I faced an issue with type of zamil chiller pump start and the condenser fan motors start but when the compressor start to work unit cutout and the alarm in DDC is showing (pump tripped ) ( no flow ) so I suspected that flow switch has issue or there is no enough water Do you think it’s the right cause or there is something else i mass to check Sorry for the long text
Brother, you need to check something Like Check water pressure in gauge inlet line and outline And secondly check the water flow switch is showing continuity or not, if the pump is on then continuity should be shown If pump but water flow switch not working or not showing continuity then Have 3 reasons 1 water flow switch Defective 2nd water flow switch Blade broken or damaged 3rd water pressure too low
Bahot badiya Sir. Nice explanation. Need more videos like this.
Sir, isi tarah kya aap de-coupler line bhi site par dikhakar explain kar sakte hai kya. Please. Thank you.
thank you for liking my videos
Thank you Sir nice vedio
Shukran bro & thank you too
Nice sir
Shukran bro
Good information sir
Thank for liking my video bro
Superb
Thank
Trouble shooting oprating service ke bare me pochna na h abhi naya unit installation hoa zamil company ka
salam jnab aap sawal
Comments box 📦mein puch
Lijiye number abhi nhi bhai bahut
Jyada muskil ho rha hai bahut
Jayada call aur messages
Aaraha aur sabka jawaab thora muskil
Ho rha hai so please🙏 don't mind bhai
Bhai mera skm chiller hai magnum control ka apcn5155 phase loss error a raha hai vmm accha hai ryb phase proper hai please tell me what Is the reson
Kuan sa company ka
Chiller hai?
@@HVACAMJADTROUBLESHOOT skm apcn5155 model
I faced an issue with type of zamil chiller pump start and the condenser fan motors start but when the compressor start to work unit cutout and the alarm in DDC is showing (pump tripped ) ( no flow ) so I suspected that flow switch has issue or there is no enough water
Do you think it’s the right cause or there is something else i mass to check
Sorry for the long text
Brother, you need to check something
Like
Check water pressure in gauge
inlet line and outline
And secondly check the water flow switch is showing continuity or not, if the pump is on then continuity should be shown
If pump but water flow switch not working or not showing continuity then Have 3 reasons
1 water flow switch
Defective
2nd water flow switch
Blade broken or damaged
3rd water pressure too low
Assalamualaikum sir aap ka number dijiye same zamil ka 300 ton Air cooled chiller operating kerte h please number dijiye sir
Walaikum salam jnab aap sawal
Comments box 📦mein puch
Lijiye number abhi nhi bhai bahut
Jyada muskil ho rha hai bahut
Jayada call aur messages
Aaraha aur sabka jawaab thora muskil
Ho rha hai so please🙏 don't mind bhai
Abe Bhai 11A, 11AA kaha se aa rha h
11a 11aa kaha se araha hai
Uske liye part 2