Thank for your sharing. Can I ask you one question? At 20:23, what happened if one CT of any feeder is in heavy saturation condition resulting secondary current of that CT is equal 0? Then Idiff=Istab and B point will change to C lie on Fault line. Which solution for this problem? Many thanks.
Very good content. Sir please make a practical video on Siemens busbar differential protection Relay by explaining the different settings options in it.
Thank you for your feedback. I will make video on Siemens Bus Bar Relay Configuration after completion of Bus Bar Protection theoretical sessions. Stay tuned for more updates.
Sir, Why slope of tripping characteristic is not having any slope during initial stage( at pick up current). At that time fault line comes below tripping characteristic.
Sir, I found a case of 400KV yard one and half breaker scheme, Present only tow dia of three are in service , In BCU Y phase tie bay of dia2 is showing zero ,other phase of same tie bay normal, and missing current shifted into Yphase of other tie bay of Dia 1 , What may be reason. request you to help to find out reason.
Mashallah. Please your all videos are very accurate 100% clear and informative
Thank you for watching. If you like the video then please share with your friends so that they may also refresh/understand these concepts.
Excellent lecture Sir. Thanks 🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏
Great explanation sir.
Thanks and welcome
Thank for your sharing. Can I ask you one question? At 20:23, what happened if one CT of any feeder is in heavy saturation condition resulting secondary current of that CT is equal 0? Then Idiff=Istab and B point will change to C lie on Fault line. Which solution for this problem? Many thanks.
Very good content. Sir please make a practical video on Siemens busbar differential protection Relay by explaining the different settings options in it.
Thank you for your feedback. I will make video on Siemens Bus Bar Relay Configuration after completion of Bus Bar Protection theoretical sessions. Stay tuned for more updates.
Sir,
Why slope of tripping characteristic is not having any slope during initial stage( at pick up current). At that time fault line comes below tripping characteristic.
sir pls.make video on end fault protection and ct supervision of busbar protection?
Yes I will explain this topic shortly.
thank yousir...
Excellent session Sir, Please do one series on MICOM configuration(PSL) for any protection
Its easy sir. I can help you.
Yes, I will definitely do one series on Micom Relay Configuration and PSL. Stay tuned for more updates.
Sir, I found a case of 400KV yard one and half breaker scheme, Present only tow dia of three are in service , In BCU Y phase tie bay of dia2 is showing zero ,other phase of same tie bay normal, and missing current shifted into Yphase of other tie bay of Dia 1 , What may be reason.
request you to help to find out reason.
check the interpanel wiring ..it may be wrongly connected for dia1 and dia2 of bcu