How to DESIGN and COMPUTE a SEPTIC TANK | Revised National Plumbing Code PH |Quick Tips

แชร์
ฝัง
  • เผยแพร่เมื่อ 14 มี.ค. 2020
  • This video tells you on how to properly design a septic tank in a residential project. No to copy paste septic tank details. Learn the needed volume and right dimensions for your future reference.
    TAKE NOTE : In septic tanks having over 6 cum capacity, the secondary compartment should be not less than 1.5 m in length.
    While there are listed design considerations that are not tackled like pipe size,slope,distance of pipe etc. This is just a preview of a septic design for size configuration. I will a make video for the right technical specs and considerations. Thanks!

ความคิดเห็น • 152

  • @danieldemayo2303
    @danieldemayo2303 3 ปีที่แล้ว

    Really love the educational content of your vlogs!

  • @ericputian975
    @ericputian975 15 วันที่ผ่านมา

    New subs here archi... im a former site supervisor ng mga hgh end houses...

  • @christinedevera4267
    @christinedevera4267 3 ปีที่แล้ว

    Thank you, Ar. sobrang helpful po para sa plate namin sa Building Utilities 🤗

  • @rainsselsadie5564
    @rainsselsadie5564 4 ปีที่แล้ว

    Thank you sir ! Keep posting!

  • @landodeniega3666
    @landodeniega3666 4 ปีที่แล้ว

    Ndi pa nagasisimula yung topic.. like na agad.. more power..!

  • @remilopingol709
    @remilopingol709 4 ปีที่แล้ว +4

    Most of our computations for plumbing are based on the books of FAJARDO and SALVAN since yan ang books natin noon sa college and I see meron pagkakaiba sa results when we use itong NATIONAL PLUMBING CODE. I am glad na sa computation ng Septic Tank You taught using NPC. Will you make other computations teachings like soil and waste pipes, storms and also vents using NPC. Thank you. I am also an Architect and RMP.

  • @bry.dionisiooooo
    @bry.dionisiooooo 3 ปีที่แล้ว

    Thank you po Ar. Miranda! from TUP-MNL po very informative po yung video niyo!

  • @peterisidro9237
    @peterisidro9237 2 ปีที่แล้ว

    Thanks Arch. Mabuhay ka po.😍

  • @melvinquidong6280
    @melvinquidong6280 4 ปีที่แล้ว +1

    May suggestion ako architect on your next tutorial about sana on computing schedule of loads for a residential building

  • @hydrogenperoxide9995
    @hydrogenperoxide9995 2 ปีที่แล้ว

    Laking tulong nito sir! Thanks!

  • @bartko8520
    @bartko8520 2 ปีที่แล้ว

    thanks, Architect John!

  • @taengoo4263
    @taengoo4263 2 ปีที่แล้ว +3

    Good day Ar.! Thank you for such an informative video. Question, I tried to compute the septic tank dimensions for a house with 1 or 2 bedrooms and I got 1.50 x 0.90 x 2.10 M (length). The digestive chamber is 1.4 m and leaching is 0.70 m. Is the dimension enough or is it too small? And is a 500x500 mm manhole suitable for this dimension? Thank you!

  • @kimdelrosario9227
    @kimdelrosario9227 2 ปีที่แล้ว

    Hi. thanks for this informative video! I just want to ask if there is a required minimum dimension for leaching chambers. can we build a leaching chamber that is less than 0.9M in width?

  • @hallelujahelohim289
    @hallelujahelohim289 3 ปีที่แล้ว

    hi.
    I have land and im putting a house
    I need a well and a septic"
    The land is packed clay and water doesnt drain well
    Do you make a leech field so I dont have to always pump the tank?
    How can I keep the septic - and the, "leech field," from contaminating the well?
    How can I find how well the septic will drain on my land, and how far away the septic has to be from the well ?

  • @mikemike4789
    @mikemike4789 3 ปีที่แล้ว

    more plumbing videos please.. thanks

  • @melanielayos
    @melanielayos 2 ปีที่แล้ว

    thank you po for this!

  • @christianperez8603
    @christianperez8603 4 ปีที่แล้ว

    Thank you po Architect.

  • @arvinlubugan481
    @arvinlubugan481 4 ปีที่แล้ว

    Thanks Architect.

  • @christianagravante9745
    @christianagravante9745 3 ปีที่แล้ว +1

    Hi sir. New subscriber mo po ako. Sana gawa po kayo ng tutorial kung papaano mag compute ng SIZE OF GUTTER na gagamitin sa roof. Yung depth and width po ng gutter. Thanks. 👍

  • @Rukawapun
    @Rukawapun 2 ปีที่แล้ว

    Relate po dun sa "Hindi lang kinacopy paste sa AutoCAD" HAHAHA pero lesson learned

  • @juanball5480
    @juanball5480 3 ปีที่แล้ว

    Nice tutorial

  • @lerrybaltar1653
    @lerrybaltar1653 4 ปีที่แล้ว

    Hi sir, paano po magadd ng new line kung gamit po namin ay anaerobic septic tank? Bubutas po ba kami sa mismong tank or magkabit po kami ng T pvc? Thanks!

  • @pandaypira4346
    @pandaypira4346 3 ปีที่แล้ว

    Nice content.. sir tip lng sana next time yung mga illustrations or table n papakita mo lakihan sana.. di mkita yung mga values.. d kc lhat may book sir.. thank you. GODbless

  • @JB-vy5cc
    @JB-vy5cc 3 ปีที่แล้ว +2

    What happens to the effluent from the septic tank? Does it eventually reach a treatment facility like it’s supposed to or does it drain into a street canal that eventually goes to an estero or river and eventually to Manila bay?

    • @Rawhousearchitects
      @Rawhousearchitects  3 ปีที่แล้ว +1

      It should go to main public or private sewarage system. It should not go directly to canals,estero, river. Unless its a storm water

  • @riccipaulinecuasito2734
    @riccipaulinecuasito2734 4 ปีที่แล้ว +5

    May suggestion lang po ako Architect. Puede po ba kayong gumawa nang vlog on how to compute water tank for commercial buildings with 4 unit apartments on its 2nd level po? Please

    • @Rawhousearchitects
      @Rawhousearchitects  4 ปีที่แล้ว

      Ill do, computation ng water tank volume :) watch out

    • @angelicaaclan384
      @angelicaaclan384 4 ปีที่แล้ว +1

      @@Rawhousearchitects hi po baka po pwede po gumawa kayo ng video for pump selection. and ratings nya,

  • @vanessajade419
    @vanessajade419 4 ปีที่แล้ว

    Thank you po Architect

  • @MikeTuason
    @MikeTuason 3 ปีที่แล้ว

    May video na ba yong kung saan lalagay mga pipings sa loob ng septic tank? ie, inlet pipe, outlet atbp. Thanks.

  • @arthurazataer1827
    @arthurazataer1827 4 ปีที่แล้ว

    Idol pwede ka gawa ng video regarding inlet and outlet measurements and the pipe dimensions...tanx idol

  • @anthonydale3660
    @anthonydale3660 3 ปีที่แล้ว

    thanks sa clarifications po, tanong ko lang po, yung 3 bedrooms po ba recommended per how many persons? at ilan po idadagdag per person po kung sakali? thank you po

  • @tranquilsoul411
    @tranquilsoul411 2 ปีที่แล้ว

    this would be agreat help tip

  • @noorrojas2006
    @noorrojas2006 3 ปีที่แล้ว +1

    Suggested to Show in drawing (layout) and computation.

  • @jasmindizon
    @jasmindizon 2 ปีที่แล้ว

    Salamat po Sir

  • @miraflorrodriguez8728
    @miraflorrodriguez8728 2 ปีที่แล้ว

    Architect our design of septic tank is this..
    Depth 1.5m
    Length 2.2m
    Width 1.5m
    Our design has 4bedrooms with 3 full cr.
    Is the septic tank size right?

  • @xianwhite5538
    @xianwhite5538 2 ปีที่แล้ว

    rEQUEST PO ako Ar. Kung Paanu ka Mag Compute ng Electrical at Plumbing baka meron ka pong Diskarte na mas mabilisan

  • @ryanestrada8486
    @ryanestrada8486 3 ปีที่แล้ว

    sir ok lng po ba yung septic tank eh nasa ilalim mismo ng comfort room?

  • @johnlewis3686
    @johnlewis3686 4 ปีที่แล้ว

    salamat po architect, may tanong po ako, may nabasa po kase ako na dapat hindi dumiretso sa septic tank ung shower and laundry liquid waste since may mga sabon sya or chemical na pweding pumatay sa natural bacteria ng septic tank. so san po dapat mapunta ung waste na yun architect. salamat po sa sagot. solid viewer nyo po ako.

  • @enricolingo1977
    @enricolingo1977 4 ปีที่แล้ว

    sir bigay ka idea mag kano costing ng balcony ng 2nd floor.

  • @foreverlovehijau4428
    @foreverlovehijau4428 3 ปีที่แล้ว

    Sir,, ano po ang technique sa pag papagawa nang septic tank sa masikip na bahay. Ang plano po namin ilalagay namin ang septic tank sa gilid nang dingding nang bahay namin. Paano po yun sir, baka mag lick o baka,, ang tubig mag lick papunta sa kabila.

  • @janlawrencealberto2678
    @janlawrencealberto2678 3 ปีที่แล้ว

    Parequest po ng explanation pa ng ibang dimensions ng septic tank like baffle walls, height and diametet or pipes hehe

    • @Rawhousearchitects
      @Rawhousearchitects  3 ปีที่แล้ว +2

      Sige sir, add ako ng detailed septic tank descriptions with sizes

  • @gelowthin1728
    @gelowthin1728 4 ปีที่แล้ว +1

    Hi sir! Thank you po dito ! Sana meron po kayong Plumbing design methodology na maishare saming mga aspiring designer thanks!

  • @kennethsabangan6842
    @kennethsabangan6842 3 ปีที่แล้ว

    sir pwede makahiram ng sample niyo sa sanitary... 2 nd year arki po para lang sa assignment

  • @ramryanaumentado2771
    @ramryanaumentado2771 2 หลายเดือนก่อน

    meron po ba video pag estimate sa cistern tank?

  • @triisha_
    @triisha_ 4 ปีที่แล้ว +2

    are employees of a certain commercial establishment included in finding the width of the septic vault sir?

    • @Rawhousearchitects
      @Rawhousearchitects  4 ปีที่แล้ว +1

      Hi, septic vaults can only be used to residential projects, in a comml prject, you need na ng sanitary treatment plant, and the right professional to design that is a sanitary engineer :)

    • @Rawhousearchitects
      @Rawhousearchitects  4 ปีที่แล้ว

      The sv would be huge if that so haha, kaya stp is needed na for that, the problem is the problem lol,
      You must also consider grease interceptors for the development, anyways i hope i answered your question indirectly hehe 🙏

    • @triisha_
      @triisha_ 4 ปีที่แล้ว

      thankyou sir big help

  • @ramhaelespaldon3674
    @ramhaelespaldon3674 3 ปีที่แล้ว

    Gawa kanaman boss ng calculation sa pressure req calculation sa pipe etc..

  • @reggie7036
    @reggie7036 11 หลายเดือนก่อน

    Hello Architect. Hinahanap ko ksi sa channel ung estimates for cistern tank. Parang nawala ata sa list. Thanks po.

  • @sjb9627
    @sjb9627 ปีที่แล้ว

    Sir tanong ko lng.! Dapat ba sementado ang sahig ng septic tank? Salamat po sa sagot!

  • @remilopingol709
    @remilopingol709 4 ปีที่แล้ว +1

    Can you make a vlog on Rain water Harvesting and Biodigester and how to incorporate them to our Plumbing Design?

  • @rufinojosesiapno420
    @rufinojosesiapno420 4 ปีที่แล้ว

    Sir parang may mali po sa middle part. Yung Length value po ninyo... Bkit po naging cu. m. yung sagot?

  • @angelalacdao6336
    @angelalacdao6336 หลายเดือนก่อน

    Sir try nyo nga po sa 2500 gallons.. parang lalong lumiit yung sagot na nakuha ko? 😅 TIA

  • @giomel82
    @giomel82 3 ปีที่แล้ว

    ilang taon po mapupuno ang tangke?

  • @rickers2011
    @rickers2011 2 ปีที่แล้ว

    Sorry for this question but is it possible to install a septic tank above ground?

    • @Rawhousearchitects
      @Rawhousearchitects  2 ปีที่แล้ว

      Your problem.would be the standard slope of the pipe, 2% slope to fully drain waste and water

  • @ericaclavelgatcho1095
    @ericaclavelgatcho1095 3 ปีที่แล้ว

    Bakit po may mga structures na naglalagay ng septic tank sa ilalim nito?

  • @Godblessforeveryone
    @Godblessforeveryone 3 ปีที่แล้ว

    pano po ang sizing ng pipe? Salamat po.

  • @rosemalang7215
    @rosemalang7215 3 ปีที่แล้ว

    Ano ang size sa septic tank kong 4 bedroom sir

  • @hanrielvengarcia2675
    @hanrielvengarcia2675 2 ปีที่แล้ว

    Pag 1 room lang po paano po. 30sqm po ang bahay

  • @jimboyocoy1444
    @jimboyocoy1444 4 ปีที่แล้ว +2

    Hi Arch. Sa mga project ko ung kay Max Fajardo parin gngmit ko.. ok pba un? Thanks... -Jim UAP Qatar

    • @Rawhousearchitects
      @Rawhousearchitects  4 ปีที่แล้ว

      Hi sir Jim, depende din po kasi sa designer, si fajardo kasi is like an additional reference. Pero I opt to choose RNPC guidelines kasi dun din kinukuha yung fixture units when designing sanitary and waterline. hope it helps thanks!

    • @jimboyocoy1444
      @jimboyocoy1444 4 ปีที่แล้ว

      Ah ok sir.. baka may copy ka ng new RNPC? Pwd makahingi.. jimboy.ocoy89arki@gmail.com.. thanks

    • @Rawhousearchitects
      @Rawhousearchitects  4 ปีที่แล้ว +1

      @@jimboyocoy1444 www.academia.edu/29988840/Revised_National_Plumbing_Code_of_the_Philippines.pdf
      dian sir pwede mo sya madownload :)

  • @sonnyenriquez6779
    @sonnyenriquez6779 3 ปีที่แล้ว +1

    San ba dumadaan ang pvc pipe ng toilet bowl mula sa second floor...sa poste ba or sa wall?

  • @edwinalcantara2308
    @edwinalcantara2308 3 ปีที่แล้ว

    Thanks sir,ask ko lang if pag hukay ay may tubig n lumabas bgo mag baywang ang hukay?

    • @Rawhousearchitects
      @Rawhousearchitects  3 ปีที่แล้ว +1

      Pasipsip sa pump sir while constructing, water table na po kaya may tubig na, need din waterproofed ang septic vault

    • @edwinalcantara2308
      @edwinalcantara2308 3 ปีที่แล้ว +1

      Thanks arki,hoping someday bgo ko mp repair uli haus ko ay kita kits for some details(magulo kc eh)ty edwin fr bacoor cavite

  • @simply_pie
    @simply_pie 2 ปีที่แล้ว

    Hello po, thank you for this helpful info po. Ask ko lang if sa building code po ba required na 3-chamber ang septic para maapprove ang building permit? 2 bedroom, 40sqm house, NCR location. Salamat po sa sagot!

  • @herminioenricob.vicencio88
    @herminioenricob.vicencio88 3 ปีที่แล้ว

    Comment lang: Hindi parehas ung mga unit symbols sa computation kaya medyo nakakalito dapat kung kukuha ka ng length (m) = cu.m / (width (m) x depth (m)). Anyway, thank you very informative.

  • @PlsJoshua
    @PlsJoshua 4 หลายเดือนก่อน

    sa apartment and hospitals din po

  • @roseannborja3815
    @roseannborja3815 2 ปีที่แล้ว +1

    Good day po! Thank you for the helpful information Ar.! Ask ko lang po, how about pag 3 chambers naman po ang reqd. na i-design, applicable pa rin po ba yung 2/3 digestive and 1/3 leaching? If ganun po kasi sosobra na po sya sa nakuhang total length ng septic tank. How would you design po a 3 chamber STP if magbbase ka po sa Table B-2 of RNPC? Thank you po for responding :))

    • @Rawhousearchitects
      @Rawhousearchitects  2 ปีที่แล้ว +2

      Hi, add ka lang another 1/3 na nakuha mo

    • @roseannborja3815
      @roseannborja3815 2 ปีที่แล้ว +1

      @@Rawhousearchitects Oww, okay po, bale okay lang po kahit mag-exceed ka po sa nakuha mong total length ng septic tank?

    • @Rawhousearchitects
      @Rawhousearchitects  2 ปีที่แล้ว +2

      Yes Mam, pero you can seek sa DAO ng DENR, mas accurate po dun. Referal code lang kasi rnpc at medyo luma na

    • @roseannborja3815
      @roseannborja3815 2 ปีที่แล้ว +1

      @@Rawhousearchitects Okay po. Thank you so much po, Ar.! God bless po :))

  • @remilopingol709
    @remilopingol709 4 ปีที่แล้ว

    Bakit yung ibang leaching chamber walang floor slab katulad ng Digestive? Tama ba yun?

    • @Rawhousearchitects
      @Rawhousearchitects  4 ปีที่แล้ว +1

      Old practice but its not allowed since the soil can be contaminated po. Cocr. Slab is a must for all chambers sir :)

  • @1975blo
    @1975blo 4 ปีที่แล้ว

    Sir more power sa vlog mo. Ang tanong ko po, kapag magpapagawa po ba ng septic tank, kailangan pa ba ng permit sa munisipyo to install septic tank?

    • @Rawhousearchitects
      @Rawhousearchitects  4 ปีที่แล้ว

      Sanitary permit sir apply ka po ,need ng plumbing plans po

  • @samarayan35
    @samarayan35 4 ปีที่แล้ว

    Sir, ung rebars po ng septic tank, kinocompute nyo din po ba?

    • @Rawhousearchitects
      @Rawhousearchitects  4 ปีที่แล้ว

      Hello , may standard spacing and grade ang rebars ng septic tank na sinusunod, pero pag masyado ng malaki you can consult a strctural.engineer :)

  • @johnpaulmarcelino9076
    @johnpaulmarcelino9076 3 ปีที่แล้ว

    Sir need po ba buhos ang flooring ng setic tank?

  • @wotwot6868
    @wotwot6868 4 ปีที่แล้ว +1

    Sir paano ba ako makakahanap ng Architect na based sa probinsya? At paano ko ma-sisigurado na kasing galing ninyo?

    • @Rawhousearchitects
      @Rawhousearchitects  4 ปีที่แล้ว +1

      Hi Sir, all licensed architects are from UAP/PIA kaya guaranteed ka, just ask first his/her license no and you can verify it to PRC. Sa I ilocos ,I have one friend na taga dian though dito sya sa manila nagwowork.

  • @yamakayamada
    @yamakayamada 4 ปีที่แล้ว

    Hi sir question lang po sa 3 chambers pano sya iaadd? Example 3 meters ung length nia ngayon tapos magaadd pa ulit ng isa so magiging 4m ung length nia? O isisiksik lang din sa 3 meters? Salamat po

  • @sangivillaruz4487
    @sangivillaruz4487 4 ปีที่แล้ว

    Hi po, iam a 5th year student po tanong ko lang po if how about po sa power house po may computation din po bayun?. Kung how much po na genset ung kailangan in a project po. This video is so helpfull din po 😊

    • @Rawhousearchitects
      @Rawhousearchitects  4 ปีที่แล้ว

      Hi, sorry but Im not really familiar sa powerhouse load computation, i think you should ask for an Electrical Engr :) thanks!

  • @ebcmovies4071
    @ebcmovies4071 4 ปีที่แล้ว +1

    Di po ba 3 chambers na nirerequire maski sa residential septic tank?

    • @Rawhousearchitects
      @Rawhousearchitects  4 ปีที่แล้ว +2

      Yes, but in revised national plumbing code of ph, minimum is 2, you can add naman ung computed leaching chamber if needed sa specific municipality is 3 :)

    • @ebcmovies4071
      @ebcmovies4071 4 ปีที่แล้ว

      @@Rawhousearchitects noted sir. Thanks!

    • @engrpogs
      @engrpogs 4 ปีที่แล้ว

      May mga municipality lang po na ang requirement nila is 3chambers po 😐

  • @dhenziorolpu9026
    @dhenziorolpu9026 4 ปีที่แล้ว

    Boss pwd bang magtayo ng CR sa ibabaw ng septic tank?

    • @Rawhousearchitects
      @Rawhousearchitects  4 ปีที่แล้ว

      If the code will rule hindi po pwede, sa open space po dapat :)

    • @dhenziorolpu9026
      @dhenziorolpu9026 4 ปีที่แล้ว

      Raw House PH ano po kayang magiging problema pag sa ibabaw

  • @kenhollom1669
    @kenhollom1669 4 ปีที่แล้ว +1

    Why i not understand nothing his says

  • @ejlopena8088
    @ejlopena8088 2 ปีที่แล้ว

    Good day po! paano po mag design ng septic tank for dormitory po?

    • @ejlopena8088
      @ejlopena8088 2 ปีที่แล้ว

      additional question po hehe, kapag dormitory po yung project, are we still gonna use the "Liquid depth= minimum of .60 - 1.80" and "Width= minimum of .90"?

  • @tagalogforadultlearners
    @tagalogforadultlearners 3 ปีที่แล้ว

    Pwede ba tayuan ng bahay ang ibabaw ng septik tank?

  • @gddraftsman5617
    @gddraftsman5617 2 ปีที่แล้ว

    #1.22

  • @ryanriovaldez3185
    @ryanriovaldez3185 4 ปีที่แล้ว

    Revised family code yata pagkakarinig ko sa 1:28 😁

  • @introvertedsapiophile5255
    @introvertedsapiophile5255 4 ปีที่แล้ว

    Gawin mo 2/3+1/3+1/3. Mag lagay ka ng allowance. Yes di na advisable yung 2 chamber as per doh. And rncp need to be revised for almost 3 decades na yan di oa nagagalaw.

    • @Rawhousearchitects
      @Rawhousearchitects  4 ปีที่แล้ว

      Yes sir, so I advice mag add ng 1/3 additional if 3 chambers ang required :) as just stated as per the code po

  • @ClickMeTV15
    @ClickMeTV15 3 ปีที่แล้ว

    sir ask ko lng po..pwede po ba wla manhole yung septic tank..plumber po kasi sabi kasi foreman namin kht wla ndaw.at old design daw un..ok lng po ba yun?

    • @Rawhousearchitects
      @Rawhousearchitects  3 ปีที่แล้ว

      Hehe hindi po pwede, itll be an access for maintenance

    • @ClickMeTV15
      @ClickMeTV15 3 ปีที่แล้ว

      ok lng daw po kasi meron dw po tubo n nkalabas at wla nmn dw po npasok sa posonegro samin..kaya ok lng daw po

    • @Rawhousearchitects
      @Rawhousearchitects  3 ปีที่แล้ว

      It isnt, as a professional i suggest have a manhole, but its up to you sir. Sa sanitary compliance bagsak yan if legally done po

    • @ClickMeTV15
      @ClickMeTV15 3 ปีที่แล้ว

      yun nga po sir..mas gusto ko tlga may manhole kaso natapos na nila kya wla n po ako mgwa..ang cnsabi ksi dw dun pdw s manhole nagccmula sumingaw

    • @ClickMeTV15
      @ClickMeTV15 3 ปีที่แล้ว

      sige po sir slmat s advice..

  • @christinebacud5262
    @christinebacud5262 3 ปีที่แล้ว

    paano po nalalaman ung size ng manhole ?

  • @davidbuhay8380
    @davidbuhay8380 4 ปีที่แล้ว

    Sir, napansin ko lang po yun sabi nyo sa ( "....the depth of a septic tank has a minimum value of .6 M to 1.8 M.. for liquid depth chamber......." (Time slider : 3:00/6:59 Minutes)
    Ibig nyo po ba sabihin is allowable depth range yan na from .6 M- 1.8 M or can say from minimum .6 M to maximum 1.8m po? If so, hindi na po ba pwede umabot ng let say 2M ?,, Salamat po Sir (davidbuhay@yahoo.com)

    • @Rawhousearchitects
      @Rawhousearchitects  4 ปีที่แล้ว

      yes as per NPCP

    • @Rawhousearchitects
      @Rawhousearchitects  4 ปีที่แล้ว

      1.8m max , pag mas mataas pa dun, aerobic and anaerobic bacteria cant process throughly :)

  • @foreverlovehijau4428
    @foreverlovehijau4428 3 ปีที่แล้ว

    Sir,, ano po ang technique sa pag papagawa nang septic tank sa masikip na bahay. Ang plano po namin ilalagay namin ang septic tank sa gilid nang dingding nang bahay namin. Paano po yun sir, baka mag lick at ang tubig mag lick papunta sa kabila. Ang lugar po kasi nang paglagyan namin nang septic tank ay mataas. Ididikit namin ang septic tank sa dingding nang kabilang bahay namin para pong magka level lang ang septic tank sa kabilang bahay namin? Pwd po ba yun? At ano po ba sir ang strategy po sa ganung bahay? Baka mag lick at mapunta ang tubig sa kabilang bahay mula sa septic tank? Ano po ang dapat gawin sir.? Maaari niyo po ba akong bigyan nang payo?.

  • @emeritalelis9392
    @emeritalelis9392 4 ปีที่แล้ว

    relate ako copy paste 😅😅😅😅

  • @rolgom
    @rolgom 4 ปีที่แล้ว

    Your style is more like hosting, but should you consider showing most of your visuals? That way, your audience will be much more enlightened with what you are trying to explain. Thanks but no offense, I find it hard to understand your way of showing into pictures the things that you want to explain. Sorry, it’s just my suggestion.

  • @nav12G
    @nav12G 3 ปีที่แล้ว

    Im an architect alam natin yan..pero sa ENRO lalo na dito sa dumaguete iba.. eh dapat nakasUnod ka sa kanilang dimension.. minsan aabot panang 8.00 meters yong vault mismo..

    • @Rawhousearchitects
      @Rawhousearchitects  3 ปีที่แล้ว

      yup sir, local ordinances always governs naman , rnpc is referral lang

  • @rainsselsadie5564
    @rainsselsadie5564 4 ปีที่แล้ว

    Thank you sir ! Keep posting!