratio. I guess definition should be corrected. Similarly for PSM.

  • @TecKideos
    @TecKideos 5 ปีที่แล้ว

    i have 2 x In given as 2 x 0.1A, time is 0.23 TMS, and Ia=0.1A TMS is fixed value does my relay operation time is different with fault current or it will always operate on same time which i set ? As i see you calculated fault current as with fixed values for PSM

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  5 ปีที่แล้ว

      no, for different fault current the psm will be different. the setting calculation is made based on the design fault current, where the fault impedances are ignored, to get the worst condition. but in actual there are fault impedance which reduces the fault current. so your relay operating time will vary. and that is the principle of idmt characteristics. inverse time, i.e. for higher fault current the operating time will be lower and for lower fault current the operating time will be higher.

    • @TecKideos
      @TecKideos 5 ปีที่แล้ว

      ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE in my case no where written in serting that its IDMT its only written as Characteristic A whats that means curve?

    • @shameer2880
      @shameer2880 4 ปีที่แล้ว

      @@TecKideos
      As per IEC standard curve A means IEC standard inverse curve...

  • @ashik2940
    @ashik2940 3 ปีที่แล้ว

    Great work by you

  • @shantanumajhi5408
    @shantanumajhi5408 3 ปีที่แล้ว

    Very informative Sir. Wish more and more will come in the same way

  • @noelvillaluz5978
    @noelvillaluz5978 ปีที่แล้ว

    What standards for calculation of protective relay setting calculation

  • @purnasahoo791
    @purnasahoo791 4 ปีที่แล้ว

    I have doubt in. What is pick up and pick up value is 5A or 1*CT sec /In is same?

  • @TecKideos
    @TecKideos 5 ปีที่แล้ว

    Hello brother, my question is if i have given only characteristic A for ABB relay and fixed TMS by the designer does tripping time vary with fault current?

  • @selvammurugaiah2074
    @selvammurugaiah2074 3 ปีที่แล้ว

    Clear and concise explanation.well done

  • @mayurjoshi2861
    @mayurjoshi2861 ปีที่แล้ว

    Very nice. Thank u Sirji

  • @maheshsahane7292
    @maheshsahane7292 5 ปีที่แล้ว

    Which technical book should we use for 50/51/50N/51N settings

  • @nayannarkhede7087
    @nayannarkhede7087 2 ปีที่แล้ว

    Thank you! amazing work!

  • @NKumar318
    @NKumar318 3 ปีที่แล้ว

    Thanks sir for the precise information, great work by you

  • @mahadevakumar2104
    @mahadevakumar2104 4 ปีที่แล้ว

    Thanks for the video. Please let me know why does t is taken as 0.5 sec only

    • @sandeepkakulapati
      @sandeepkakulapati 4 ปีที่แล้ว

      its depends on system withstandable sc current . For example breaker sc rating 40KA For 1sec, so rated fault current should be cleared within that time

  • @amanmehta2100
    @amanmehta2100 3 ปีที่แล้ว

    Thank you so much sir please make another differential protection relay vedio

  • @surendrakverma555
    @surendrakverma555 2 ปีที่แล้ว

    Very good. Thanks 🙏🙏🙏🙏

  • @saksham9180
    @saksham9180 5 ปีที่แล้ว +3

    Thank you,
    It is what I needed.

  • @dharamnathsharma8192
    @dharamnathsharma8192 4 ปีที่แล้ว

    Thank you dear. It enhanced my clarity.

  • @emonshariyar4155
    @emonshariyar4155 3 ปีที่แล้ว

    Very important lesson 👌👌👌

  • @afghanwindsolarltdaws4287
    @afghanwindsolarltdaws4287 5 ปีที่แล้ว

    Thanks you so much for your great video , Please tell me what is ( 0.02 & 0.14) in your calculation is it constant ?

  • @palashhossain2989
    @palashhossain2989 3 ปีที่แล้ว

    Good topics

  • @md.abdullahal-mamun5936
    @md.abdullahal-mamun5936 3 ปีที่แล้ว

    Good teaching

  • @cozymantrilo
    @cozymantrilo 3 ปีที่แล้ว

    Where did sir get the 1.732 from ?

  • @abirjana8167
    @abirjana8167 4 หลายเดือนก่อน

    Thank you sir,very informative video🙏🙏,Plz Upload new video☑️

  • @masumbillah2665
    @masumbillah2665 3 ปีที่แล้ว

    Thanks for this video

  • @tamimgamming514
    @tamimgamming514 3 ปีที่แล้ว

    Nice one

  • @ashokar9135
    @ashokar9135 3 ปีที่แล้ว

    Hi sir good evening
    How can we select ct of 4000a when the fault current is More than the CT ratio. How can CT sustains excess current. Kindly let me know sir.

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  3 ปีที่แล้ว +1

      Every equipment has a continuous current rating and a short time withstand rating. Short circuit falls under short time category. That is why you need to specify ct as say 2000/1A, 50kA for 1 sec. High fault current will be tolerated only for 1 sec.

    • @ashokar9135
      @ashokar9135 3 ปีที่แล้ว

      @@electricaltechnologyandind5335
      Thanks for clearing my doubt sir...... Thank you so much

  • @ekosan991
    @ekosan991 5 ปีที่แล้ว +4

    Keep on, please show us the differential setting calculation for transformer

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  5 ปีที่แล้ว +2

      I shall release a series of videos fr different Protection. So please stay tuned and support

    • @ekosan991
      @ekosan991 5 ปีที่แล้ว +1

      Thank you very match

  • @syed_taha_ahmed
    @syed_taha_ahmed ปีที่แล้ว

    Hello Gentlemen very nice video
    Could you please brief me about
    I>,>>,I>>> pickup written in 7SJ62

  • @sogibhassan3578
    @sogibhassan3578 3 ปีที่แล้ว

    Good job

  • @md.mehedihasan8314
    @md.mehedihasan8314 4 ปีที่แล้ว

    Thanks a lot of.
    And what is l> , l>> & l>>> ?

  • @ShairAliDar
    @ShairAliDar 7 หลายเดือนก่อน

    How to calculate the settings for the feeder relay used on RMU.

    • @Srinivasaae
      @Srinivasaae 6 หลายเดือนก่อน

      😢ssazstslssaz😮s

  • @nadersad
    @nadersad 3 ปีที่แล้ว

    I have a question, what is the time which relay needs to clear the fault?

  • @happymirrorofyourlife1517
    @happymirrorofyourlife1517 2 ปีที่แล้ว

    hi sir .how did you get psm value 0.02

  • @djgamming485
    @djgamming485 3 ปีที่แล้ว

    Thanks for solving my problem

  • @gnanavelvelu9645
    @gnanavelvelu9645 5 ปีที่แล้ว +3

    bro, may i know where did you got 0.14 in the calculation?

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  5 ปีที่แล้ว +4

      it is iec standard inverse relay characteristics. i have a video on different relay characteristics. watch that. your doubts will be cleared.

  • @ahamedshahinck8562
    @ahamedshahinck8562 3 ปีที่แล้ว

    thanks for information

  • @karma23577
    @karma23577 4 ปีที่แล้ว

    while calculating TMS, we have assume t=0.5 sec so how we can assume this data?

    • @sandeepkakulapati
      @sandeepkakulapati 4 ปีที่แล้ว +1

      sandeep kakulapati
      1 second ago
      its depends on system withstandable sc current . For example breaker sc rating 40KA For 1sec, so rated fault current should be cleared within that time

  • @yokeleetan8525
    @yokeleetan8525 2 ปีที่แล้ว

    i love your video

  • @karademirzck
    @karademirzck 3 ปีที่แล้ว

    thank you. i was so clear

  • @ksusmitha5402
    @ksusmitha5402 5 ปีที่แล้ว

    Sir u said that pick up current is equal to pick up of relay then y u didn't put the 5A in denominator of PSM formula sir instead u multiply 120%with full load current, y so sir?

    • @ksusmitha5402
      @ksusmitha5402 5 ปีที่แล้ว

      If so sir what is the difference between pick up of relay with CT value in formula and pick up current without CT value in formula which u have used in denominator of PSM? Kindly explain clearly sir!!

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  5 ปีที่แล้ว

      see suppose you have full load current 100A, Ct ratio of 120/1 A, then if you say i will set the relay to pick up at 120% of flc the your pick up will be 100*1.2*1/120=1

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  5 ปีที่แล้ว

      incase your ct secondary is 5A then the oick up shall be 5

  • @Roni_Hossain9809
    @Roni_Hossain9809 3 ปีที่แล้ว

    Great

  • @keithto5990
    @keithto5990 ปีที่แล้ว

    Good tutorial

  • @punilakra854
    @punilakra854 2 ปีที่แล้ว

    Very helpful

  • @saravananv2825
    @saravananv2825 2 ปีที่แล้ว

    For motor feeder how we consider

  • @pratikshasingh8560
    @pratikshasingh8560 5 ปีที่แล้ว +1

    please show us some realys, and 220kv breakers details internal connetions and working procedure for example master relay , for 220kv
    sf6 breakers ...

  • @sureshpadhy2243
    @sureshpadhy2243 3 ปีที่แล้ว

    On which basis required time delay is taken 0.5 s

  • @delosmark18
    @delosmark18 5 ปีที่แล้ว

    Kindly also discuss about the theory behind distance and directional relays

  • @akhilganapathineedi
    @akhilganapathineedi 5 ปีที่แล้ว

    Superb I even taken notes of everything

  • @PurvamBaxi
    @PurvamBaxi 3 ปีที่แล้ว

    How to set I> and I>> and Ie and Ie>> what does that term mean

  • @MdRasel-nc2sz
    @MdRasel-nc2sz 3 ปีที่แล้ว

    Thank you.

  • @zillurrahman4859
    @zillurrahman4859 3 ปีที่แล้ว

    Thank you sir

  • @raghavms1410
    @raghavms1410 4 ปีที่แล้ว

    Bro how did you calculate fault current. Please share the formula

    • @Arg212
      @Arg212 ปีที่แล้ว

      FLC/Impedance

  • @MehediHasan-wc7nq
    @MehediHasan-wc7nq 3 ปีที่แล้ว

    Important part

  • @md.al-alifsiddiki1620
    @md.al-alifsiddiki1620 3 ปีที่แล้ว

    Thanks Sir ❤️❤️❤️❤️❤️❤️❤️❤️

  • @jkj1459
    @jkj1459 4 ปีที่แล้ว

    WHAT IS THAT FACTOR 0.14 FOR CALCULATING RELAY OPERATING TIME ?

  • @moynakhatun992
    @moynakhatun992 3 ปีที่แล้ว

    Beautiful

  • @ashishsoni3287
    @ashishsoni3287 3 ปีที่แล้ว

    Thanks you...

  • @jkj1459
    @jkj1459 4 ปีที่แล้ว

    SIR HOW YOU DERIVED THE FAULT CURRENT ( BY WHAT PRINCIPLE ) ?

  • @torikulislam5161
    @torikulislam5161 3 ปีที่แล้ว

    Nice

  • @MDRaj-xp2dp
    @MDRaj-xp2dp 3 ปีที่แล้ว

    LOVE it

  • @mohammadjaved934
    @mohammadjaved934 9 หลายเดือนก่อน

    Good

  • @jkj1459
    @jkj1459 4 ปีที่แล้ว

    NICE ENGINEER

  • @naimulislam41
    @naimulislam41 3 ปีที่แล้ว

    Thank you

  • @raulsumalpong7327
    @raulsumalpong7327 5 ปีที่แล้ว

    Hi Thanks for the video. Anyway can you make a make regarding TCC curves...Thanks

  • @rakeshnanda9506
    @rakeshnanda9506 5 ปีที่แล้ว

    Nyc explanation....sir ese type ka more videos upload kijiye

  • @mdrajibhossain685
    @mdrajibhossain685 3 ปีที่แล้ว

    Love it

  • @প্রবাসীআপডেটনিউজ

    nice

  • @saqibbashir2866
    @saqibbashir2866 2 ปีที่แล้ว

    Sir it is requested make the formula correct,
    PSM is the ratio between fault current in secondary of CT to pick up current.

  • @mamunhossain3553
    @mamunhossain3553 3 ปีที่แล้ว

    super

  • @prakashjainapur6482
    @prakashjainapur6482 5 ปีที่แล้ว

    Most useful

  • @sujonshahofficial2572
    @sujonshahofficial2572 3 ปีที่แล้ว

    Wow

  • @jambugj8591
    @jambugj8591 5 ปีที่แล้ว +1

    Please tell me how you said breaker operating time 60ms added.

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  5 ปีที่แล้ว +5

      in generally breaker operating time is 60 mSec. the breaker contacts need 60 mSec time to completely extinguish the arc.

  • @nilbill648
    @nilbill648 4 ปีที่แล้ว

    Nice explanation
    U have any WhatsApp group sir?

  • @SaifulIslam-vb7gb
    @SaifulIslam-vb7gb 4 ปีที่แล้ว

    Thanks a lot.

  • @yusufpradityarahman9994
    @yusufpradityarahman9994 4 ปีที่แล้ว

    WHERE CAN I GET THE 1.732 NUMBER?

  • @mokonemaphale6137
    @mokonemaphale6137 5 ปีที่แล้ว

    Please make vedio on relay-relay coordination calculations

  • @mdforidulislam695
    @mdforidulislam695 3 ปีที่แล้ว

    wow

  • @sahedahamed3424
    @sahedahamed3424 3 ปีที่แล้ว

    Nic

  • @abdullayt588
    @abdullayt588 3 ปีที่แล้ว

    joss

  • @royalnirob1504
    @royalnirob1504 3 ปีที่แล้ว

    Wosm

  • @shelfrobthomas449
    @shelfrobthomas449 4 ปีที่แล้ว

    The formula depends on what kind of relays to be used.

  • @amlendrasharma7805
    @amlendrasharma7805 5 ปีที่แล้ว

    Dear sir please make a vidio on p111 relay setting manually

    • @neelprajapati1318
      @neelprajapati1318 5 ปีที่แล้ว

      Picture not showing clear.Make it clear.

  • @pateafanai5489
    @pateafanai5489 3 ปีที่แล้ว

    Sir Daniel-a vanga en zawng helamah like. 🤣🤭 👍

  • @SaifulIslam-cq9dy
    @SaifulIslam-cq9dy 3 ปีที่แล้ว

    Gd

  • @ibrahimhossin2880
    @ibrahimhossin2880 3 ปีที่แล้ว

    nics

  • @kedarnathswain2540
    @kedarnathswain2540 4 ปีที่แล้ว

    Sir 0.08 kya hai plz describe

  • @khan_tanzeem0521
    @khan_tanzeem0521 4 ปีที่แล้ว

    👍🏻

  • @denyhams
    @denyhams 4 ปีที่แล้ว

    0.14 kalkulation for destriction

  • @sureshthayana
    @sureshthayana 2 ปีที่แล้ว

    Last 0.5sec+60sec
    =56sec how is