Charging R-410A Refrigerant Into An Air Conditioner Using Wireless Probes!

แชร์
ฝัง
  • เผยแพร่เมื่อ 16 ม.ค. 2025

ความคิดเห็น • 104

  • @deanmartin1966
    @deanmartin1966 6 หลายเดือนก่อน

    I'm sure I've said it before, but thanks for all the great free information you and all the other great teachers provide. Such a wealth of knowledge. I'm 58 and I absolutely hated high school. Until I got into the trades. Then surprisingly I became an "A" student. I seriously love the trades and think its a great alternative to a four year college. My grand daughter is 15 and wants to become a welder. She makes me proud. Once again, thanks. Phil

  • @electrolatif
    @electrolatif 6 หลายเดือนก่อน +2

    The best aircon video in TH-cam ❤

  • @Meenomack
    @Meenomack 5 หลายเดือนก่อน

    This guy is a bad dude ! Always on point !

  • @paulrmfd
    @paulrmfd 6 หลายเดือนก่อน +2

    absolutely instructional keep up the good work

  • @yannkitson116
    @yannkitson116 6 หลายเดือนก่อน +2

    Great video, I have Testo probes and a slightly different app but it is all the same in the end :)

  • @deanmartin1966
    @deanmartin1966 6 หลายเดือนก่อน +2

    Excellent video Craig. I do love my fieldpeace probes.

  • @kevinpearce3281
    @kevinpearce3281 4 หลายเดือนก่อน +1

    I bought those probes. I don’t have the manometers yet tho. Some day I’ll get what I need to do my job properly.

  • @pbrewton
    @pbrewton 4 หลายเดือนก่อน

    @acservicetechchannel Craig, correction to your statement: 75F as our *outdoor* dry bulb... 😊 8:47

  • @Domopartner
    @Domopartner 4 หลายเดือนก่อน

    great explanation thanks

  • @edwardlouie
    @edwardlouie 6 หลายเดือนก่อน +4

    I like using core depressors so I don't need to spin on/off quickly.

  • @mohdrifi1930
    @mohdrifi1930 6 หลายเดือนก่อน +1

    Excellent! You need to do this method to ac split unit also! Appreciate your effort teacher! ❤️❤️❤️❤️

    • @cryptkeyper
      @cryptkeyper 6 หลายเดือนก่อน +2

      This is a ac split unit

    • @jericosha2842
      @jericosha2842 6 หลายเดือนก่อน +3

      This doesn't work on mini split ductless if that's what you mean

  • @Tomkayanja
    @Tomkayanja 5 หลายเดือนก่อน +1

    Thank for the video, the effort and time you put in make the world a better place to leave in.

  • @pongobongo2295
    @pongobongo2295 6 หลายเดือนก่อน

    Use Appion charging tees. This is my go to charge set up. Also, get a third probe and map to outdoor air temp.

  • @jorgemanzano7232
    @jorgemanzano7232 6 หลายเดือนก่อน +1

    Well explained! Thank you very much 😊

  • @kennethlobo4420
    @kennethlobo4420 6 หลายเดือนก่อน +1

    Well explained ❤

  • @craigmarshall40
    @craigmarshall40 5 หลายเดือนก่อน

    Great video thank you for spending the time

  • @gingerstrand6153
    @gingerstrand6153 6 หลายเดือนก่อน +1

    Great video, thank you!!

  • @kastenusa
    @kastenusa 6 หลายเดือนก่อน +5

    Can you please make a video on where to connect probs on package unit correctly. Thank you!

    • @cryptkeyper
      @cryptkeyper 6 หลายเดือนก่อน

      I second this

    • @kinstonboy1
      @kinstonboy1 4 หลายเดือนก่อน

      Supply & return duck lol​@@cryptkeyper

  • @AndyHoltOutdoorUniversity
    @AndyHoltOutdoorUniversity 6 หลายเดือนก่อน

    Nice job, Craig!

  • @repairitdontwreckit4257
    @repairitdontwreckit4257 6 หลายเดือนก่อน +1

    Thanks. Nice job.

  • @manueldacosta6539
    @manueldacosta6539 6 หลายเดือนก่อน

    Excellent video as always, thank you.

  • @zahedaminullah6934
    @zahedaminullah6934 6 หลายเดือนก่อน +1

    Great video man!

  • @TheWathever516
    @TheWathever516 6 หลายเดือนก่อน +1

    Great video!

  • @x-got2bkidiny-justlikeabov787
    @x-got2bkidiny-justlikeabov787 5 หลายเดือนก่อน +1

    Awesome explanation but … the label on the unit says indoor TXV with 10 deg F sub cooling. You say it has a fixed orifice so you’re using the superheat method - am I a missing something here?

    • @acservicetechchannel
      @acservicetechchannel  5 หลายเดือนก่อน +1

      Yes so the outdoor unit will always tell you the subcooling if a txv is used. However, as you can see through that plexiglass at the indoor unit, there is a piston there and not a txv. Single stage outdoor units can be installed with any combination of indoor units and metering device, thanks! To learn more check out our books at acservicetech.com !

    • @iamtheedrummer1
      @iamtheedrummer1 4 หลายเดือนก่อน

      Yeah I caught that

  • @povoljan13
    @povoljan13 6 หลายเดือนก่อน +1

    The charging hose has air when you hooked it up to the tee. The small space after the shutoff valve is dead air space. Needs a better setup maybe?

  • @butlerstouchHVAC
    @butlerstouchHVAC 6 หลายเดือนก่อน +1

    great vid

  • @ludylopez3327
    @ludylopez3327 5 หลายเดือนก่อน

    😮It's advisable to charge luguid in suction side.

  • @pitaeata8493
    @pitaeata8493 6 หลายเดือนก่อน +1

    need tips and tricks to determine if a system has a piston or txv. Sometimes on UNCASED coils it is impossible to remove the front of the field made cover to get a look.

    • @sir.cannabis1173
      @sir.cannabis1173 6 หลายเดือนก่อน

      I'm thinking one could tell by how fast the numbers move. Craig mentioned it might take 15 minutes for pressures to equalize with a fixed.

    • @mackenziegray2090
      @mackenziegray2090 6 หลายเดือนก่อน

      If you see a threaded union outside the case, chances are you got a piston.

    • @turnedearthdesign8678
      @turnedearthdesign8678 6 หลายเดือนก่อน

      Also check the chart on the condenser. It usually (but not always) tells you what the pressure of one of the lines should be which should match up to the metering device used

  • @APHVAC0913
    @APHVAC0913 6 หลายเดือนก่อน

    Great video 👌🏽

  • @AllanJansen-pu1cx
    @AllanJansen-pu1cx 15 วันที่ผ่านมา

    I have a question is it necesarry to use a imperial quick charge to charge R410a is ot sny quicker when using it .or just charging without it is just as quick

  • @JoeSullivan-k6c
    @JoeSullivan-k6c 6 หลายเดือนก่อน

    ? What is the link for the brass tees to purchase sir. Thank You.

  • @justinhughes452
    @justinhughes452 6 หลายเดือนก่อน

    What was the recommended amount of refrigerant on the name plate? How much was in system at the start and what was the total amount at the rnd of this demonstration?

  • @lorunner1213
    @lorunner1213 6 หลายเดือนก่อน

    Craig. Does the outdoor Dry bulb temp matter if being read from the sunny side of the condenser vs the shady side?

  • @carlossaenz4075
    @carlossaenz4075 3 หลายเดือนก่อน

    Can I down load the calculation app ? And so what do need to do

  • @JuanJuarez-en5xn
    @JuanJuarez-en5xn 6 หลายเดือนก่อน

    Can you make a video on RTU’S?

    • @mackenziegray2090
      @mackenziegray2090 6 หลายเดือนก่อน

      It's the samething. What part confuses you?

  • @JuanJuarez-en5xn
    @JuanJuarez-en5xn 6 หลายเดือนก่อน

    Where can I buy those T’s that go on your probes do you have a link to them ?

  • @arthurrabon9349
    @arthurrabon9349 6 หลายเดือนก่อน

    multi zone split unit question. if you have 3 zones and 1 zone is having troubles meeting set temp. how does system respond.

  • @globecomputers1
    @globecomputers1 6 หลายเดือนก่อน

    Great video! Like always! Question can you provide a link for those AC test caps? I need to buy a set.

    • @HVAC_Tips_Tricks_Calcs
      @HVAC_Tips_Tricks_Calcs 6 หลายเดือนก่อน +1

      Just take two spare caps and drill a hole in them.

  • @mtbbiker6401
    @mtbbiker6401 6 หลายเดือนก่อน +1

    I don't understand how taking a low pressure (vapor line) reading at the condenser translates to the pressure in the evaporator. Why is it not industry standard to take low pressure (vapor line) reading at the evaporator?

    • @8799crosby
      @8799crosby 6 หลายเดือนก่อน +1

      There is no ports at the evap .

    • @mtbbiker6401
      @mtbbiker6401 6 หลายเดือนก่อน

      @@8799crosby So we are measuring total super heat temp using thermometer near the service port at the condenser (outdoor unit for heat pump) and measuring the pressure at the same service port to measure the temperature at the evaporator (indoor unit for heat pump). We measure pressure to convert to temperature. If we are measuring the temp and the pressure at the same spot, why don't the temp readings match? I'm trying to understand the physics behind this. Does it have to do due with saturation temp, sensible heat, latent heat?

    • @EricJohnson-dr5wb
      @EricJohnson-dr5wb 6 หลายเดือนก่อน

      @@mtbbiker6401good question. The pressure on the low side is essentially the same in the evaporator as it is at the low side service port. The vast majority of the cooling is due to the liquid to vapor phase change in the evaporator coil. The additional heating of the 100% vapor is the superheat. You want there to be some superheat to prevent liquid refrigerant from entering and damaging the compressor.

    • @957543
      @957543 5 หลายเดือนก่อน

      Because you want to be able to be in one spot

  • @jroberts3428
    @jroberts3428 5 หลายเดือนก่อน +2

    I've been flooding alot of compressors 😳

    • @markniles3013
      @markniles3013 4 หลายเดือนก่อน

      We all do. Sometimes when your busy. Lol

  • @NickNameNemo
    @NickNameNemo 6 หลายเดือนก่อน

    If system has leakage (r410a) and still remains some amount of refrigerant, let’s say 70-80% of total, should I recover all refrigerant from system and charge it with new or just add needed amount?

  • @vonboldler5219
    @vonboldler5219 6 หลายเดือนก่อน

    Hi mike!

  • @edwardlouie
    @edwardlouie 6 หลายเดือนก่อน

    This method doesn't always work with inverter variable speed equipment that change the superheat target based on various logics.

    • @HVAC_Tips_Tricks_Calcs
      @HVAC_Tips_Tricks_Calcs 6 หลายเดือนก่อน +1

      Inverters usually don’t have fixed orifices.

  • @jimwhite9483
    @jimwhite9483 6 หลายเดือนก่อน

    How hard would it be for Fieldpiece to add a wireless input for ODDB in the app or on the SMAN 380V?

    • @turnedearthdesign8678
      @turnedearthdesign8678 6 หลายเดือนก่อน

      You can link one of their psychrometer probes to the outdoor dry bulb

  • @SocratesDionisius
    @SocratesDionisius 4 หลายเดือนก่อน

    What if we add r32 to r410 system. Let say we add 30% r32 into it?

  • @tomaszpoznanski7584
    @tomaszpoznanski7584 6 หลายเดือนก่อน

    Iam a contractor and would like to do a course/training for a/c contractor. Can you recommend any in NY/NJ/PA area? Any schols?

  • @wpl11972
    @wpl11972 6 หลายเดือนก่อน +2

    I just use my valve core removal tool as my tee.

    • @emidiolopez1409
      @emidiolopez1409 6 หลายเดือนก่อน +1

      So you remove the schrader valve to do SH or SC? Or what kind of removal tool do you use that has a press tool built in? Because the Appion that I use don’t have the press tool so I can’t take any risk of losing 5+ pounds of refrigerant by removing the schraders lol

    • @HVAC_Tips_Tricks_Calcs
      @HVAC_Tips_Tricks_Calcs 6 หลายเดือนก่อน

      @@emidiolopez1409if your loosing 5 lbs with a core removal tool you’re using it wrong. How much refrigerant are you going to lose I’d the schrader doesn’t seal?

    • @emidiolopez1409
      @emidiolopez1409 6 หลายเดือนก่อน

      @@HVAC_Tips_Tricks_Calcs Ive never said I’m losing 5 pounds by using the schrader removal tool. I said that’s just stupid if you have to remove the schrader valves every time you have to check the pressures on an AC, NO way I’m taking risks in losing factory refrigerant if something doesn’t goes bad with the removal tool.

  • @pana5075
    @pana5075 6 หลายเดือนก่อน

    Espero este video en español

  • @monstaro19
    @monstaro19 6 หลายเดือนก่อน

    We need a way to use this in cars its 106 in Florida

  • @davidlopan6649
    @davidlopan6649 6 หลายเดือนก่อน +2

    I can see myself pulling the pressure probes off the T and accidentally letting out all the refrigerant. lol definately would put a valve core on that for me.

    • @lorunner1213
      @lorunner1213 6 หลายเดือนก่อน

      I use apion tee’s. They are low loss with schraders on both male ends of the tee. So doesn’t matter if you pull just the probe off. Or the tee with the probe.

    • @davidlopan6649
      @davidlopan6649 6 หลายเดือนก่อน

      @@lorunner1213 Yeah I love appion tools. Just purchased their recovery machine.
      I didn't get probes yet probably next year.

    • @JuanJuarez-en5xn
      @JuanJuarez-en5xn 6 หลายเดือนก่อน

      Where did you bought those T’s ?

    • @lorunner1213
      @lorunner1213 6 หลายเดือนก่อน

      @@JuanJuarez-en5xnJohnstone Supply

  • @HVAC_Tips_Tricks_Calcs
    @HVAC_Tips_Tricks_Calcs 6 หลายเดือนก่อน

    Although I’m sure sponsored, nice to see someone make a video that didn’t say you had to use MQ and True Flow or you’re a hack.

  • @Mok-l5i
    @Mok-l5i 6 หลายเดือนก่อน

    🙏🙏🙏🙏

  • @mikev.1034
    @mikev.1034 6 หลายเดือนก่อน

    👍👍

  • @martinguzman4323
    @martinguzman4323 5 หลายเดือนก่อน

    👍👍👍👍👍👍👍👍👍👍👍👍👍

  • @noname-cw5or
    @noname-cw5or 5 หลายเดือนก่อน +1

    I thought this was a joke at first

  • @var8492
    @var8492 6 หลายเดือนก่อน

    What if my liquid pressures are at 390 and suction 174 with a 11 t/s !??

  • @YankeesFan74
    @YankeesFan74 6 หลายเดือนก่อน +1

    sadly most techs will hook up and immediately say it's good or needs refrigerant because companies are so focused on getting techs in and out as fast as possible. Most expect a complete diagnosis to be complete in 30 min max preferably less.

    • @TheRealDegen100
      @TheRealDegen100 6 หลายเดือนก่อน +1

      Preferably way less but every call is different. Only calls that really take time is determination of why a part failed.

  • @hazendismukesjr.8319
    @hazendismukesjr.8319 6 หลายเดือนก่อน

    😂why didn't you use a charging orifice

  • @kevinpearce3281
    @kevinpearce3281 6 หลายเดือนก่อน +8

    Why can’t you put the r410a into the liquid side if it’s coming in as a liquid

    • @davidgochenour7072
      @davidgochenour7072 6 หลายเดือนก่อน +20

      It would push refrigerant into your bottle

    • @camilo8cheryl
      @camilo8cheryl 6 หลายเดือนก่อน +11

      High pressure

    • @FreonChugger
      @FreonChugger 6 หลายเดือนก่อน +11

      The liquid side is at a high pressure while the system is running. Connecting the refrigerant jug to the suction line, which is a lower pressure, will suck the refrigerant into the system.

    • @wyattdekay7763
      @wyattdekay7763 6 หลายเดือนก่อน +1

      Usually to much pressure

    • @boongoon92
      @boongoon92 6 หลายเดือนก่อน +1

      It's leaving as a liquid

  • @snwsk8
    @snwsk8 6 หลายเดือนก่อน

    Great tips as always, thank you