Gledhill Boilermate repair no hot water

แชร์
ฝัง
  • เผยแพร่เมื่อ 2 พ.ย. 2023
  • gledhill Boiler mate 2000 (systemmate) has no hot water. there was no voltage going to the hot water circulator. this is usually a fault with one of the hot water sensors. It is difficult to tear the sensors as they are digital so do not give the same readings as a NTC sensor. it is best to change both sensors. when working correctly the circuit board will send a variable voltage to the pump depending on the temperatures read by the sensors. #gledhill #syatemaye
  • แนวปฏิบัติและการใช้ชีวิต

ความคิดเห็น • 5

  • @alfypierri8022
    @alfypierri8022 8 หลายเดือนก่อน +1

    Thanks foe the video. I've got the pump on the left always on with no demand. Any suggestions?

    • @thornhillplumbing
      @thornhillplumbing  8 หลายเดือนก่อน +1

      the pump on the left will continue running until the thermal store is up to temperature. The boiler thermostat / flow temperature should be set to maximum.

  • @bingbongbingo22
    @bingbongbingo22 5 หลายเดือนก่อน

    I’ve just got a new acb after a boiler breakdown with no heat/hot water. it’s working now with the new acb except I’ve no hot water! Mildly warm at first then freezing cold!! Any ideas?

  • @bagdaduk
    @bagdaduk 8 หลายเดือนก่อน

    i've just had to drain my tank to replace a pump for the radiators. But not it filled up and i don't have hot water. I believe there might be a air block. how do i go about fixing it

    • @thornhillplumbing
      @thornhillplumbing  8 หลายเดือนก่อน

      You did not need to drain the tank to fit a central heating pump