Capacitor Bank ON ho raha hai isme load(Ampere) ka koi role nhi hai..PF depends on positive reactive Power is caused by Inductive loads... isme aapko power factor kya chal raha hai aapko system ka usper depend krta hai...345amp. mein pf kya hai?
Due to Current THD... Actually current THD setting is 30% and alarm come after 30 % but here current THD is approximately 34%..so alarm is coming here.
Apfc relay 12r
Problem is plants loading amp. 1000 and all capacitor off or plant load is 345 amp. than all capacitor bank on
Capacitor Bank ON ho raha hai isme load(Ampere) ka koi role nhi hai..PF depends on positive reactive Power is caused by Inductive loads... isme aapko power factor kya chal raha hai aapko system ka usper depend krta hai...345amp. mein pf kya hai?
Hello sir,
My I just installed this controller..but power factor not maintaining 0.999. can u help sir
Please sir send my problem salutation
Hello sir good afternoon
Alarm Kyo aarha
Due to Current THD... Actually current THD setting is 30% and alarm come after 30 % but here current THD is approximately 34%..so alarm is coming here.