Gledhill Boilermate repair no hot water
ฝัง
- เผยแพร่เมื่อ 2 พ.ย. 2023
- gledhill Boiler mate 2000 (systemmate) has no hot water. there was no voltage going to the hot water circulator. this is usually a fault with one of the hot water sensors. It is difficult to tear the sensors as they are digital so do not give the same readings as a NTC sensor. it is best to change both sensors. when working correctly the circuit board will send a variable voltage to the pump depending on the temperatures read by the sensors. #gledhill #syatemaye
- แนวปฏิบัติและการใช้ชีวิต
Thanks foe the video. I've got the pump on the left always on with no demand. Any suggestions?
the pump on the left will continue running until the thermal store is up to temperature. The boiler thermostat / flow temperature should be set to maximum.
I’ve just got a new acb after a boiler breakdown with no heat/hot water. it’s working now with the new acb except I’ve no hot water! Mildly warm at first then freezing cold!! Any ideas?
i've just had to drain my tank to replace a pump for the radiators. But not it filled up and i don't have hot water. I believe there might be a air block. how do i go about fixing it
You did not need to drain the tank to fit a central heating pump