Blown Taco SR501 Switching Relay - How to Test Resistance on Taco 007 Circulator

แชร์
ฝัง
  • เผยแพร่เมื่อ 14 ต.ค. 2024
  • The resistance on a Taco 007 should be between 130-160 ohms. Out of range? Replace! Blown Taco SR501 switching relay replaced on this Burnham Independence Steam boiler SIN4. How to test resistance on circulator.
    What’s in your Veto? Here is mine:
    Veto TP-XXL amzn.to/3zX10vg
    Milwaukee M12 Fuel 1/4" Impact Driver amzn.to/3I9yLfI
    Wiha Allen Keys: amzn.to/33ipGmb
    HIKMICRO B20 amzn.to/33iGklx
    Furnace Switch amzn.to/31X89PT
    Milwaukee Light amzn.to/3I38Lmh
    Wagos amzn.to/34QoiaU
    Milwaukee Set amzn.to/33vnQOz
    Torpedo Level amzn.to/3no1oOk
    Crescent set amzn.to/3GtZeV8
    Wiha 7 piece set amzn.to/3rkISaK
    Milwaukee step bit amzn.to/3I395Bv
    Flare wrench amzn.to/3noJZ8s
    Ridgid 10” wrench amzn.to/3GvRnqa
    Fluke non-contact tester amzn.to/31VQgAQ
    Klein drivers amzn.to/3qoe21W
    Knipex Wrenches amzn.to/3trzFjS
    Klein 11-1 amzn.to/3tpsPLD
    12” crescent amzn.to/3A0CZ6S
    Gerber Gear Pocket Knife amzn.to/3foaW7I
    Yellow Jacket Hand Ratchet amzn.to/3nrDgup
    I am on Discord & WhatsApp!
    Discord: / discord
    WhatsApp Group: chat.whatsapp....
    Mikey Pipes Uncensored: / @mikeypipesuncensored
    New oval raised silver stickers are from:
    Armored Decal Company Inc.
    35 Victoria St. E, Unit 9
    Alliston, Ontario L9R 1T3
    (p) 705-435-6665
    (e) ken@armoreddecal.com
    (Tell them Mikey Pipes sent you)
    Please support this channel and Mikey Pipes and consider the following…
    Pipe Doctor long-sleeve shirts are available in Medium, Large & XL
    Minimum donation of $34 is appreciated
    Pipe Doctor FlexFit Embroidered Caps
    Minimum donation of $37 is appreciated
    (If you are international - please add a minimum of $40 for shipping/postage)
    Shopping on Amazon? Please use my referral link amzn.to/2PjjS4v
    Sticker Requests:
    Do you want a sticker to show your support of this channel? Email your request to me! mike@mikeypipes.com
    Name
    Address
    City, State, Zip
    Consider making a donation of $5.00, or ANY amount, to the postage fund! I literally mail out stickers all over the globe. I've sent stickers to HVAC guys in Afghanistan, New Zealand & all over Europe.
    PayPal is: office@pipedoc.net
    Venmo: @PipeDoctor
    CashApp: $mikeypipesny
    Want to send a love letter, note or gift? Our mailing address is:
    Mikey Pipes
    C/O Pipe Doctor Plumbing
    80 E Hawthorne Ave
    Valley Stream, NY 11580
    #Taco #Relay #Circulator

ความคิดเห็น • 68

  • @larryboy8821
    @larryboy8821 2 ปีที่แล้ว +3

    A little KR. Bailed out of California in January, the place has gone insane. Retired early to Nebraska, found Mikey Pipes because I didn't know anything about boilers, water softeners and RO systems. I do now! Thanks Pipes!!

    • @Lewdacris916
      @Lewdacris916 2 ปีที่แล้ว +1

      wish i could leave the state but all my family and friends are here! definitely wont be able to retire here with the way the housing market is going!

  • @eddiew.6485
    @eddiew.6485 2 ปีที่แล้ว +2

    I was digging your conversation with the Homeowner…….wished there was more! 😎
    Nice job as always, Mikey👍

  • @brucerobak145
    @brucerobak145 2 ปีที่แล้ว +7

    A thought. Use a temporary power cord to test each circulator motor seperately first before removing the circulator control.
    Doing this you'll isolate the parts to find where the problem is, be it with the circulators or circulator control. Noisy circulator bearings, impeller problem, shorts in the motor or wiring will be revealed. Isolate and divide up the components to find the problem to conquer it.

  • @georgiamurray1878
    @georgiamurray1878 2 ปีที่แล้ว

    Getting better and better all the time

  • @papascoobs4096
    @papascoobs4096 2 ปีที่แล้ว +7

    Sigh...This is what happens when plumbers play with electrical.I was screaming at the screen "MIKEY THE FUSE LOOK AT THE FUSE, DONT TAKE IT OFF MIKE"!!!But to your credit you found it in the end.

  • @johncavaco6491
    @johncavaco6491 2 ปีที่แล้ว +2

    It depends if the capicator is charge. Take capicator out of the circuit to read the motor windings.

  • @tomdube971
    @tomdube971 2 ปีที่แล้ว +1

    I’m trying to figure out the reason for the hot plate heat exchanger. Is there glycol in that zone or what? Maybe that zone is used to melt snow on the sidewalk? And while you’re talking finance with the customer you should have Peter pipe those relief valves to the floor

  • @charliewest5377
    @charliewest5377 2 ปีที่แล้ว +1

    My friend Thanks for sharing this

  • @realestateservicessaleshea99
    @realestateservicessaleshea99 2 ปีที่แล้ว

    Did you charge him for the conversation 🤔 🤣🤣🤣😎
    Thanks again for the videos!
    Stay safe.
    Retired (werk'n)keyboard super tech. Wear your safety glasses!

    • @ATSNorthernMI
      @ATSNorthernMI 2 ปีที่แล้ว +1

      At least an hour. If it's not a full hour, just bullshit until it gets there. That way you don't charge the customer for an extra hour and it only being 20 minutes in.

  • @pabloolivas5197
    @pabloolivas5197 ปีที่แล้ว

    Hello Mikey..
    I have a situation that room temperature rises above the thermostat setting. For example, it's 75 (and rising) while the thermostat setting is 70. I found that the Taco SR501 red indicator light (call for heat) is always on, with or without the thermostat connected to the system. So I think the problem is not the thermostat but rather the Taco SR501 switch relay. To control temperature, I have to manually switch off the power to the heating system. What could cause the red indicator light on all the time? How do I know for sure that the Taco SR501 relay is the problem? Thanks for your insights.

  • @bobcat138
    @bobcat138 2 ปีที่แล้ว

    So you show hot on the white wire using the no contact tester ? Or maybe I saw it wrong on the vid

  • @throttlebottle5906
    @throttlebottle5906 2 ปีที่แล้ว

    a good inspector would catch the lack of relief valve on the hydronic loop. but most of them would be too busy flagging and writhing over multiple other issues to even notice.

  • @isobelmason1069
    @isobelmason1069 2 ปีที่แล้ว

    You have the best ideas

  • @petem6291
    @petem6291 2 ปีที่แล้ว

    Mike , it would’ve been Interesting to see how many amps the bad motor was drawing ?? Being that you work with the 007 all the time it would be good to know what a good amp draw is I guess you could test a few of them When there are new and when they have been in service…

    • @throttlebottle5906
      @throttlebottle5906 2 ปีที่แล้ว

      the max allowable current draw is on the rating plate and in manuals/documentation. the actual current draw varies with feet of head (flow resistance), it should never be above the rating on the tag/manual, per circulator.

  • @kennethbailey2616
    @kennethbailey2616 9 หลายเดือนก่อน

    We don’t have a sales tax here in Montana.

  • @libbyjames4513
    @libbyjames4513 2 ปีที่แล้ว

    Thank you so much for sharing

  • @annemacomber9736
    @annemacomber9736 2 ปีที่แล้ว

    stupendaaaa,Super ! You are so striking!

  • @duwayneodom1297
    @duwayneodom1297 2 ปีที่แล้ว

    @mikeypipes you look like a discount Kurt Russell 😂

  • @atlasfueloilinc.2421
    @atlasfueloilinc.2421 2 ปีที่แล้ว

    Still only circulating the mud on the bottom of the boiler. Which is also the coolest water.

  • @marionbaker7424
    @marionbaker7424 2 ปีที่แล้ว

    With much respect..you are fantastic...and you are stunning

  • @victoriasaunders2342
    @victoriasaunders2342 2 ปีที่แล้ว

    I Love the look

  • @careydecker4427
    @careydecker4427 2 ปีที่แล้ว

    Yes love it

  • @chriscurran416
    @chriscurran416 2 ปีที่แล้ว +1

    Hi mike about 200/220 ohms on circulator

    • @chriscurran416
      @chriscurran416 2 ปีที่แล้ว

      Bearing im in uk voltage here is higher than 110 in the states so i would say 130-150 states

  • @karrierace8661
    @karrierace8661 2 ปีที่แล้ว

    Nice video you have there

  • @teresaoehler9309
    @teresaoehler9309 2 ปีที่แล้ว

    Pleasant video

  • @ATSNorthernMI
    @ATSNorthernMI 2 ปีที่แล้ว

    Probably not a bad idea to change the control relay just to eliminate a potential problem later on down the road.

  • @mikeobrien9404
    @mikeobrien9404 2 ปีที่แล้ว

    Should there be a strainer on the entering side of each side of the plate type heat exchanger.

    • @throttlebottle5906
      @throttlebottle5906 2 ปีที่แล้ว

      yes, but those clog very fast in such service. it shouldn't pull off the very bottom of boiler, it should come from an elevated tapping below operating water level and above the bottom, then return into the very bottom or close. most have specific tapping's just for feeding heating loops, usually listed and labeled for domestic hot water indirect tanks.

    • @mikeobrien9404
      @mikeobrien9404 2 ปีที่แล้ว

      @@throttlebottle5906 So it is better to change the heat exchanger the clean strainers

  • @StephenWolver
    @StephenWolver 2 ปีที่แล้ว +1

    Just a reminder current=voltage/resistance. If the motor resistance is 200+ ohms it draws less current than at 160 ohms.

    • @throttlebottle5906
      @throttlebottle5906 2 ปีที่แล้ว

      that's an AC motor though, so throw out much of what you know for DC circuits, because impedance and other factors throw a huge monkey wrench in there, far more math and data needed 😵

  • @rosehunt6158
    @rosehunt6158 2 ปีที่แล้ว

    lovely video

  • @johng1077
    @johng1077 2 ปีที่แล้ว

    You aren’t double taxed if you remember you said you pay the difference from what you had already paid when you bought the part. I am surprised NY done;t have tax resale certificate it it probably one of the most widely used things for resellers along with NEXUS. Connections with particular taxing jurisdiction.

  • @atlasfueloilinc.2421
    @atlasfueloilinc.2421 2 ปีที่แล้ว

    I always wondered how you got out of a customer’s house before they started talking to you.

  • @pamelaojeda8879
    @pamelaojeda8879 2 ปีที่แล้ว

    Bravo

  • @snidelywhiplash8923
    @snidelywhiplash8923 2 ปีที่แล้ว

    What's the purpose of the heat exchanger?

    • @snidelywhiplash8923
      @snidelywhiplash8923 2 ปีที่แล้ว

      @@PipeDoctor I understand what a heat exchanger is, even an in-room radiator can be described as a heat exchanger. My question, and sorry if poorly worded, is ----why is this heat exchanger here, what purpose is it used for this home? Is its use here typical of what's done with other home HVAC systems in your area? Thanks.

    • @MrDmadness
      @MrDmadness 7 หลายเดือนก่อน

      ​@@snidelywhiplash8923separates system glycol in the heat loops from boiler primary loop, if there was a rupture on the radiator the boiler doesn't go down

    • @snidelywhiplash8923
      @snidelywhiplash8923 7 หลายเดือนก่อน

      @@MrDmadness In the first 60 seconds of the video, MP says points to a pump on the heat exchanger and says it's circulating water to the basement zone.
      Why would a house occupied presumably 12 months of the year need to have glycol circulating in some radiant zones?

    • @MrDmadness
      @MrDmadness 7 หลายเดือนก่อน

      @@snidelywhiplash8923 because proper glycol levels will not allow the zone to freeze in the case its not used and it gets cold, it's very common in high mass and baseboard heating applications. Glycol also prevents internal corrosion as its an oil so not oxidizing due to the water. The caveat is that it can jelly up if left un circulating too long

  • @ednadean7984
    @ednadean7984 2 ปีที่แล้ว

    love

  • @miketimmins697
    @miketimmins697 2 ปีที่แล้ว

    Kurt Russell ... YES !

  • @gordonfrancis4039
    @gordonfrancis4039 10 หลายเดือนก่อน

    1st brass circulator 2 strainer 3 insulation fiberglass on the piping 4 you used black pipe on your relief valve biggest no no

  • @aliciagriffin9560
    @aliciagriffin9560 2 ปีที่แล้ว

    CHEERS!!

  • @demijenkins9486
    @demijenkins9486 2 ปีที่แล้ว

    Süper Off

  • @patmcnally6
    @patmcnally6 2 ปีที่แล้ว

    No Mike you do not look like Kurt Russell but You can take the lead Part in ESCAPE FROM THE STATE OF INSANITY.

  • @hollydavidson5219
    @hollydavidson5219 2 ปีที่แล้ว

    Superlike

  • @joseph-ine452
    @joseph-ine452 ปีที่แล้ว

    Sweet potatoes that was long video.

  • @scotts4125
    @scotts4125 2 ปีที่แล้ว

    You can't have him. Gov. DeSantis that is. We love him.

  • @jimmyjamesl2318
    @jimmyjamesl2318 2 ปีที่แล้ว +1

    completely wrong about how resale tax works

  • @dorothygoff3224
    @dorothygoff3224 2 ปีที่แล้ว

    T O P

  • @macinieves3863
    @macinieves3863 2 ปีที่แล้ว

    Good

  • @reedjr5281
    @reedjr5281 2 ปีที่แล้ว +1

    200ohms

  • @melissalawrence4465
    @melissalawrence4465 2 ปีที่แล้ว

    ohhhhhh God So beautiful

  • @Hvac-dude
    @Hvac-dude 2 ปีที่แล้ว

    THE resistance should be 0.3 and 2 ohms

  • @lisaholliman6097
    @lisaholliman6097 2 ปีที่แล้ว

    "Strong"

  • @katysalter2021
    @katysalter2021 2 ปีที่แล้ว

    Immensely killer