One Simple way to check if an AC drive is good

แชร์
ฝัง
  • เผยแพร่เมื่อ 24 ก.ค. 2019
  • If you have ever worked around AC Drives also know as VFD, you may run into situations where the input fuses are blown. Maybe the motor went bad on you. Now you are not sure if the AC drive is good or not. You are afraid to power up the AC drive.
    Well, there is a way to check your high voltage circuit on your AC Drive giving you the confidence to apply voltage to the AC drive again.
    Follow along as I show you how to do this simple test called, "Static Check" to give you the okay to apply power to your AC drive.
    Follow us on our Facebook page too!!
    / electronictechincnc

ความคิดเห็น • 79

  • @jesusortiz6842
    @jesusortiz6842 2 ปีที่แล้ว +1

    You are incredible. Thanks for teaching us.

  • @maulandhall2340
    @maulandhall2340 4 ปีที่แล้ว +4

    Thanks so much i am grateful for this online course very much appreciate bless

  • @jorgeresendiz1932
    @jorgeresendiz1932 3 ปีที่แล้ว +1

    excellent video. Thank you. Very thorough explanation.

  • @fernandomartins7261
    @fernandomartins7261 3 ปีที่แล้ว +1

    Thanks a million for your great explanation and effort. Kind regards.

  • @haroldlanglois8986
    @haroldlanglois8986 3 ปีที่แล้ว +1

    Great explanation, very understandable. thanks

  • @aghvacappliancerepair4120
    @aghvacappliancerepair4120 2 ปีที่แล้ว

    Awesome video man, gave a great explanation on how to check the bridge rec and igbt, I will defiantly be using this method from time to time.

  • @elmoncho72
    @elmoncho72 ปีที่แล้ว

    Great video that helps me to understand deeper in VFDs drive field

  • @Theandrew189
    @Theandrew189 ปีที่แล้ว

    Awesome video. I always wondered how to do some kind of test like this to support me saying, " Drive is bad boss".

  • @samsirjaafar364
    @samsirjaafar364 3 ปีที่แล้ว +1

    Great explaination. Tqvm.

  • @canaldamanutencao4446
    @canaldamanutencao4446 3 ปีที่แล้ว +1

    Very cool. Very well explained, I would like to congratulate you for the initiative.

  • @sudhirpatil3434
    @sudhirpatil3434 4 ปีที่แล้ว +1

    Very nice explanation!

  • @samuelgantala5253
    @samuelgantala5253 3 ปีที่แล้ว

    Thanks i've learned the basic test.

  • @laworder6092
    @laworder6092 3 ปีที่แล้ว +3

    Thank you sir. Well explained I salut for your generosity.

  • @AA-hu9mh
    @AA-hu9mh 2 ปีที่แล้ว +1

    Awesome explanation 👏🏻

  • @supertech2853
    @supertech2853 ปีที่แล้ว

    Thank you for the video it is very helpful

  • @willskee7817
    @willskee7817 3 ปีที่แล้ว

    Valuable information thanks buddy

  • @cheyguvera9680
    @cheyguvera9680 ปีที่แล้ว

    Great explaination sir, god bless you

  • @NLocus1
    @NLocus1 3 ปีที่แล้ว +1

    Excellent Video.
    If you have a problem with your control board, this may also be a cause of IGBT Gate short-circuited. Beware. The gates could not be accessed from outside, dismantle and check.

  • @guptabrothers1938
    @guptabrothers1938 2 ปีที่แล้ว

    Very good explanation carry on thanks for it.

  • @015diesel
    @015diesel 3 ปีที่แล้ว

    Thanks for the video

  • @michaelshansen7070
    @michaelshansen7070 4 ปีที่แล้ว +1

    Wow great, now I understand...

  • @labenrosatase
    @labenrosatase 8 หลายเดือนก่อน

    Thanks for your tutorial .. gob bless sir..

  • @donaldpatan930
    @donaldpatan930 4 ปีที่แล้ว +1

    Thank you another day another learn

    • @gatedavid95
      @gatedavid95 2 ปีที่แล้ว

      Good explanation

  • @donovanj8840
    @donovanj8840 4 ปีที่แล้ว

    Job well done..

  • @COFFEE23409
    @COFFEE23409 4 ปีที่แล้ว +4

    Excellent video. I never considered that method of testing.

  • @dr-gaberibrahim5268
    @dr-gaberibrahim5268 4 ปีที่แล้ว

    Thanks so much

  • @gershonfroumine6827
    @gershonfroumine6827 ปีที่แล้ว

    Thank you LU

  • @ezhavaganesh
    @ezhavaganesh 3 ปีที่แล้ว

    Best video i found superb thanks a lott

  • @nikhilviswam9546
    @nikhilviswam9546 2 ปีที่แล้ว

    Great information. Kuuyaaa.

  • @kimtran8540
    @kimtran8540 2 ปีที่แล้ว

    Thank you.

  • @sthabilemthembu2854
    @sthabilemthembu2854 ปีที่แล้ว

    great video
    What would be the readings if there was a short circuit?

  • @brianb5779
    @brianb5779 3 ปีที่แล้ว

    Anything different w allen bradley 4's and 40's with this kind of testing?? Also thank you for all your info

  • @compressorman43
    @compressorman43 2 ปีที่แล้ว

    Great explanation thanks . How we test hi hight volts for leak iGBT

  • @wirenutt57
    @wirenutt57 3 ปีที่แล้ว +3

    How about checking the rectifier diodes with reverse polarity? You checked the forward voltage drop, but if you switch the leads, you should get an open. If you get anything other than high resistance, the diode could be shorted. Take into account the fact that the huge filter caps will take a bit to charge, and you might see a temporary short because of that.

    • @cdrive5757
      @cdrive5757 9 หลายเดือนก่อน

      Have you ever revisited your comment since you posted it? I know it must have made sense to you when you posted it but think about what you said.
      Wakodahatchee Chris

  • @ricardofelizco8323
    @ricardofelizco8323 3 ปีที่แล้ว

    thxs for video learning...can you give some information and application of SEMITRNS M SKKR400/0.2-BVR for VFD design and function..thank you and best regards Sir

  • @henrymendez5934
    @henrymendez5934 3 ปีที่แล้ว

    Thanks Lou very informative. How do I reach you?

  • @makashem8704
    @makashem8704 2 ปีที่แล้ว

    Dear Friend,
    Thank you for your video, i would like to know that i don't have 3 phase 380v.line in my workshop. Only 220v. available, how i can check my vfd after repair it? Plz let me know it will be very useful to me.
    Thanks

  • @mattivester7353
    @mattivester7353 ปีที่แล้ว

    Could you discuss what the DC Buss terminals are? I see there are 4 terminals.

  • @ashishrsahu
    @ashishrsahu 3 ปีที่แล้ว

    Please make a video on siemens simovert 430 440 drive and abb dcs drive 550 checking

  • @suhailthanikal
    @suhailthanikal 4 ปีที่แล้ว

    Thanks

  • @MDsayed-xz7df
    @MDsayed-xz7df 2 ปีที่แล้ว

    I have a question sir.
    ig5a lsis vfd. It’s showing low voltage when i run the drive. What should i do sir?
    We are audience waiting for your kind information.
    Thank you sir.

  • @ksteelcambodia595
    @ksteelcambodia595 4 ปีที่แล้ว

    i have an AC motor inverter EDS2000 model. and i followed your instructions to test it. the result showed the same as in your video instructions, but when i power it up and press RUN, it showed error E013. could you recommend something?

    • @electronictech785
      @electronictech785  4 ปีที่แล้ว +1

      I don't have the manual for the drive. What does the E013 fault?

  • @samsirjaafar364
    @samsirjaafar364 3 ปีที่แล้ว

    Good Evening. I have washing machine (laundry) using single phase input with 3 phase motor. My priblem is.... The motor body tempreture very hot, touch by hand. Than sometime, motor not running. In this case, motor problem or VFD problem? Plesse advise.

    • @electronictech785
      @electronictech785  3 ปีที่แล้ว +1

      A single phase being turned back to 3 phase is already not the best way to drive a motor but with that being said, I would check the motor out first if its heating up.

  • @alankellerhouse1249
    @alankellerhouse1249 ปีที่แล้ว

    Thez video on. Ac drive was very good
    Iexplain how the. Ac drive works
    I would like to see trouble shout videos and =epairs.

  • @janmalesela2510
    @janmalesela2510 3 ปีที่แล้ว

    Hi, this test can be conducted in a new vfd. Or ii need to power it first .then disconnect the cables . I tested in a new vfd but everything is open. That's my question. Again what if the cable is faulty or motor . One say whole the cable was faulty the vfd was showing dc bus over voltage can you explain that to ne

    • @electronictech785
      @electronictech785  3 ปีที่แล้ว

      Yes, new and used. You are checking the bridge rectifier and the IGBTs. This test is not for testing cables so the line input cables and motor cables should be disconnected. DC Bus over voltage means that the voltage on the Bus has exceeded the VFDs threshold.

    • @janmalesela2510
      @janmalesela2510 3 ปีที่แล้ว

      @@electronictech785 hi sir, I tested new vfd everything is one. Testing diode forward bias is open. Testing Igbt is open. Now I was just asking need to charge the resistor or not .

  • @jerrellmahan4814
    @jerrellmahan4814 4 ปีที่แล้ว

    Most of the VFDs sold today don't provide the + and - terminals for the DC bus. How can the diodes be checked without the + and - terminals?

    • @electronictech785
      @electronictech785  4 ปีที่แล้ว

      In that case, you'll have to get access to the bus caps which would require you to take it apart. The only time we see VFDs with no + and - terminals are the small Horse Power VFDs.

    • @jerrellmahan4814
      @jerrellmahan4814 4 ปีที่แล้ว

      @@electronictech785That's what I was afraid of. Thanks for your help.

  • @dizzolve
    @dizzolve 2 ปีที่แล้ว

    can you test when powered up

  • @jsteele42378
    @jsteele42378 4 ปีที่แล้ว

    is this want I use to work with dealing with Variable Frequency Drives ?

    • @electronictech785
      @electronictech785  4 ปีที่แล้ว

      The higher horsepower VFD is profitable. You have to know what industry and where they are at.

    • @jsteele42378
      @jsteele42378 4 ปีที่แล้ว

      @@electronictech785 Wow you are getting into some really super tech and more that nice to know subjects ! ! ! ! ! !

  • @Jugc0006
    @Jugc0006 2 ปีที่แล้ว

    Awesome we'll cover

  • @joycandromojumdar
    @joycandromojumdar ปีที่แล้ว

    Dear sir thank you this inverter is diagram please

  • @emedosichijioke4557
    @emedosichijioke4557 2 ปีที่แล้ว

    pls i did my static check and my igbt module is good but yet i didnt get power output even when the drive is running using the local mode

  • @tankmanikhapangi6279
    @tankmanikhapangi6279 2 ปีที่แล้ว

    Sir how can resolve problem fault code 5696 pu state feedback in abb acs 880 vfd drive

  • @joycandromojumdar
    @joycandromojumdar ปีที่แล้ว

    This inverter schematics diagram please.

  • @jsteele42378
    @jsteele42378 4 ปีที่แล้ว

    I can't seem to remember is 3 phase " each leg is 70 degrees or 30 degrees out of phase with each other " ? chit seems I wouldn't for get and maybe I wrong.

    • @electronictech785
      @electronictech785  4 ปีที่แล้ว

      For a three-phase AC voltage source, the phase shift is 120° with respect to each other

    • @jsteele42378
      @jsteele42378 4 ปีที่แล้ว +1

      @@electronictech785 Yep sorry I now remember thanks so much ! I was thinking that this was the reason that several motors and compresses did need starter cap if you had 3 phase.

  • @zainabbas2524
    @zainabbas2524 4 ปีที่แล้ว +3

    Thought it would be more indepth and more visual .

    • @RyanJardina
      @RyanJardina 4 ปีที่แล้ว +4

      How more in depth do you need? The only thing that's really missing is he should be drinking a bottle of whiskey.

  • @nukeelda
    @nukeelda 3 ปีที่แล้ว

    PB where is conected?

  • @aldosejacobite5381
    @aldosejacobite5381 3 ปีที่แล้ว

    How to contact u sir

  • @bismillahelectronicsindust9824
    @bismillahelectronicsindust9824 4 ปีที่แล้ว

    Sir I teach Ac drive repairing video upload thanks

  • @multisado7562
    @multisado7562 3 ปีที่แล้ว

    Hello Sir, I sell electromagnetic heater , I wish can repair by our self can you teach us ? I would send the photos of electromagnetic heater if can teach for us to repair it..

  • @rameshodedara1401
    @rameshodedara1401 4 ปีที่แล้ว

    Hello sir,
    Thanks for your effort.
    => As power electronics engineer, I know this thing, i thought u may explain testing of control circuit, or driver circuit problem or feedback portion at signal level. Very disappointed.