  • Here is the investigation I did in finding out the fault into our VFD

ความคิดเห็น • 83

  • @2mango15
    @2mango15 ปีที่แล้ว +8

    I am the Chief Engineer who work without ETO and I find your videos very interesting and helpful... Great job!

    • @ziakhattab6687
      @ziakhattab6687 ปีที่แล้ว

      Give me a chance to work with you as an ETO thanks🤩

    • @teferiiifantahun6062
      @teferiiifantahun6062 7 หลายเดือนก่อน

      Good day chief am ETO let me to work with you, kindly

    • @teferiiifantahun6062
      @teferiiifantahun6062 7 หลายเดือนก่อน

      Good day chief am ETO let me to work with you, kindly

  • @realdevbro447
    @realdevbro447 ปีที่แล้ว +11

    Your drawing was perfectly ok.

  • @chuckboyle8456
    @chuckboyle8456 ปีที่แล้ว +3

    Absolutely superb discussion and identification of the fault! Thank you so much for the video episode. Excellent!

  • @bayareajacob
    @bayareajacob ปีที่แล้ว +2

    You really make me wish I could have become a ship electrician. Must be so fun and satisfying. Great video again. Thank you.

  • @piinheiiiro
    @piinheiiiro ปีที่แล้ว +1

    You're great professional , I always watch your videos of troubleshooting.

  • @Gatsu1995
    @Gatsu1995 ปีที่แล้ว +1

    Thanks for the video. I'm a residential HVAC tech, so it's really cool to see this.

  • @fatihh7180
    @fatihh7180 ปีที่แล้ว +2

    Thank you so much for this instructive video. Keep going it. Take care of yourself.

  • @user-md3ir9zy5t
    @user-md3ir9zy5t ปีที่แล้ว +1

    Magaling, bro💪.I told my cadet to subscribe to you.I also have experience, but the video from the blog with the non-working expansion valve helped me a lot.

  • @dhaniel1339
    @dhaniel1339 ปีที่แล้ว +1

    Nice and good job sir leckyjake. Another additional knowledge about on how the proper elec. Motor winding, VFD and MCB testing/checking...Salamat sa video sir ETO leckyjake....Have a safe and smooth sailing sir.....GOD BLESS YOU 🙏

  • @fenflyer
    @fenflyer ปีที่แล้ว +3

    Thanks brilliant video 👍
    Personal experience of using VFD in our workshop
    (240 v 1 phase to 380v 3 phase VFD)
    Most nights 2300-0300 is perfect faultlessly performance but anytime between 1100-1345 is totally useless 🤔
    =
    Incoming 240v 10kva line transformer falls away @ 1100-1345 to much demand on area network 😬🤔🤦

    • @liam3284
      @liam3284 3 หลายเดือนก่อน

      perhaps need a solar panel to support the daytime loads?

  • @jaymajohnelton3271
    @jaymajohnelton3271 ปีที่แล้ว +1

    Thank you for the shared knowledge💙

  • @ObservantAlchemist
    @ObservantAlchemist ปีที่แล้ว +1

    Very insightful, thank you for sharing 🙏🏽

    • @leckyjake
      @leckyjake  ปีที่แล้ว

      thank you for watching

  • @richardgoonis
    @richardgoonis ปีที่แล้ว +1

    Great video lecky. Thank you

  • @oceaneight5583
    @oceaneight5583 ปีที่แล้ว +1

    Thank you for sharing Sir .... Malaking tulong ang learning n binabahagi nyo... God Bless you po

  • @vietvu8659
    @vietvu8659 ปีที่แล้ว +2

    Thank you my friend. This video very good for everybody.

    • @leckyjake
      @leckyjake  ปีที่แล้ว

      thank you very much

  • @glauciojackson2269
    @glauciojackson2269 ปีที่แล้ว +1

    Excelent my friend, congratulations!

  • @gazmasoda1
    @gazmasoda1 ปีที่แล้ว

    Thank you very much for sharing

  • @mithileshramteke3882
    @mithileshramteke3882 ปีที่แล้ว

    Thank you so much sir

  • @teferiiifantahun6062
    @teferiiifantahun6062 7 หลายเดือนก่อน

    Goods experience and explanation

  • @ChandanaPriyantha-pq3uv
    @ChandanaPriyantha-pq3uv หลายเดือนก่อน

    I learnt the lessons of electrical power.I 'll hope you sir, next lesson Thank you

  • @joebagadonuts-j4y
    @joebagadonuts-j4y ปีที่แล้ว

    i always learn from you LJ! thanks!

  • @patsroll
    @patsroll ปีที่แล้ว +1

    Thanks love your videos im an eto cadet and ur videos help alot

  • @geiuspalmero3919
    @geiuspalmero3919 หลายเดือนก่อน

    Thank you sir for sharing this so informative video ❤️

  • @Engr.Bon_sportytv25
    @Engr.Bon_sportytv25 ปีที่แล้ว +1

    Thank you for a New learning Sir⚡

  • @darimax
    @darimax ปีที่แล้ว +2

    Good video, one advise is taht during you measurment el.motor you can push button of your wire, for youe comfortable

    • @leckyjake
      @leckyjake  ปีที่แล้ว

      it fails sometime, i just made requisition

  • @svyat8710
    @svyat8710 ปีที่แล้ว +2

    It's a very useful Channel 👌 👍

    • @leckyjake
      @leckyjake  ปีที่แล้ว

      thank you for watching

  • @juliusbosquehamilton1075
    @juliusbosquehamilton1075 ปีที่แล้ว +1

    Very understanding

  • @aveshgupta4252
    @aveshgupta4252 6 หลายเดือนก่อน

    Thank you

  • @AL6S00740
    @AL6S00740 ปีที่แล้ว +2

    So an other idea would be to go and torque check all the VFDs and Motors , because IF one failed the rest are also in line to fail in similar ways. SO I would suggest take one by one out of commission and re-tighten all the bolts and connections and check for lose connections.

  • @joevisdiplomaticmoves6306
    @joevisdiplomaticmoves6306 ปีที่แล้ว +1

    Been a while since I worked as an electrician on motors,kinder remind me on continuity test of windings

  • @zack3706
    @zack3706 ปีที่แล้ว +2

    Hi Jake, I love these videos. Just a question - do you need to carry out a risk assessment before hand for this work or is one already in place? Also any permit to work required or lock out tag out?
    Thanks

  • @user-it9uq4jb8r
    @user-it9uq4jb8r ปีที่แล้ว

    Thanks and Regards Bro

  • @hasitharajapaksha6423
    @hasitharajapaksha6423 10 หลายเดือนก่อน

    excellent 👌👌

  • @cliveramsbotty6077
    @cliveramsbotty6077 ปีที่แล้ว

    i was so happy when you made the drawing

  • @firdauspeoh987
    @firdauspeoh987 ปีที่แล้ว

    thanks a lot lecky jake. now im e/l cadet hopefully i can gain more knowledge from u. my lecky onboard not too helpful ;(

  • @kelechicharles166
    @kelechicharles166 ปีที่แล้ว +1

    Can you just establish an academy where people can come for training? You're really doing a great job. Thanks a lot

  • @johncantrell614
    @johncantrell614 ปีที่แล้ว +4

    Good video. We always try to tell our apprentices at the shipyard what you have said about isolating each part of the system separately. As you say, it helps you track down the individual problem, and also makes sure that when you use the megger on things, you only will be using it on the parts of the circuit that can handle the high voltages that the megger will put out.
    If you do not take off any sensing wires or similar things first, then you could be sending 500- 1000 volts from the megger to sensitive electronics, which cannot handle those voltages, creating a far bigger problem than you started out with……

    • @michaelw4258
      @michaelw4258 ปีที่แล้ว

      Yes, you are right. But 500V DC is not so much for a 400 V(?) AC powered inverter. Around 560V DC is a normal operational voltage. This VFD has gone anyway.

    • @johncantrell614
      @johncantrell614 ปีที่แล้ว +2

      @@michaelw4258 yes, in that case, you are correct. But in other cases, there are often sensing devices on generators and things that can be burned out by the high voltages that the mergers put out. Those items are what I was mentioning, and was why it is important to isolate these things so they are not burned out by mistake. 🙂

    • @HILBERTOFUNES7
      @HILBERTOFUNES7 ปีที่แล้ว

      Always,
      and this fundamental,we isolate sensitive electronic circuits such as AVR etc when we use megger test in case of supplying 500vdc( the generated voltage from megger test)to the electronic circuit with danger of damaging it irreversably.

  • @adelramos8296
    @adelramos8296 ปีที่แล้ว +2

    Question and comment. First of all big fan of your videos, currently subscribed, thank you so much for posting your videos❤
    That being said, when you were checking insulation instead of using the Test button on the meter, why didn’t you use the Test button on the red lead?

    • @leckyjake
      @leckyjake  ปีที่แล้ว +1

      sometimes it fails, there is something wrong on my probe that needs replacement. I already requested it and still waiting for the spare

    • @michaelw4258
      @michaelw4258 ปีที่แล้ว +1

      ​@@leckyjake I have a keysight Insulation Multimeter, same issue. Bottom on test leads is defective😂

  • @beckylupton3881
    @beckylupton3881 6 หลายเดือนก่อน

    Thank you so much for posting all your videos! As a shore side electrician I would love to get sea experience. How do I get to be a cadet with you?!?!?🎉

  • @hepebaste
    @hepebaste ปีที่แล้ว

    Good job lecky

  • @lixtvofficial9008
    @lixtvofficial9008 ปีที่แล้ว +1

    Magandang hapon po sir watching po

  • @KrizzNANDU
    @KrizzNANDU 27 วันที่ผ่านมา

    Rip mahn.. you will be missed..

  • @ievgenod9708
    @ievgenod9708 ปีที่แล้ว +1

    if power cable connected to a mot not giving low insulation res during test what purpose to disconnect cable?

  • @rb1m426
    @rb1m426 ปีที่แล้ว

    Present lods😊

  • @arjunak7807
    @arjunak7807 ปีที่แล้ว +1

  • @6Diego1Diego9
    @6Diego1Diego9 ปีที่แล้ว

    he too good!

  • @janphilipbalbin8886
    @janphilipbalbin8886 ปีที่แล้ว

    hi. im curious, why is it necessary to also replace the vfd? thank you.

  • @Marineelectricalknowledge
    @Marineelectricalknowledge ปีที่แล้ว +2

    Hi sir, in my ship our main cooling sea water vfd showing fan failure. Fan is actually not accessible what is the solution?

    • @leckyjake
      @leckyjake  ปีที่แล้ว +1

      you have to access the fan ofcourse

  • @ngendokerzgaming5330
    @ngendokerzgaming5330 หลายเดือนก่อน

    Insulane motor is good condition.. so where is the proublem? VFD or MCCB?

  • @jirehblanza576
    @jirehblanza576 11 หลายเดือนก่อน

    hi sir, paano po mag ojt or internship sa barko na katulad po ng ginagawa ninyo, paano po magapply. thanks po

  • @realdevbro447
    @realdevbro447 ปีที่แล้ว +2

    What would the tester show if there was a fault?

    • @nedelcucostin9289
      @nedelcucostin9289 ปีที่แล้ว

      0

    • @kasska6717
      @kasska6717 ปีที่แล้ว +1

      0Ω or 1Ω if good you will see >1000MΩ

    • @inothome
      @inothome ปีที่แล้ว

      There is usually a minimum insulation resistance value given by the manufacturer. But with no specs a rule of thumb is 1 Meg Ohm per 1,000V plus 1 Meg Ohm. So on a 400V motor like this there should be at minimum 1 to 2 Meg Ohm and he was measuring over 550Meg Ohm. But if he was measuring in the kilo-Ohm range then something would be suspect, it doesn't have to be 0 or very low to fail. With insulation resistance the higher the better.

  • @PR-zs9pw
    @PR-zs9pw ปีที่แล้ว

    Where are you now in ship or sign out?

  • @maksst2885
    @maksst2885 ปีที่แล้ว +1

    From my point of view, no reason to disconnect “Delta” connection in the terminal. The measurements with plates or without will be the same. Also I don’t understand why you are going to replace power cable? Is there short circuit?

    • @inothome
      @inothome ปีที่แล้ว +3

      He broke the delta so he could check individual winding resistances. He mentioned he checked them but didn't show it.

    • @maksst2885
      @maksst2885 ปีที่แล้ว +1

      @@inothome without broken delta connection you can check individual windings! No point to do it, check what does it means delta connection. Even with star you can check without broken connection. If reading between three phase will be different, after that you should brake connection

    • @leckyjake
      @leckyjake  ปีที่แล้ว +6

      there are cases where you have equal continuity but all you are measuring is a shorted Lines. The proper IR test is to separate each windings and measure in between. that is only 5 mins additional time to your job.

    • @inothome
      @inothome ปีที่แล้ว +3

      @@leckyjake Exactly!! Do it right and it only takes a few extra minutes.

  • @kuldeepsingh8486
    @kuldeepsingh8486 ปีที่แล้ว +1

    Sir how you replace vfd and power cable in that make that video also sir

  • @arvinlabador704
    @arvinlabador704 ปีที่แล้ว

    Kuya idol pwede po mag conduct insulation resistance ng 3phase induction motor kahit naka connect si VFD....hindi po bah masisira si VFD.... salamat po and God bless you......😊

    • @bossmarbin-yv8ug
      @bossmarbin-yv8ug ปีที่แล้ว +1

      Isolate muna si VFD bago mag megger.

  • @ianrosal1235
    @ianrosal1235 หลายเดือนก่อน

    wow puro fluke

  • @MuhammadQasim-fj5bn
    @MuhammadQasim-fj5bn ปีที่แล้ว

    Where was the actual fault ?

    • @liam3284
      @liam3284 3 หลายเดือนก่อน

      loose wiring in the VFD