Good day my man, I would like to thank you for your videos they’re all clean, useful and easy to understand. Could you please upload a video of a star delta circuit with indicator lights and emergency stop switch if possible 😊 Thank you in advance 🙏🏿
Thank you very much sir What is the problem when the main and the star are on and when trying to change over, they both switch off and the delta is not picking ?
Your circuit is wrong! What you have done is suppling control circuit from the timer NC, that's why the circuit runs in star but when the count down is done the entire circuit goes off. Not that the Timer only should control star and delta contactors but not the main. Your circuit should work in this configuration, When start button is pressed , the timer and star contactor should come on and then main contactor after the timer count down star contactor should go off without causing any problem then the delta come in. Op that helps thanks for watching.
It would be more helpful to your viewers if you name the terminals you’re connecting the wires to as to saying here and here. We can’t really see the names of the terminals and not all contractors have the same terminal arrangements. Really helpful content regardless 👍👍
Yes very important, safety is important for equipment and the operators. Here is why it. for the STAR DELTA case assuming the star contactor fail mechanically in the closed mode, Delta contactor still ENGAGE if your circuit isn't interlocked, but if interlocked even with a mechanical failure the Delta won't ENGAGE. it can only run Delta or Star but not both at same time. op that helps.
Well done,my question is, what could be responsible for a situation where you have your 3 phase intact but the contactor will not close when you give start command by pressing the start button?
why STAR contactor latch first and then and the MAIN contactor? It is the same if they start together. What is the reason for making the STAR contactor to latch first and then the MAIN contactor. Thank you
There are some contactors like the joy which do not have normal closed terminal where do you connect when u want to connect the star to the main contactor in ur wiring diagram
No....... and its because star-delta only used on the high loaded motor. when the motor is driving a big load it draws a lot of currents, that why we can't start it with DIRECT ONLINE it can blow easily. single phase motor is rated low. there is no need to start them with star delta.
Sizing the contactor is entirely depends on the current demand of the load For example, if your motor draws 15Amps then you would give it a contactor of 30Amps but I don't really see a 30A contactor, therefore, 45Amps is good for a 15A motor. OP that helps.
Can you try to upload another without using (here, there, this, path,) use the lables T1T2T3.... NO NC.. your video is great but i loose track when you use those terms
There is no book in particular that I can recommend, but if learn there is more information online and on youtube. you can start reading more blog posts on the areas you want to learn read here electrecasolutions.com/
Can you help on how you can connect an outomatic change over and pay pass it ...and and again ...how to pay pass a katko change over while using back up utility power
Hi team, the content and justification are well express via schematic diagram. My suggestion Tutor if you could simplifies that interpretation in to WIRING DIAGRAM Regards Dick Allen 🎉
I will make a video soon but let me explain something.........let me say we have 3 indicator lights for STAR, DELTA AND MAIN the purpose of the 3 lights is to indicate if the contactor is ENGAGED or NOT, Each of those light is to be connected to A1 and the NEUTRAL of each contactor. such that star contactor will come ON and OFF with its light....... op that helps...
The star contactor engages first, then the main contactor.... and to achive this ...the coil wire of the main contactor should go through the NO of the star contactor such that when the Star closes it's contact the Main contactor engages also...............op that helps
Thank you, but they're few things I didn't understand were by when u explain u say here.... Can u be more specific were by when u connect a wire try to tell us that A1 - NC etc and can u zoom in your camera so that we can see your contractors we jus wanna see how they're labeled.... Thank you
Can u jus help me on only 3 things please, I jus wanna know how your main contactor is labeled, same as the Delta and Star, I'm just a little bit confused with the drawing.. For example, Such as mains is No or Nc. Please I really want to know about this, thank you
I have seen electricians work without a voltage tester ; even car mechanics do the same without calculating the voltages that come from the battery ore AC curent that flow true components.
Engineer am not , therefore understanding the purpose of breaking btn the line supplying the main via the star auxiliary since u have connected it via the NC making no difference
Well explained but poor labeling, saying connecting here and connecting there isn't technical enough, why won't you use the the real labels like a1 of so and so to NO of so and so,,
Wow you have done it again excellent stuff ,you are my best electrical tutor.thankyou sir .
Thank you.....for that support and it's to know that am adding value to someone ....
Hi Sir thank you very much for your teaching about electrical installation my carrier in my long run. Once again thank you very much.
Very simple and easy to understand thanks for sharing this powerful video
Thanks for watching.
hello Mr David thank you for your helpful contents, I really appreciate
Great presentation and more helpful my brother.
Much appreciated
u've done it well,go on & thank u so much.
Thanks and welcome
Good day my man, I would like to thank you for your videos they’re all clean, useful and easy to understand.
Could you please upload a video of a star delta circuit with indicator lights and emergency stop switch if possible 😊
Thank you in advance 🙏🏿
Great suggestion! ill do my best.
Wiring diagram would have been better, this video lost me
How wrong will it be if the main initial start loop doesn't go through the star auxiliary contact? Kindly explain.
This is also my question ??
Thank you very much sir
What is the problem when the main and the star are on and when trying to change over, they both switch off and the delta is not picking ?
Your circuit is wrong! What you have done is suppling control circuit from the timer NC, that's why the circuit runs in star but when the count down is done the entire circuit goes off.
Not that the Timer only should control star and delta contactors but not the main.
Your circuit should work in this configuration, When start button is pressed , the timer and star contactor should come on and then main contactor after the timer count down star contactor should go off without causing any problem then the delta come in.
Op that helps thanks for watching.
It would be more helpful to your viewers if you name the terminals you’re connecting the wires to as to saying here and here. We can’t really see the names of the terminals and not all contractors have the same terminal arrangements. Really helpful content regardless 👍👍
Thank you point noted.
@@electreca1 Me thoughts exactly
Would you please do a video showing or indicating clearly the terminals you are connecting to
Hi, I didn't really understand how you wired the second main auxiliary contact. Can you please clarify. Thanks
I will clarifty on that in the coming whiteboard video.Thanks for watching.
its awesome but, i wish you can provide terminals numbers for all the contacts.
very good. i think i will go over this until i get it thanks a million
Your welcome come .....Thanx for watching
Does the terminals of the motors differ when you what to wire DOL and star delter?
Sir, terminal numbers are you connecting?
Good day, could you number the terminals in your drawing for the purpose of clarity.
Noted
I’m a bit confused, on the diagram are the delta and star connectors reversed than the ones shown?
Thanks so much for the videos
Hello sir..are the interlock auxiliary connections reaally important if your sure of the circuit
Yes very important, safety is important for equipment and the operators. Here is why it. for the STAR DELTA case assuming the star contactor fail mechanically in the closed mode, Delta contactor still ENGAGE if your circuit isn't interlocked, but if interlocked even with a mechanical failure the Delta won't ENGAGE. it can only run Delta or Star but not both at same time.
op that helps.
Well done,my question is, what could be responsible for a situation where you have your 3 phase intact but the contactor will not close when you give start command by pressing the start button?
How do connect auxiliarys to the timer and Delta and star contactors.
@benard please refrase your question and ask again.
why STAR contactor latch first and then and the MAIN contactor? It is the same if they start together. What is the reason for making the STAR contactor to latch first and then the MAIN contactor. Thank you
There are some contactors like the joy which do not have normal closed terminal where do you connect when u want to connect the star to the main contactor in ur wiring diagram
There is auxiliary contact that is hooked either on the top or sides of the contactor. Avery type of contactor big or small has that capability.
Thanks for your videos
I really like your tutorial
Thank you Kevin.... I also post articles on my blog here. electrecasolutions.com/
We appreciate so much can you do a video of how a conveyor operates
Still planning on that video. Thanks for watching
Hello there, I have question to ask you about star delta starter is possible to connect with single phase or to setup with single phase?
No....... and its because star-delta only used on the high loaded motor. when the motor is driving a big load it draws a lot of currents, that why we can't start it with DIRECT ONLINE it can blow easily.
single phase motor is rated low. there is no need to start them with star delta.
How many seconds do you adjust the timer on before switching from star to Delta
That normally can depend on the number of factors that ill discuss incoming video but 10-15seconds for most stuation can do.
@@electreca1 ok,so how many Amps are those contactors
Sizing the contactor is entirely depends on the current demand of the load
For example, if your motor draws 15Amps then you would give it a contactor of 30Amps but I don't really see a 30A contactor, therefore, 45Amps is good for a 15A motor.
OP that helps.
@@electreca1 Thank you very much Engineer David
how about you install a 3 phase wiring connection for bell wiring illustarations and draw the wiring diagram for CEEMODULE 2 KINDLY
Thank you for that video
Hello Sir! I really don't see how you connected the supply to the circuit, is it 3phase or single phase??
Sorry about that, The control circuit is single phase, Am planning on making another video that is more easy and transparent.
@@electreca1 Thanks! How I wish you do it soon 🙏
can you do a video for a soft starter?the control diagram and also power..Step by step as you did with the star delta
Can you try to upload another without using (here, there, this, path,) use the lables T1T2T3.... NO NC.. your video is great but i loose track when you use those terms
Ok, thanks
Which the best book for all this control panel
There is no book in particular that I can recommend, but if learn there is more information online
and on youtube.
you can start reading more blog posts on the areas you want to learn
read here electrecasolutions.com/
@@electreca1 I love it.
Hae tanks sir you have helped a lot
Can you help on how you can connect an outomatic change over and pay pass it ...and and again ...how to pay pass a katko change over while using back up utility power
Hi team, the content and justification are well express via schematic diagram. My suggestion Tutor if you could simplifies that interpretation in to WIRING DIAGRAM Regards Dick Allen 🎉
Can u please show us, how to connect the lighting indicator on this Star Delta starter control. Thank you
I will make a video soon but let me explain something.........let me say we have 3 indicator lights for STAR, DELTA AND MAIN the purpose of the 3 lights is to indicate if the contactor is ENGAGED or NOT, Each of those light is to be connected to A1 and the NEUTRAL of each contactor. such that star contactor will come ON and OFF with its light....... op that helps...
very encouraging electrical engineering lectures,but using the same colour of wire confuses me alot,thanx.
Thanks David can you please explain PLC
I will prepare the video
How do I know that the contactor is 380,240,and 415volts?
Contactors have specification sticker on them which bares all the rating information, just like electrical devices.
Thanks for watching
Thanks sir I also appreciate your video, sir my question is why it it that when the motor start it disengaged the contractor immediate that sir
It depends on the Delay usually for the Delta contactor to come in usually 10 sec
Thats good,,then how do we now wire the motor,
i will post a power circuit video soon
good day please why do you loop star contactor
The star contactor engages first, then the main contactor.... and to achive this ...the coil wire of the main contactor should go through the NO of the star contactor such that when the Star closes it's contact the Main contactor engages also...............op that helps
@@electreca1 thank you. it did
@@electreca1 great do you have WhatsApp
Which terminal numbers connection of delta, star wiring?
Could you do a video on how to size star delta starter? Thanks
Can u make video of where i can connect my generator control cable to which terminal
wonderful!
Thank you, but they're few things I didn't understand were by when u explain u say here.... Can u be more specific were by when u connect a wire try to tell us that A1 - NC etc and can u zoom in your camera so that we can see your contractors we jus wanna see how they're labeled.... Thank you
Thanks very much for feedback......... I'll work on it.
Can u jus help me on only 3 things please, I jus wanna know how your main contactor is labeled, same as the Delta and Star, I'm just a little bit confused with the drawing.. For example, Such as mains is No or Nc. Please I really want to know about this, thank you
The main contactor didn't disconnect, suppose delta only run the motor
Pls can you do a video on how to wire an inch or Jog circuit direct online
I will work on it. Thanks for watching.
Thanx so much sir but i am requesting that u help me simplify more the control diagram of possible. Thanx
Use deffrent colors in wiring to improve in our understanding
What is the function of a timer
How can get classes of control panel
Wow , i really like it.
I'm glad you like it and thanks for watching.
In yo next video you will need to explain as.to why one must use contactors,time and a switch instead of a breaker and switch
Helpful though somewhere you confused the viewer little bit,somewhere you said NC instead of NO,kindly follow and see.
sorry about that ill try to fix it.
Thanks sir
PLEASE SHOW THE STAR/DELTA STARTER DIAGRAM USING OFF--DELAY TIMER .
Explanation is good but the control diagram is not very clear
The writings have very small letters
I am planning a better way for the upcoming videos of the kind.
How else can one reach in person especially in social media
You have to mention NC&NO while connecting main,delta &star
Sorry i don't get your input, you can type again if you dont mind.
In the middle sir that delta has no power yet how star working or how give power to the motor
How can I semperent the control circket
Please also try to stick to the technical terms like Nc,No ,of the components
Noted
Sir please share the rating of relay.
Please try to use different colors of cables
Noted, thanks for watching .
Thanx
I have seen electricians work without a voltage tester ; even car mechanics do the same without calculating the voltages that come from the battery ore AC curent that flow true components.
Kindly show the Forward Reverse starter Diagram Using Off-Delay-Timer
Sorry brother, you haven't shown us how to connect Foward Reverse motor with timer
Good wark
pls clearly mention all contacts connected eg A1,A2, 21 & 22, 13 & 14, 95 & 96 of the o/L, etc
Engineer am not , therefore understanding the purpose of breaking btn the line supplying the main via the star auxiliary since u have connected it via the NC making no difference
This video will clear some air. th-cam.com/video/N0XrfE3VTLE/w-d-xo.html
Well explained but poor labeling, saying connecting here and connecting there isn't technical enough, why won't you use the the real labels like a1 of so and so to NO of so and so,,
Thank you and Point taken.
Where a u ?
Show me star delta stater without timer
I have failed to understand it well,,,
I get ur explanation but the wiring makes no difference, more guidance please
Can I plz join u
With push button
Sir ct and pt connection please sir
I lost you when you say here n here you are not explaining am lost the connection of main contactor.
Great do u have WhatsApp bro
Working on it.
Man ,that's grt move for starters coz normally in college they don't explain clearly all that.big up
Could u please make for automatic generator control also.