SirDefault setting is : 0.015 of In hai.Aap default setting rakh sakte h koi problem ni h
Etasmart8t k common me ac volt denge ya dc volt
Brother 8R - means you have to use normal cap duty ContactorAnd 8T means it’s designed for thyristor Use only when you have thuristor
Hello sirhow to slove UNDC
SirUndc means under current , means there is no sufficient current from ct Check ct output secondary current at Apfc ct terminals and car polarity
OCOM aur UNDC alarm ki setting kaise karna hai. Kaunse menu main Jana hai
As per my best knowledge , I think there is NO option in AFPC Menu to change UNDC(under current ) setting .Secondly this is mandatory protection which update you that there is some issue in current input.
mujhe UNDC ka threshold change karna hai. kya aapke pass apfcr ki koi manual hai? @@eeebackbenchers
How to solve UNDV (alarm) problem
Simply means undervoltage : check voltage level and ensure the rated voltage at defined terminals
🎉
RMS line to line voltage worg voltage show disply why problem
Verify voltage level at APFC terminals & ensure connection should be done as per manufacturer recommendation.
Ithd alarm aa raha hai
Current harmonics is higher than 25% You should you detuned reactor or do harmonics study on your plan for better result
2500/5 ki ct h undc fault h to 0.015---0.5 me se kya seting hogi
Apft
37.5amp...ok
Nice ❤
Thankyou
👏👏
Thanks for appreciation
Sir
Default setting is : 0.015 of In hai.
Aap default setting rakh sakte h koi problem ni h
Etasmart8t k common me ac volt denge ya dc volt
Brother 8R - means you have to use normal cap duty Contactor
And 8T means it’s designed for thyristor
Use only when you have thuristor
Hello sir
how to slove UNDC
Sir
Undc means under current , means there is no sufficient current from ct
Check ct output secondary current at Apfc ct terminals and car polarity
OCOM aur UNDC alarm ki setting kaise karna hai. Kaunse menu main Jana hai
As per my best knowledge , I think there is NO option in AFPC Menu to change UNDC(under current ) setting .
Secondly this is mandatory protection which update you that there is some issue in current input.
mujhe UNDC ka threshold change karna hai. kya aapke pass apfcr ki koi manual hai? @@eeebackbenchers
How to solve UNDV (alarm) problem
Simply means undervoltage : check voltage level and ensure the rated voltage at defined terminals
🎉
RMS line to line voltage worg voltage show disply why problem
Verify voltage level at APFC terminals & ensure connection should be done as per manufacturer recommendation.
Ithd alarm aa raha hai
Current harmonics is higher than 25%
You should you detuned reactor or do harmonics study on your plan for better result
2500/5 ki ct h undc fault h to 0.015---0.5 me se kya seting hogi
Apft
37.5amp...ok