Sizing the SEPTIC TANK // Gaano Kalaki Ang Gagawin_Vlog 022

แชร์
ฝัง

ความคิดเห็น • 170

  • @bahayguhitplanodisenyo2568
    @bahayguhitplanodisenyo2568 4 ปีที่แล้ว +5

    Very useful info and very clear explanation akitek..nice job! ntawa ko s copy patse n septic tank drawing..

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      thanks for watching sir...God bless!

    • @donsantiago6298
      @donsantiago6298 3 ปีที่แล้ว +1

      @@arkitekjon hello sir, yung sample size na septic tank, gaano katagal bago mapuno ung digestive chamber. Kasi ang volume lang Niya ay 1.2 cu.m. ilang percent ang solids sa 75 gallon/ day na sewer discharge.

    • @arkitekjon
      @arkitekjon  3 ปีที่แล้ว +1

      supposed to be hndi yan basta-basta mapupuno dahil may outflow after na-process ang effluent sa Chamber..hindi sya storage or tambakan ng discharge.

  • @bachuteric3626
    @bachuteric3626 4 ปีที่แล้ว

    Good job Architect! Very practical and informative vlog, I appreciate it much.

  • @anselmobuday852
    @anselmobuday852 3 ปีที่แล้ว +1

    Thank you very much. Very informative. Now I know how to compute the realistic dimensions of the septic tank.

  • @miriamparisian8872
    @miriamparisian8872 4 ปีที่แล้ว

    Thank you for a very important info.

  • @pattysdiary9798
    @pattysdiary9798 4 ปีที่แล้ว

    Great advice at very useful and informative

  • @patrickargana6937
    @patrickargana6937 3 ปีที่แล้ว

    Salute! Thank you Sir! More power sa inyo!

  • @kimpaulosolis7862
    @kimpaulosolis7862 4 ปีที่แล้ว +1

    Very informative Arch. More power! 🙂

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      thanks bro Kim...

  • @hannahheart6273
    @hannahheart6273 4 ปีที่แล้ว

    Very informative. . Thank you Architect. GOD bless

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      thank you Annamarie😊

  • @nofeardhon
    @nofeardhon 4 ปีที่แล้ว

    Useful info..deserving like and subscribe..👍😉

  • @commonpeople9801
    @commonpeople9801 4 ปีที่แล้ว

    Galing naman ni Arkitek JON!

  • @bhengjewpin2474
    @bhengjewpin2474 11 หลายเดือนก่อน

    Thanks arki...

  • @josephdavepaterno1007
    @josephdavepaterno1007 3 ปีที่แล้ว

    very useful!!!

  • @francisbarona8513
    @francisbarona8513 4 ปีที่แล้ว

    one of the best Arki Vloger na napapanood ko. Very informative.

  • @jeanatkin4571
    @jeanatkin4571 2 ปีที่แล้ว

    Thanks good info.

  • @jenbee5002
    @jenbee5002 2 ปีที่แล้ว

    nice galing po hahaha. medyo may mali padin pala sa mga computations ko haha thanks for clarifying everything.

  • @devs9294
    @devs9294 3 ปีที่แล้ว

    Maraming salamat pk, Ar. Jon! Sobrang helpful po nito para sa plate na ginagawa ko ngayon sa Building Utilities. 💗

    • @arkitekjon
      @arkitekjon  3 ปีที่แล้ว

      Thank you din 😊

  • @remilopingol709
    @remilopingol709 4 ปีที่แล้ว

    Arch. Jon Can you discuss din on your future vlog yun BIO DIGESTER and also RAIN WATER HARVESTING if that is practical in a regular residential project. I have a client who wants to incorporate that in her house which is my project now.

  • @fayea.3433
    @fayea.3433 3 ปีที่แล้ว

    Thank you Architect!

    • @arkitekjon
      @arkitekjon  3 ปีที่แล้ว

      thanks also for watching, Faye!

  • @vincefajardo7181
    @vincefajardo7181 3 ปีที่แล้ว

    salamat arkitek

  • @evelyndennis9199
    @evelyndennis9199 4 ปีที่แล้ว

    Thank you . I learn a lot . 👍👍👍😍

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      thanks dn sa panonood😊

  • @vivianroasa
    @vivianroasa 4 ปีที่แล้ว

    Very informative your vlog

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      thanks Vivian😊

  • @reyacebes692
    @reyacebes692 4 ปีที่แล้ว

    Salamat po hihi

  • @mjrosete4842
    @mjrosete4842 3 ปีที่แล้ว

    Very informative details. Re: of rowhouse 3 units, ano po ang standard dimension ng septic tank although hindi fixed ang nos.of tenant in periods of time.

  • @pithecophagajefferyi7460
    @pithecophagajefferyi7460 2 ปีที่แล้ว +1

    *Settling Chamber na po ang tawag, Arkitek. Bawal po mag leach, dapat water tight

  • @MrThevegaTV
    @MrThevegaTV 4 ปีที่แล้ว

    shout out boss next mo gagawin

  • @roseannborja3815
    @roseannborja3815 2 ปีที่แล้ว +1

    Thank you sir! Ask ko lang po, is it possible to create a 3-chamber septic tank using the RNPCP? Or by applying the 2/3 digestive and 1/3 leaching? Thank you for responding sir :)

  • @taengoo4263
    @taengoo4263 2 ปีที่แล้ว

    Thank you for such an informative video Ar. Jon! Can I ask a question, I tried to compute the septic tank dimensions for a house with 1 or 2 bedrooms and I got 1.50 x 0.90 x 2.10 M (length). The digestive chamber is 1.4 m and leaching is 0.70 m. Is the dimension enough or is it too small? And is a 500x500 mm manhole suitable for this dimension? Thank you Ar.!

  • @motoadvntour2627
    @motoadvntour2627 4 ปีที่แล้ว

    Sir bka pwede i-consider sa leaching chambers yun space for plastering/water proofing purposes kung CHB ang gamit kasi sa 0.50m parang masikip trabahuin nun.

  • @altheaalejo5702
    @altheaalejo5702 4 ปีที่แล้ว +1

    Very reliable. Mukang kapag sa kanya ka nagpagawa Ng house plan di ka dadayain. Sana one day makapagpagawa ako house plan Kay Sir. 😊

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      tenchu😊 keep safe

  • @pithecophagajefferyi7460
    @pithecophagajefferyi7460 2 ปีที่แล้ว

    Hi, in sign and seal only service, do you charge additional fee kung may errors ka na nakita at pinacorrect mo sa designer? Thank you

  • @144Tropical
    @144Tropical 4 ปีที่แล้ว

    Architect Jon, Please feature a container van home, how-to, styles, costs, advantages and disadvantages. thks

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      hopefully may maifeature tau na kgaya ng request mo😊

  • @ramhaelespaldon3674
    @ramhaelespaldon3674 3 ปีที่แล้ว

    Arki jon mag gawa kanaman ng capculation about sa roof drain pls para sa mga aspirant na master plubmer at mag tatake ng master plubmer.. tyaka topic anu dapat aralin sa master plubmer takers.. ehehehehe anu ba dapat aralin namin sa arithmetic ar??

  • @cherylguray2583
    @cherylguray2583 3 ปีที่แล้ว

    Thank you sa information...oo nga same sa plan ko wala na nakalagay ang estimate ng septic tank."

  • @nicosfilestravelandwhatsoe7251
    @nicosfilestravelandwhatsoe7251 3 ปีที่แล้ว

    salamat sa edukasyun arkitek.

    • @arkitekjon
      @arkitekjon  3 ปีที่แล้ว

      salamat dn sa panonood!

    • @nicosfilestravelandwhatsoe7251
      @nicosfilestravelandwhatsoe7251 3 ปีที่แล้ว

      @@arkitekjon isa po akong freelance draftsman sir. my mga tanong po sana ako tunkol sa plumbing. kasi yung latest plan na ginawa ko sa plumbing is binalik. d daw po acceptable kasi my kulang.
      flom iloilo po

  • @raymundohombria9649
    @raymundohombria9649 3 ปีที่แล้ว

    Sir ar Jon about sa sludge, dipo ba ma kapuno sa digestive tank?

  • @nishr.8706
    @nishr.8706 ปีที่แล้ว

    arch question yung background music mo po may nag aappear na heart2 sa likod mo po. bat po ganun?

  • @rogue66v
    @rogue66v 2 ปีที่แล้ว

    Sa last leaching chamber po ba dun natin lalagyan ng outlet pipepa discharge sa sewer?

  • @yahwehdecano1838
    @yahwehdecano1838 4 ปีที่แล้ว +1

    pano po ba sir jon kumuha ng master plumbing exam, even newly grad in architecture program ba pwede na may take neto?

  • @jaysonmaleek131
    @jaysonmaleek131 3 ปีที่แล้ว

    ano pong law yung nagsasabing 3 compartment dapat yung septic tank sir?

  • @davedagatan320
    @davedagatan320 3 ปีที่แล้ว +1

    Thank you po nagamit ko siya sa reporting ko for septic tanks. hehehehe

  • @marcosalandanan4646
    @marcosalandanan4646 4 ปีที่แล้ว +1

    arki..paano po gngawa ung flat na wall sa labas ng bahay ung hnd kita ang poste.salamat

  • @ilovekat8407
    @ilovekat8407 3 ปีที่แล้ว +1

    TRUE! Actually noong 2nd yr kami, yung plate namin sa Plumbing kinopya namin sa blackboard HAHAHAHA, kaya nandito ako btw thank you Ar. Jon💕.

  • @iamluckystarmiraquel2102
    @iamluckystarmiraquel2102 3 ปีที่แล้ว

    Gud pm. Sir ask ko lng po malaki po ba ang septic tank na 3mx6mx2m(lalim) for 2 storey house with 4 cr/ and 10 persons living in the house?

  • @TheAndre2408
    @TheAndre2408 3 ปีที่แล้ว

    Arki Jon, I hope you could reply on my query coz' this puzzled me a lot. You mentioned na hindi pwede isama ang waste water from the kitchen and bathroom, Q1 saan mapupunta ang waste water na galing sa kitchen and bathroom kung walang public canal na pagconektahan? Q2 kailangan ko ba gumawa ng pangalawang tanke (waste water tank) for the sole purpose of catching kitchen and bathroom water so as not to disrupt the function of aerobic and anaerobic bacteria sa regular septic tank ko? Salamat and GOD Bless!!!!! more power to your vlog!!!!!

  • @ayamason
    @ayamason 2 ปีที่แล้ว

    Sir as per RNPC ang minimum volume to consider is 2cu.m so kahit 0.85cu.m nakuha mo po dapat ung minimum pa din gamitin mong volume which is 2cu.m instead of 0.85 as per RNPC po iyan Sir.

  • @stripehearts
    @stripehearts 4 ปีที่แล้ว +1

    arki, suggestion lang po, next time screen record mo yung sketching mo pra masundan ka namin 😁 thank you! nakining tlga ako hehehhe papagawa kami bhay eh

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      noted sa suggestion bro. thanks😊

  • @jjl3776
    @jjl3776 ปีที่แล้ว

    sir practical pa rin po ba ang septic tank sa mixed-use building, especially for 1000 persons? thank you po sa pagsagot

  • @JonahRuthMPeria
    @JonahRuthMPeria ปีที่แล้ว

    Hello po, thank you so much po sa info... ask ko lang po, pano po kung hindi nagawa yung 0.3 m na air gap? pls, answer po kasi nagpapagawa poko atm..pls pls

  • @rufinojosesiapno420
    @rufinojosesiapno420 3 ปีที่แล้ว

    Ibig sabihin sir... Mag allot tayo ng 0.28 cubic meter per person. Tama po ba sir?

  • @Leelee-rm5gu
    @Leelee-rm5gu ปีที่แล้ว

    Sir pano po .30 air space hindi po ba kasali depth na 1.20 or add .30.

  • @gehrypajarillo5855
    @gehrypajarillo5855 3 ปีที่แล้ว

    kitek john sir mas mgnda po sna kng ibabase n ntn yng capacity ng septic tank for residential and aprtments sa RA1378 pages 200 ayun dun sa 1 or 2 bedroom nsa 750 gals agd yng capacity at kpg 3 bedrooms consdidered 1k gals na thn yng digestive chamber ntn always 2/3 nung total capacity at 1/3 nmn yng leaching chamber at yng additional leaching chamber po ay base n sa LGU kng ppglgyan ng additional chamber.TY

  • @tvchannel3248
    @tvchannel3248 4 ปีที่แล้ว

    new sub sir salamat sa kaalaman

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      thanks for watching😊

  • @keithferryaguilar630
    @keithferryaguilar630 2 ปีที่แล้ว

    Good day po! Saan po pwede kumuha ng mga given data?

  • @tapisyu6938
    @tapisyu6938 3 ปีที่แล้ว

    Kung nakakatulong both anaerobic at aerobic, why not Length = Total Volume / Width x (1.20m anaerobic + .30m aerobic) ? All in all - nice vlog po.

  • @melodymanicdo5396
    @melodymanicdo5396 3 ปีที่แล้ว

    Saan po galing yung 1.125+0.75?

  • @johnlewis3686
    @johnlewis3686 4 ปีที่แล้ว

    salamat po architect, may tanong po ako, may nabasa po kase ako na dapat hindi dumiretso sa septic tank ung shower and laundry liquid waste since may mga sabon sya or chemical na pweding pumatay sa natural bacteria ng septic tank. so san po dapat mapunta ung waste na yun architect. salamat po sa sagot. solid viewer nyo po ako.

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      correct...usually sa drainage na drecho ung waste water galing sa shower at laundry.

  • @jobelgerard
    @jobelgerard 3 ปีที่แล้ว

    Hi ark. We are currently building our house and noticed our septic tank is behind the house and near the foundation. Is ok to be that way? Thanks

    • @arkitekjon
      @arkitekjon  3 ปีที่แล้ว +1

      Hello. Ok lang nmn as long as it is properly made, observing the minimum standards of Sanitation. Ang reason ng iba bkt mas mlapit sa harap o kalsada is that para mas accessible kung mgpapa-sipsip sila incase.

    • @jobelgerard
      @jobelgerard 3 ปีที่แล้ว

      @@arkitekjon thank you very much for this ark. Very helpful po. Vlog request: what to check during construction phase for clients/owners. We do not have any background on engineering po kc so we do not know what to look for if we visit the site. Thank u

    • @arkitekjon
      @arkitekjon  3 ปีที่แล้ว

      @@jobelgerard it helps to be well-versed dun sa plano ng bahay nyo and sa different phases ng Construction para masundab nyo. But normally, the Design Architect should be the one doing the Site Visits from time to time assisting you sa Technical side. Kaya lagi ko cnsabi na mas ideal ang set-up na Hindi dapat "inclusive" ang Design sa Contractor kc walang check and balance.

  • @reynaldonuguidjr.1124
    @reynaldonuguidjr.1124 7 หลายเดือนก่อน

    75 gallons masyadong malaki po. baka 75 liters per day lang as per RNPCP Table B-3.

  • @mr.g2360
    @mr.g2360 4 ปีที่แล้ว

    2:40 Relate much. Arki student here

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      thanks for viewing...keep grinding, future Architect! 😊

  • @starain8511
    @starain8511 2 ปีที่แล้ว

    Hello po sir Architect may tanung po sana ako.
    Sa computation ko po kasi 35 persons x 75 gallons = 2,625 gallons
    1.125 + .075 ( 2,625 ) = 1,969.875 gallons
    1.969.875 gallons x 1 cu.m/ 264 gallons = 7.46 or 7.5 cu.m
    Yung depth po ng aking tubig =1.5 m
    Yung Width po = 2m
    Yung Length po = 2.5m
    Total po 1.5m x 2m x 2.5m = 7.5 cu.m
    Kung kalahati po ng aking digestive = 2.5m / 2 = 1.25m
    1.25m x 2 dahil dalawa po aking leaching = 2.5m
    Total inside length po ng aking septic = 5meters, Width = 2 meters
    Okay lang po ba yung size o masyadong malaki ang aking septic tank para sa 35 persons?
    Salamat po

  • @donmanigos1942
    @donmanigos1942 4 ปีที่แล้ว +1

    Hello architect, subscriber here , ok lang ba na wala nang bottom slab ang isang septic tank? May na.experience kasi ako na hindi na nagbuhos for bottom slab, gravel nalang ang inilagay.

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      hello Don, 3-Chambers kc ang Septic Tank...ung 2-Chambers may bottom slab tlg hnd yan pwd ipa-sip lang sa lupa. pls refer sa plano ng isng Master Plumber.

  • @tyronehayato1910
    @tyronehayato1910 3 ปีที่แล้ว

    Yung pina check sakin na septic tank. Anlaki ng dimension. 4 lang din sila na nakatira.

  • @remilopingol709
    @remilopingol709 4 ปีที่แล้ว

    Yung tatlong chamber, the other two will be leaching chambers, what is the difference between the leaching chambers na open sa ground from the one you showed na meron slab like the digestive chamber? Hindi na ba allowed yun dalawang chamber lang like the what we use to have? Thank you and more power.

    • @ryanmartinez1007
      @ryanmartinez1007 3 ปีที่แล้ว

      Leaching should not be contaminated . LC +DC is equal to septic vault...septic is watertight ...you need to install distribution Box 1.5 m away from the septic

  • @ramhaelespaldon3674
    @ramhaelespaldon3674 4 ปีที่แล้ว

    Ar. Question lang alam ko subra calculation ng design mo considered na pwedi yang design mo peru usapang sa plumbing codes tayu if sabi half of the digestive ang leaching eh cguro subra tayu 2m consider natin partation wall 2.15 ba ang exact dimention tyaka another question yong dimention ba sa digestive chamber yong 1m is inner dimention po ba or outer??

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว +2

      yes...good point. nasabi na sa atin ng isa sa ngcomment hnd ko naisama ang thickness ng septic partition. altho hnd naman magiging malaki ang difference kc ni-round off din natin😊

  • @charlielorenzo3644
    @charlielorenzo3644 4 ปีที่แล้ว +1

    Plumber din pala kayo?

  • @mariacristinasoriano8774
    @mariacristinasoriano8774 4 ปีที่แล้ว +1

    Hi Architect Jon. Saan dapat po ba ipatayo ang septic tank? May say ba ang neighbour mo kung saan dapat ipatayo?

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      wala nmn say ang kapitbahay mo kng saan ilalagay, as long as hnd detrimental sa knila na hnd mangamoy, etc xiempre for good relationship.

  • @alpheyus
    @alpheyus 3 ปีที่แล้ว

    Arkitek, Pwede ba ipasok sa loob ng banyo un portion ng septic tank if masikip un lote.

    • @arkitekjon
      @arkitekjon  3 ปีที่แล้ว +1

      pwdng sa harap ng bahay, sa parking o sa likod wag sa loob.

  • @MBihon2000
    @MBihon2000 4 ปีที่แล้ว +1

    Hanggang ngayon ba may septic tank pa rin ang metro Manila area houses?

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว +1

      yes po...majority meron pa dn. but in upscale subdivisions like wala na. Sewer lines nila drecho na sa central treatment plant.

  • @avamariecarlon7570
    @avamariecarlon7570 3 ปีที่แล้ว

    Sir Jon my Facebook page kaba? Papagawa kc ako ng septic tank next month good for two toilets yun saka 8 persons gagamit wala akung idea.
    Slamat

  • @gabrieldy6848
    @gabrieldy6848 4 ปีที่แล้ว +2

    Hi sir yung discharge na namention is bathroom lang po ba di na kasama yung sa kusina? Another question sa pagkuha po ba ng permit kailangan ng drainage kung sakali hindi kasama sa discharge yung other household discharge like sa kusina at laundry? Sa case ko po kase yung lot namin sa province walang drainage canal kasi medyo bukid sya. Thanks

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว +1

      yes Gabriel. kasama ang Kitchen at Laundry sa plumbing systems...ang iniiwasan lang sa mga canals especially open canals ay maaring mksama sa kalusugan ng tao or sa kalikasan😊

    • @gabrieldy6848
      @gabrieldy6848 4 ปีที่แล้ว

      @@arkitekjon thank you sa reply sir. Last question sir, masama ba or detrimental ba sa poste o pundasyon ng bahay kung katabi ng septic tank yung isang poste? Given din na 2 story building?

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      hnd nmn, as long as hnd maapektuhan ung lapad, lalim at dami ng bakal ng mga pundasyon mo...

  • @marifepascualsison
    @marifepascualsison 3 ปีที่แล้ว

    Thank you Sir ! Paano po malalaman nacopy paste yung plano ng bahay po

    • @arkitekjon
      @arkitekjon  3 ปีที่แล้ว +1

      pag hindi swak sa Lot, orientation at specific needs or lifestyle mo.

  • @aranwaldartana1537
    @aranwaldartana1537 3 ปีที่แล้ว

    Ang galing ng pagkakaexplain sir. Ask ko lang sir kung pwede lagay septic tank sa garage. Salamatt sir

    • @arkitekjon
      @arkitekjon  3 ปีที่แล้ว +1

      yes pwd naman...make sure lang na matibay ang ibabaw dahil mabigat ang sasakyan

    • @aranwaldartana1537
      @aranwaldartana1537 3 ปีที่แล้ว

      @@arkitekjon Salamat po mabuhay kayo sir ✨☺

  • @jeeps1509
    @jeeps1509 4 ปีที่แล้ว

    Archi J ... pag gngawa n ang bahay...sino ang nag c check n tama ang gawa ng construction above the architect ?? kasi minsan mayga ibang archi dyan n s d rin ma ayos ang trabaho... gaya din ng mga ibang profesyonal ???

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว +1

      it helps kung meron na 3rd party professional kgya ng Project Manager. agree ako sayo...sadly meron prn iilang Arki na pasaway.

    • @jeeps1509
      @jeeps1509 4 ปีที่แล้ว

      @@arkitekjon ...thanks for d quick reply...mag ppgawa ako ng bahay and I am looking for an archi...bka pwde ka ??

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      sure...i'd love to 😊 u can reach me sa FB ko Jon Orteza. thanks

  • @ronaldvideo927
    @ronaldvideo927 3 ปีที่แล้ว

    Architect saan galing yung V=1.125 + 0.75(no. of gal) ? Anong source mo dun?

  • @michaelnabus9126
    @michaelnabus9126 4 ปีที่แล้ว

    Hi sir.ask ko lng kung total length na po b ung 2m?or total inside dimensions?or add nlng ung thickness ng CHB?and ung sa computation po b ng volume regardless po b sa laki ng lote or structure?kung couple lng sila hlmbwa then malaki ung bahay,still gnyan prin po b ung recommended size?thank you sir sa pag sagot.more educational videos pa po.

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว +1

      hello michael. yes hnd ko naoverlook ko ung chb thickness pero minor difference nlng nmn. ung computation ay based sa number of occupants.

    • @michaelnabus9126
      @michaelnabus9126 4 ปีที่แล้ว

      @@arkitekjon okay sir!mrming slmat po

  • @enriquemoreno3287
    @enriquemoreno3287 4 ปีที่แล้ว +1

    Ask ko lang po kung 5 door apartment tama po ba ang dimensions ko na L 2.50 x W1.50 mts. Digestive chamber thanks po new sub po ako

    • @gehrypajarillo5855
      @gehrypajarillo5855 3 ปีที่แล้ว

      sir gud day as per RA 1378 National Plumbing Code of the Phils sa 5 unit apartment nsa 2250gals po yng discharge so as per sa diniscuss ni kitek mkkuha n po yng sukat nun ngvvaries nlng po yun sa liquid depth bsta ang min. 0.60m nor more than 1.8m.Thank you by the way yng disgestive chamber is 2/3 sa total capacity ng septic tank.

  • @corazonquinn8007
    @corazonquinn8007 3 ปีที่แล้ว

    Panu po s probinsya s bukid po. Apply din po gnyan system. Wl nmn po dun sewage n tulad s ciy

    • @arkitekjon
      @arkitekjon  3 ปีที่แล้ว +1

      it would be good na maapply prn. to safeguard health and environment

  • @dannydeguzman4620
    @dannydeguzman4620 2 ปีที่แล้ว

    Sir, nag susupervise ba o bini visit din natin ang ating mga pinipirmahang mga plans, if ever po, meron po bang charges?

    • @arkitekjon
      @arkitekjon  2 ปีที่แล้ว

      yes, dapat to make sure na masusunod ang plano...but of course depende sa contract nyo kng ilan ang limit ng periodic visits mo. in excess of that, may charge na.

    • @dannydeguzman4620
      @dannydeguzman4620 2 ปีที่แล้ว

      @@arkitekjon paano po kung yung project ay nasa probinsya, paano po ang arrangement sa supervision/visit?

  • @manyanita3682
    @manyanita3682 4 ปีที่แล้ว

    Yung dimensions mo sir is for clear span? Not considering po nung thickness ng wall/chb's

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      yes bro clear span😊

    • @manyanita3682
      @manyanita3682 4 ปีที่แล้ว

      @@arkitekjon copy sir, thank you sa information. Nag subscribe na ako :)

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      thank you dn po sa panonood😊

    • @manyanita3682
      @manyanita3682 4 ปีที่แล้ว

      @@arkitekjon so hindi pala 2mx1m yung dimensions sir. Considering thickness ng walls

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      oo nga pla...thanks for pointing that out. altho halos di nmn na gnun kalaki ang magiging epekto. 😊

  • @aquahabitatdivesafaritours4540
    @aquahabitatdivesafaritours4540 4 ปีที่แล้ว

    Thank u again Arketik Jon malinaw talaga ang turo mo. Pero marami pa sana ako katanungan tungkol dyn. Pero di bale kung may budget na ska tyo magusap. Please send your contact details. Para d2 sa Coron ang plano ko. Thanks

  • @motogoodboy
    @motogoodboy 4 ปีที่แล้ว

    Arkitek ano naman po yung basic formula sa computation sa tiles ? Ft inch and meters. Thanks po arkitek

    • @juanmiguelgutierrez3896
      @juanmiguelgutierrez3896 4 ปีที่แล้ว +1

      Total floor area divided by size ng tiles plus 5 or 10 % wastages

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      thanks for answering for me, Juan Miguel 😊

    • @motogoodboy
      @motogoodboy 4 ปีที่แล้ว

      Thank you so much po.

  • @narsingkopo8267
    @narsingkopo8267 4 ปีที่แล้ว

    paano kung di ka naka tap sa public sewage or imburnal ,saan mapupunta ang treated wastewater ? kailangan ba gumawa ng septic pit para ma absorb?? very informative video many thanks

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว +1

      Hello Michael, kng kagaya dito sa atin sa provinces na wlng public sewage system pwd na maliit lang na Septic Pit since treated nrn naman ang tubig na lalabas. altho not safe for human consumption prn of course but not as harmful na sa tao at environment😊

    • @ardiefepadua4416
      @ardiefepadua4416 4 ปีที่แล้ว +1

      arkitek JON hello... Gaga Saan ka architect? Batak ko mgpa gawa ng bahay soon...planning to get ur service >Sana Hindi masyadong mahal:haha

    • @ardiefepadua4416
      @ardiefepadua4416 4 ปีที่แล้ว

      Taga saan ka?

    • @ardiefepadua4416
      @ardiefepadua4416 4 ปีที่แล้ว

      *

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      hahaha. nagulat ako sa Gaga. anyway im based in Pasig😁

  • @marilynpatajo9825
    @marilynpatajo9825 4 ปีที่แล้ว

    Sinesemento po ba ang floor ng septic tank

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      ay opo...dapat watertight yan to avoid contaminating our environment. mkakaapekto po kc sa ating kalusugan😊

  • @lyka3221
    @lyka3221 4 ปีที่แล้ว

    Sir sabi niyo po V=1.125 + 0.75 ( 300 gallons )= 226.13? Tama po ba? Cinaculate ko po kasi ang total answer po is 562.5 gallons po

  • @whitelady09
    @whitelady09 4 ปีที่แล้ว

    ,aster plumber din ka pala . Di mo naman Sinabi CHAROT ! Pinapanood ko palang ngayon kc.

  • @remilopingol709
    @remilopingol709 4 ปีที่แล้ว

    Hindi na ba allowed yun dalawang chambers lang?

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      yes po...hnd na allowed ngaun ang 2-chambers lang

    • @ryanmartinez1007
      @ryanmartinez1007 3 ปีที่แล้ว

      @@arkitekjon 3 chambers ? In what sections or article under R.A 1378 ?

  • @Resicases
    @Resicases 3 ปีที่แล้ว

    muka ka po mabaet san po kayo sana pede magpagawa ng haus plan

    • @arkitekjon
      @arkitekjon  3 ปีที่แล้ว +1

      hehe. salamat po.😊

  • @viewpoints8797
    @viewpoints8797 4 ปีที่แล้ว +1

    Walang extra lol? Paano po kung nagawa mo na ang septic for 4 tapos may bisita at titira na so dagdag sila.

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว +1

      meron ni-round off q nga db. saka depende kng ilang years titira ang mga bisita mo e di kailangan nga mas malaki😁

  • @tessmartinez9446
    @tessmartinez9446 3 ปีที่แล้ว

    Sinisementado ba po ang flooring ng septic tank?

    • @arkitekjon
      @arkitekjon  3 ปีที่แล้ว +1

      yes po...pls consult a Masterplumber for proper Septic Installation😊

    • @jasperosbual4310
      @jasperosbual4310 3 ปีที่แล้ว

      @@arkitekjon papaano kapag provincial area gaya sa lilipatan kong tirahan. usually open ang ilalim o walang flooring ang kadalasang ginagawa nila. ano po ba magandang tip na pwede kong mahingi sa iyo? bagong subscriber lang po ako salamat po.

  • @henryalaron
    @henryalaron 4 ปีที่แล้ว

    New subscriber po sir jon sa pasig din ako plano ko po magpagawa ng bahay kaso nagiipon pa ako pwedi poba kyo ang konin ko

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      pwd naman po😊 pls PM to my FB - arkitek JON...thanks

  • @marzyoutubechannel9563
    @marzyoutubechannel9563 3 ปีที่แล้ว

    Sir pwede b maglagay ng septic tank sa loob ng bahay

    • @arkitekjon
      @arkitekjon  3 ปีที่แล้ว

      pwd naman. but much better kng sa mga service areas mo ilagay. wag sa living or dining areas kc dpat may manhole ka, dyahe kung bubuksan mo ung manhole nasa Dining Area😊

    • @marzyoutubechannel9563
      @marzyoutubechannel9563 3 ปีที่แล้ว

      @@arkitekjon sir hindi b pwede lagyan ko n lang ng access n tubo sa labas ?para hindi n ako maglagay ng manhole? Ano b yung advantage ng may manhole,salamat po

  • @kurtandrewjokicobul-lalaya6056
    @kurtandrewjokicobul-lalaya6056 3 ปีที่แล้ว

    😂😂🤣🤣🤣🤣

  • @mayouguimba2382
    @mayouguimba2382 4 ปีที่แล้ว

    B0ss id0l tan0ng k0 lng ung 1.125pluz 0.75 V yan ba f0rmula kung gst0 m0 tuklasin kung ilan cubic na tubig ang magagamit m0 thank u

    • @arkitekjon
      @arkitekjon  4 ปีที่แล้ว

      hello, yes ung volume na kakasya sa assumed total discharge ng mga nakatira😊

    • @mayouguimba2382
      @mayouguimba2382 4 ปีที่แล้ว

      @@arkitekjon 0k salamat b0ss id0l atleast may idea na ak0 thank u p0

  • @eulosuarez3666
    @eulosuarez3666 3 ปีที่แล้ว

    arkitek paano nakuha ang 226.13 galons kasi 1.125+0.75x300 =562.5 galons. pls reply po